Dometic ASCDU15HV 1161 Installation And Operation Manual Download Page 4

4

EN

General Information 

Universal Air Conditioning Unit

 

WARNING: EXPLOSION HAZARD . Failure to 
obey these warnings could result in death or 
serious injury .

•  Avoid puncturing or breaking the unit or any of the 

unit’s tubing.

•  When installing this equipment, always observe 

precautions described in the literature, tags, and 
labels attached to the unit.

•  Follow all safety codes.

•  Wear safety glasses and work gloves and place a fire 

extinguisher close to the work area.

•  Failure to follow these guidelines could result in a 

system rupture that would release high-pressure gas 
and airborne shrapnel.

NOTICE: 

Improper installation or misunderstood 

operating procedures can result in unsatisfactory 
performance and/or premature failure of these units.

2  General Information

This section provides general information about 
the refrigerant used in this system and the general 
information regarding the unit.

The images used in this document are for reference 
purposes only. Components and component locations 
may vary according to specific product models. 
Measurements may vary ±0.38 in. (10 mm).

2 .1  R-410A Reference Information

This section provides information regarding the type of 
refrigerant used in this air conditioning unit.

•  This system uses R-410A refrigerant.

•  R-410A is an environmentally safe hydrofluorocarbon 

(HFC) refrigerant.

•  R-410A refrigerant operates at a higher pressure 

than R-22. Ensure that the servicing equipment and 
replacement components used are designed to 
operate with R-410A.

 

I

Refer to the service manual for this unit for more 
information on R-410A refrigerant.

2 .2  Q3 Control Standard Features

This list provides the functions that are standard for the 
Q3 control when used with the ASCDU15HV 1161.

•  115 Volt, 60 Hz AC power supply
•  User-friendly, four-button display panel
•  Option to display temperature in degrees Fahrenheit 

or Celsius

•  Programmable functions
•  Non-Volatile Memory (NVM) requires no backup 

power

•  Switch inputs for high/low refrigerant pressure
•  Time function (away mode)
•  Anti-icing cycle prevents evaporator icing
•  Programmable fan operation
•  Programmable display brightness
•  Air-filter cleaning or replacement timer
•  Low-voltage monitor

 

I

An optional outside temperature sensor is available 
for this unit.

2 .3  Product Data Plate

MFG NO.

710015113

921053890

9600005548

DESCRIPTION

CAP. (BTU)

VOLTAGE/HERTZ

PHASE

MAX. FUSE

MIN. FUSE

FLA. COOL

FLA. HEAT

ASCDU15HV1161  2.5KW 115/60/1 

15000

FAN

5.92

OPERATE AT 60HZ ONLY

VOLTAGE - 104 MIN. 126 MAX. FREQ-57-63HZ.

L.R.A.

69.8

tCO2e

2.25

GWP

2088

OIL

DIAGRAM

PATENT(S):

Assembled in USA

DPEV02

2000 NORTH ANDREWS AVE
POMPANO BEACH, FL  33069  USA
954-973-2477  WWW.DOMETIC.COM

DOF700

POE

340494

REFRIG. --- OZ/GRAMS

R410A 38/1078

115*

1

40

30

25.7

24.3

SHOP ORDER

PROD NO.

SERIAL NO.

SKU NO.

w

q

Data Plate

q

 Amp Draw Cool and Heat

w

 Weigh-In Charge

Summary of Contents for ASCDU15HV 1161

Page 1: ...S AIR CONDITIONER L 5005 Form No 340813 20200305 2020 Dometic Corporation AUTO DEHUMIDIFY ASCDU15HV 1161 Q3 Control EN Universal Self Contained Air Conditioning Unit and Q3 Control Installation and Op...

Page 2: ...9 Installing the Optional Outside Air Temperature Sensor 13 6 10 Start Up Checklist 14 7 Operation 15 7 1 Understanding Button Functions 15 7 2 Normal Heating or Cooling Cycle 16 7 3 Modes and Progra...

Page 3: ...tand these instructions before installing or operating this product The installation must comply with all applicable local or national codes including the latest edition of the following standards U S...

Page 4: ...luorocarbon HFC refrigerant R 410A refrigerant operates at a higher pressure than R 22 Ensure that the servicing equipment and replacement components used are designed to operate with R 410A I IRefer...

Page 5: ...ressor Start Capacitor yHigh Pressure Switch HPS 1 Compressor Run Capacitor uLow Pressure Switch LPS 1 Evaporator Blower Capacitor i10 ft 3 m Interconnect Cable 2 Condenser Blower Capacitor oElectrica...

Page 6: ...able Functions Ranges and Factory Defaults on page 18 12 Off Mode Indicator Lights when the system is off Note that the Data Display remains on You can continue to adjust the set point display reading...

Page 7: ...esulting from mechanical influences and excess voltage Alterations to the product without express permission from the manufacturer Use for purposes other than those described above Dometic Corporation...

Page 8: ...4 18 38 in 46 cm 5 20 37 in 51 cm 6 20 13 in 51 cm Evaporator Side View 7 17 75 in 45 cm 8 14 88 in 38 cm 4 3 Electrical Box Dimensions i t u y r e w q d f o s a Top Front Side 5 Electrical Box Dimen...

Page 9: ...udes the drill and cut template P N 086812 4 5 Cable Lengths Description Size Display Cable 15 ft 5 m Typical Indoor Air Sensor 15 ft 5 m Standard on Self Contained Systems Outside Air Sensor optional...

Page 10: ...9 7 2 10 18 19 11 3 1 6 17 16 5 4 12 13 15 14 8 19 2 7 18 10 9 17 6 1 3 11 12 4 5 16 15 13 14 2 IF PRESENT ON BOARD JUMPER CSNB MUST BE CUT WHEN USING A CONTACTOR OR SOLID STATE RELAY ON THE COMPRESS...

Page 11: ...icing Dometic equipment to prevent any loss of refrigerant Failure to obey this caution could result in minor or moderate injury NOTICE This product contains R 410A fluorinated greenhouse gas in seale...

Page 12: ...oper use and may cause damage to the electrical components I IConnect the wiring as per the wiring diagram located on the unit 1 Connect the vehicle s power supply to the unit 2 Install a ground fault...

Page 13: ...lug the cable into the port labeled INSIDE on the circuit board located in the electrical box 6 8 Installing the Q3 Control 1 Plan the location of the display using the drill and cut template P N 0868...

Page 14: ...including the main power supply tight Y N 6 10 2 Starting the Unit 1 Turn the circuit breaker for the air conditioner to the On position 2 Turn the control on 3 Use the Q3 control to set the system f...

Page 15: ...refrigerants must by law be reclaimed If an indoor leak is suspected thoroughly ventilate the area before beginning work Never burn refrigerant as poisonous gas will be produced Always follow EPA gui...

Page 16: ...n operation When in Auto fan mode the fan speed will return to low speed once the set point temperature has been satisfied and the cooling or heating cycle has ended 7 3 Modes and Programmable Functio...

Page 17: ...inside temperature If inside temperature is greater than 99 F 37 C or less then 0 F 17 C the display shows either 99 F 37 C or 0 F 17 C respectively as the maximum or minimum inside temperature 7 3 7...

Page 18: ...C 2 31 4 Fan Response Differential 8 8 8 1 F 0 6 C 2 31 5 Low Fan Speed 38 2 57 6 High Fan Speed 85 41 99 7 Fan Mode C Continuous C Continuous I Intermittent 8 AC Line Voltage Calibration Plus or min...

Page 19: ...e delay before the display shows readings If an attempt is made to change the five minute time delay the changes will not be recognized by the system 2 Fahrenheit Celsius or Auto Selection Select F fo...

Page 20: ...antly The high fan speed adjustment allows you to set the maximum high speed voltage to the threshold of the blower high speed response The Q3 control system divides the fan speed voltage steps into f...

Page 21: ...boats For very humid climates shorten the overall time period and extend the dehumidification time In dry climates select a longer overall time period between cycles and a shorter dehumidification ti...

Page 22: ...and the display will show OA closed circuit if the high pressure switch circuit is OK or FA open circuit if the high pressure switch circuit has a fault or system is overcharged or has loss of condens...

Page 23: ...in aux heat heat mode I IWhen you enable the aux heat heat function h1 the fan will delay turning off for 30 seconds to allow the auxiliary heater to cool down The delay occurs when the auxiliary heat...

Page 24: ...faults on page 18 3 Press the Mode button to access the programmable value of the displayed function number The function s current value flashes on the display 4 Press the Up or Down buttons to change...

Page 25: ...reduced There is low airflow through the system The airflow through the evaporator is blocked Inspect for and remove any obstructions in the return air stream Clean the return air filter and grille C...

Page 26: ...oad is open due to lack of air flow though the condenser Allow the compressor to cool Turn the system off for a while it may take up to three hours to reset the thermal overload 10 2 Digital Controls...

Page 27: ...before reprogramming the Q3 control Change Programmable Function 21 to increase the duration of the Anti Icing Routine If the anti icing cycle does not melt the ice switch the air conditioning unit t...

Page 28: ...ntrol board The low pressure switch opens when the suction pressure drops below a preset minimum limit If the low pressure switch opens the unit will first run for two minutes and then shut down for 5...

Page 29: ...conds the Q3 control shows a constant Cool or Heat Mode may be selected for emergency operation and the display will show a constant Emergency Operation Ar FL The Q3 control flashes Ar FL for 15 secon...

Page 30: ...aning the Return Air Filter Check the Return Air Filter once a month or more often if local conditions and usage patterns dictate and replace or clean as necessary To clean the filter Remove the filte...

Page 31: ...coils may result in reduced performance Avoid the use of the following Coil brighteners High pressure washers Poor quality water for cleaning Use of non recommended coil cleaners is strongly discoura...

Page 32: ...Mobile living made easy dometic com YOUR LOCAL DEALER dometic com dealer YOUR LOCAL SUPPORT dometic com contact YOUR LOCAL SALES OFFICE dometic com sales offices...

Reviews: