background image

V E N T I L A T I O N

LAB1306R, Issue 1, March 2018 

Page 1

SPR418

Bluebrain Controller

Installation and

Operating Instructions

It is important to follow the advice in this manual and

correctly maintain the system to ensure a healthy

indoor environment.

Summary of Contents for Bluebrain

Page 1: ...1306R Issue 1 March 2018 Page 1 SPR418 Bluebrain Controller Installation and Operating Instructions It is important to follow the advice in this manual and correctly maintain the system to ensure a he...

Page 2: ...appliance Cleaning and user maintenance shall not be made by children without supervision 3 All wiring must be in accordance with the current IEE Wiring Regulations BS7671 The electrical installation...

Page 3: ...V E N T I L A T I O N LAB1306R Issue 1 March 2018 Page 3 Page 16 1 0 User control interface operation User control interface front view User control interface back view Day...

Page 4: ...DAY The hour text will flash Use the and buttons to set the hour Press DAY The minute text will flash Use the and buttons to set the minute Press DAY The day will flash Use the and buttons to set the...

Page 5: ...ic bypass operation Press COPY four times to move to Menu 7 IhuN Use the or button to set to off OF This action inhibits the automatic humidity controlled boost operation Press SET to return to the ho...

Page 6: ...ow speed cannot be set higher than Boost speed and Boost speed cannot be set higher than Max speed Press SET to record or ESC to discard the settings and return to the home screen 1 4 Automatic heat e...

Page 7: ...Press COPY as required to move to Menu 1 Filter Use the or buttons to change the time delay in steps of 50 hours as required or off Note The filter check reminder is factory set at the maximum of 3000...

Page 8: ...Use the or button to set to on or off Note The Delay on function will always be overridden by automatic humidity sensing Press SET to record or ESC to discard the settings and return to the home scree...

Page 9: ...and is adjustable between 15 C and 25 C Factory default 20 C Use the or buttons to set the operating temperature in steps of 1 C Press SET to record or ESC to discard the settings and return to the h...

Page 10: ...squares indicate a time period where the unit is in automatic bypass mode i e the unit will monitor the temperatures and open or close the bypass accordingly White squares blank spaces indicate a time...

Page 11: ...g PROG the day number will be displayed and then the day to copy to by pressing the and buttons the day number will flash When the two correct days have been selected press COPY and the timeline patte...

Page 12: ...actory settings P1 t3 20 C t4 10 C Humidity 60 Filter 3000 hours Fan 1 Low 20 Fan 1 Boost 50 Fan 1 Max 80 Fan 2 Low 20 Fan 2 Boost 50 Fan 2 Max 80 Bypass temp off T5 Delay on off Delay off off Hum on...

Page 13: ...LAB1199R Issue 4 Apr 2017 Page 25 V E N T I L A T I O N LAB1306R Issue 1 March 2018 Page 13...

Page 14: ...isolated before removing covers to electrical connections Fault Checks and possible solutions Nothing displayed on the controller LCD screen Check there is power connected to the unit Presence of an o...

Page 15: ...ct connection check there is nothing obstructing fan 2 Little or no air is extracting or supplying through the room valves Check that the filters have been removed from the pre commissioning protectiv...

Page 16: ...715523 Web www domusventilation co uk E OE V E N T I L A T I O N V E N T I L A T I O N Domus Ventilation Cambria House Caerphilly Business Park Van Road Caerphilly CF83 3ED Tel 44 0 3443 715523 Fax 44...

Reviews: