8

INSTALLATION INSTRUCTIONS DUCTED  CCC

Register Required

C. AIR DISTRIBUTION DUCT INSTALLATION

1. Install the Air Distribution Ducts in the RV Roof Cavity. The Distribution System must meet:

a. RV’s requirements
b. System requirements listed in Section 4 on page 6 of this Manual. Terminate the start of the Duct at the back edge

of the 14-1/4" x 14-1/4" (±1/8")  opening previously cut. See FIG. 2, 3, & 4.

FRAME

14-1/4" (±1/8”)

OPENING

AC POWER
SUPPLY WIRE

DUCT

FRAME

DUCT

ROOF

INSULATION

DUCT

CEILING

DUCT

14-1/4" (±1/8”)

OPENING

INSULATION

SIDE VIEW

(TOWARD BACK OF RV)

TOP VIEW

(BACK OF RV)

LOW VOLTAGE WIRES:

12VDC
Furnace
Load Shed
Sensors

FRAME

CCC, CONTROL CABLE(S)
or 7-Wire Analog Cable

FIG. 2

FIG. 3

FIG. 4

Duct Size And Requirements For 3105007.XXX And 3105935.XXX Return Air Cover

Duct Size And Requirements For 3308120.XXX Genesis Air Filtration System

Total Outlet Air Area
Minimum 21.0 Sq. In.

Total Outlet Air Area
Minimum 32.0 Sq. In.

Register Required

Register Required

Register Required

Register Required

Register Required

Register Required

Register Required

Roof
Rafters

Roof
Rafters

Note: Duct Size is Inside Dimensions

Note: Duct Size is Inside Dimensions

Short Duct Run Minimum
1/3 Total Duct Length

Short Duct Run Minimum
1/3 Total Duct Length

Ducts

Min.

Max.

Depth

1-1/2”

2-1/2”

Width

7.0”

10.0”

Total Length

15.0’

40.0’

Ducts

Min.

Max.

Depth

2.0”

2-1/2”

Width

8.0”

10.0”

Total Length

15.0’

40.0’

Registers
8 Min.-- 12 Max.
(Per Unit)
14 Sq. In Free Area
Per Register

Registers
8 Min.-- 12 Max.
(Per Unit)
14 Sq. In Free Area
Per Register

14-1/4" x 14-1/4" (±1/8")

Roof Opening

14-1/4"x14-1/4" (±1/8")

Roof Opening

Summary of Contents for 57908.321

Page 1: ...ic Control Kit Ducted 59136 531 59136 536 59136 621 59136 631 59516 303 59516 331 59516 336 59516 501 59516 531 59516 536 59516 601 59530 632 600312 321 600315 326 600312 421 600315 321 600315 421 630...

Page 2: ...erature For a more permanent solution to high heat gain accesso ries like A E outdoor patio and window awnings will reduce heat gain by removing the direct sun They also add a nice area to enjoy compa...

Page 3: ...1 3 62 0 2 5 5 8 325 250 0 55 0 90 16 0 20 Amp 94 3 5 KW 5 0 KW 57915 621 13 500 11 0 54 4 2 5 5 8 325 250 0 55 0 90 16 0 20 Amp 94 3 5 KW 5 0 KW 57915 622 13 500 11 0 54 4 2 5 5 8 325 250 0 55 0 90 1...

Page 4: ...31 N A 8 0 48 3 2 0 5 6 325 250 0 40 1 10 19 0 15 Amp 94 3 5 KW 5 0 KW 59530 531 N A 7 8 53 0 2 0 5 6 325 250 0 40 1 10 19 0 15 Amp 94 3 5 KW 5 0 KW 59530 532 N A 8 0 53 0 2 5 5 8 325 250 0 40 1 10 18...

Page 5: ...front to back and centered from side to side B For Two Unit Installations Install one air conditioner heat pump one third and one airconditioner heatpumptwo thirdsfromfrontofRVand centered from side t...

Page 6: ...ductwork will not collapse or bend during and after the installation Dometic Corporation will not be liable for roof struc tural or ceiling damage due to improperly in sulated sealed or collapsed duc...

Page 7: ...be electrical wiring between the roof and the ceiling Disconnect 115 volt AC power cord and the positive 12 volt DC terminal at the supply battery Failure to fol low this instruction may create a sho...

Page 8: ...Duct Size And Requirements For 3105007 XXX And 3105935 XXX Return Air Cover Duct Size And Requirements For 3308120 XXX Genesis Air Filtration System Total Outlet Air Area Minimum 21 0 Sq In Total Outl...

Page 9: ...dedicated 12VDC supply line 18 to 22 AWG from the RV s converter or battery to the roof opening a This supply line must be located in the front portion of the 14 1 4 x 14 1 4 1 8 opening b Make sure t...

Page 10: ...V AC REAR A C 115V AC REAR A C 4 CONDUCTOR CONTROL CABLE 4 CONDUCTOR CONTROL CABLE 115V AC FRONT A C 115V AC FRONT A C FURNACE 2 WIRES FURNACE 2 WIRES DOMETIC COMFORT CONTROL CENTER DOMETIC COMFORT CO...

Page 11: ...f the air conditioner and pull the unit electrical cord down for later installation See FIG 11 AC Power Supply Pull Electrical Cord Down Roof Gasket FIG 11 Disconnect 115 volt AC Failure to follow the...

Page 12: ...nterTM CCC cable previously terminated see Section 6 B Control Cable into one of the control cable leads out of the air conditioner Either one of the two 2 control cables can be used 6 Connect the rem...

Page 13: ...sive The foam divider should be level with the ceiling 1 4 Tear off the excess at the pre cut perforations in divider See FIG 13B 2 Peel the paper off of the foam divider and stick it in place on the...

Page 14: ...ed See FIG 16B for Brisk Air unit and Fig 17B for Penguin units FIG 15A Installing unit with 3308120 XXX Genesis Air Filtration System continued on page 15 column B FIG 16A If bolts are left loose the...

Page 15: ...luminum foil tape not supplied to seal the ends of the foam divider to the sides of the opening Make sure the area behind the flange on the ceiling template is sealed See FIG 18B FIG 18B Use Aluminum...

Page 16: ...t power be supplied to the air conditioner and check for proper operation Refer to Operating Manual or User s Guide for a description of the air conditioner operation Installing unit with 3308120 XXX...

Page 17: ...e shortened by placing the Differential dip switch in the ON position Note Setting the Differential dip switch should only be required when the installation conditions are less than desirable and is n...

Page 18: ...579 590 591 595 600 630 579 590 591 595 600 630 509 S POPLAR ST 509 S POPLAR ST LAGRANGE IN 46761 LAGRANGE IN 46761 115VAC 60Hz 1 O 115VAC 60Hz 1 O 60 HZ 1 O 60 HZ 1 O 3106515 020 USE COPPER USE COPPE...

Reviews: