Dometic 3241.301 Installation & Operating Instructions Manual Download Page 9

9

MAINTENANCE

A.  Air Filter

 

1.  Periodically (a minimum of every 2 weeks of opera-

tion) slide out the return air filters located on the 

end of the air distribution box. Wash the filters with 

soap and warm water, let dry and then reinstall.

Note:

 To insure easy future removal the filters need to be 

replaced with the domed side of their handle positioned 

towards the ceiling.

Note:

 Never run the unit without both return air filters in 

place. This will plug the unit evaporator coil with dirt and may 

substantially degrade the performance of the unit over time.

B.  Air Distribution Box Housing

 

1.  Clean air distribution box housing and control panel 

with a soft cloth dampened with a mild detergent. 

Never use furniture polish or scouring powders.

C.  Fan Motor

 

 

1.  The blower motor is factory lubricated and requires 

no service.

D.  Frost Formation On Cooling Coil 

 

1.  Frost on a small portion of the coil is not unusual. 

Under  certain  conditions,  ice  may  form  on  the 

evaporator coil. This is indicated by very cold output 

at very low air speed and the icing can be seen 

through the air inlet holes with the filters removed. If 

this should occur, inspect the filter and clean if dirty. 

Make sure air vents are open and not obstructed. 

Units have a greater tendency to frost when the 

outside temperature is relatively low. This may be 

prevented by adjusting the thermostat control knob 

to a warmer setting (counter clockwise). Should 

frosting continue, operate on any 

FAN

 

ONLY

 setting  

until the cooling coil is free of frost; then resume 

normal operation. If frost condition persist, contact 

your local service center for assistance.

 

2.  On Outdoor Coil While Heating

 

a.  Operation at low outdoor temperatures causes 

low coil temperatures. This can result in ice 

forming on the out door coil in certain conditions. 

This is indicated by reduced heat output and 

could fully stop fan rotation in extreme condi-

tions. To avoid this the system controls turn off 

the compressor if out door temperature 

 

drops below 5.6° C. and returns heating when 

the temperature raises 2.8° C.

SERVICE-UNIT DOES NOT OPERATE

If your unit fails to operate or operates improperly, check 

the following before calling your service center.

A.

  If  Caravan  connected  to  motor  generator,  check  to 

be  sure  motor  generator  is  running  and  producing 

power.

B.

  If Caravan connected to power supply by a land line, 

check to be sure line is sized properly to run unit load 

and it is plugged into power supply.

C.

  Check your fuse or circuit breaker to see if it is open. 

Insure fuse is not burnt, or circuit breaker is "ON" and 

not activated.

D.

  After the above checks, call your local service center 

for further help. This unit must be serviced by qualified 

service personnel only.

E.

  If  any  wiring  or  supply  cord  is  damaged  and

needs  to  be  replaced,  it  must  be  replaced  by  the 

manufacturer or its service agent or a similarly quali-

fied person.

F.

  When calling for service, always give the following:

 

1.  Unit type and serial number found on identification 

label located on base pan of unit bottom. (Remove 

filter and view through network of holes) 

 

2.  Air distribution box model and serial number found 

on rating plate located on ceiling template. Observe 

this rating plate through the air distribution box right 

side vent opening.

G.

 

Heater Element thermal reset (Type 3241 only) may 

be performed by qualified personal with an electrically 

insulated probe. See FIG. 18. The unit is disassembled 

from above to facilitate this. The unit should be reviewed 

at the time of reset to insure air flow is not blocked and 

motor is functioning properly. Disconnect the 220 - 240 

VAC power supply prior to performing this reset.

Disconnect 220 - 240 VAC. Failure to follow 

these instructions could create a shock haz-

ard causing death or severe personal injury.

FIG 18

Summary of Contents for 3241.301

Page 1: ...THIS UNIT INFORMATION FOR FUTURE REFERENCE Type Number Product Number Serial Number ADB Number ADB Serial Number Date Purchased This manual must be read and understood before installation adjustment s...

Page 2: ...p 3 Powerwhentheunitstartsmustbeabove198VAC and the frequency must be 50 Hz at all times D The ability of the air conditioner to maintain the de sired inside temperature depends on the heat gain of th...

Page 3: ...is unit installa tion 2 The manufacturer will not be liable for any dam ages or injury incurred due to failure in following these instructions 3 The equipment shall be installed in accordance withnati...

Page 4: ...ay create a shock hazard causing death or severe personal injury FIG 3 Dimensions Are Nominal Dimensions Are Nominal 70 mm overall depth 635 mm 508 mm Front 76 mm 125 mm 130 mm 76 mm 362 mm x 362 mm 3...

Page 5: ...placed with type Y attachments if done by qualified personal Thisunitweighsapproximately45Kilograms Topreventbackinjury useamechanicalhoist to place unit on roof Do not slide the unit This may damage...

Page 6: ...pter tabs into the ceiling template See FIG 11 3 Pin Heater Connector If Electric Heat Installed FIG 9 9 Pin Connector Control Box Return Air Opening Discharge Opening Remove Liner From Foam Tape Fron...

Page 7: ...End Of ADB To Ceiling Push Here To Engage Latches Then Remove Labels Auxiliary Screw Locations Auxiliary Screw Locations FIG 15 Install 2 Primary Mount Screw First Strain Relief b Tighten the strain r...

Page 8: ...2 3 minutes before turning on the unit This allows the refrigerant pressures in the unit system to equalize so the com pressor may restart B Cooling Operation Blue Graphic 1 Setthethermostatatthedesi...

Page 9: ...ed heat output and could fully stop fan rotation in extreme condi tions To avoid this the system controls turn off the compressor if out door temperature drops below 5 6 C and returns heating when the...

Page 10: ...10 ROOF MOUNT ASSEMBLY Rear Air Conditioner Heat Pump AC HP Discharge Duct Ceiling Template With Metal Brackets Mounting Bolts Air Distribution Box ADB Roof Opening FIG 19 Duct Adapter Vents Filter s...

Page 11: ...51 5 75 7 127 21 620 02 6 211 725 72 21752 6 02725 20 7 8 67 57 51 75 51 51 6 5 2 7 8 7 3 66 2035 6625 7 31 37 5 203 20 50 3 1 3 1 5 3 7 31 7 7 5 7 51 5 67 57 66 67 127 21 620 02 6 127 21 620 02 6 5 1...

Page 12: ...2 6 67 57 3 353 3 66 75 7 5 25 353 20 50 203 3 31 37 5 25 7 353 1 1 211 725 1 7 31 51 7 7 1 3 6 5 2 2035 6625 5 9 56 1 9 9 7 8 31 8 0 17 7 7 67 7 51 51 8 5 20 51 7 02725 9a 86 233 5 21 8 7256 21 5 1 7...

Reviews: