domat UC905 Quick Start Manual Download Page 2

 

08/2018 Subject to technical changes. 

domat UC905 

Communication 

RS485, Modbus RTU,  

selectable speed 1200 ... 115200 bps 

SW 

ModComTool 

Temperature measuring range 

-

20 ÷ 70 °C

 

(accuracy ±1 ˚C) 

 

Humidity measuring range 

10 ÷ 90 rH (accuracy ±3 % rH) 

 

CO

2

 concetration measuring range 

NDIR  technology,  range  0-5000  ppm,  measuring 
accuracy  (operating  conditions  0-

45  °C,  relative 

non-

condensing  humidity  0  to  85%)  ±  50  ppm  ± 

3% of measured value, CO2 reaction time (90%) 
90 s 

Setpoint  

as configured, +/- 10 to +/- 1 K 

Display 

LCD 60 x 60 mm 

Terminals 

screw terminals for wires 0,14 

 1,5 mm

2

 

Cover 

ABS, RAL9010, 

other colours

 

Protection 

IP20 

Dimensions 

90x115x30 mm 

Ambient temperature 

External conditions: -5 

 45 

°C; 5 –

 95 % relative 

humidity;  non-condensing  gases  and  chemically 
non-aggressive  conditions  (according  to  EN 
60721-3-3 climatic class 3K5 

Storage:  -5 

  45 

°C;  5  –

  95 %  relative  humidity; 

non-condensing  gases  and  chemically  non-
aggressive conditions (according to EN 60721-3-1 
climatic class 1K3) 

Standards conformity 

EMC  EN  61000-6-2  ed.3:2005,  EN  61000-6-4 
ed.2:2006 + A1:2010 (industrial environment) 

Electrical safety EN 60950-1 ed.2:2006 + 
A11:2009 + A12:2011 + A1:2010 + A2:2014 + 
Opr.1:2012 + Z1:2016 

Hazardous substances reduction EN 50581:2012 

 

Terminals 

1

2

3

4

5

6

7

8

9

 

 

1: NC   not connected 
2: NC   not connected 
3: NC  not connected 
4: NC   not connected 
5: GND   technical earth (TE) 
6: G0   power 

 common point 

7: G 

 power 

 
8: K- 

 communication, RS485 

 

9: K+   communication, RS485 + 

Summary of Contents for UC905

Page 1: ...oncetration in the room air temperature correction setpoint by a knob and required operation mode which is set by a short push or in the menu Data is transmitted to the room controller The main controller FCR015 may send to the unit other data heating cooling mode fan stage day night standby mode etc which are displayed on the LCD display Connect the room unit to FCR015 over a 4 core cable the mos...

Page 2: ...nsions 90x115x30 mm Ambient temperature External conditions 5 45 C 5 95 relative humidity non condensing gases and chemically non aggressive conditions according to EN 60721 3 3 climatic class 3K5 Storage 5 45 C 5 95 relative humidity non condensing gases and chemically non aggressive conditions according to EN 60721 3 1 climatic class 1K3 Standards conformity EMC EN 61000 6 2 ed 3 2005 EN 61000 6...

Page 3: ...e operated easily and measure correct values of temperature i e in the height of about 150 cm with no direct sunlight or other heat cool source AHU outlets refridgerator electrical appliances The device consists of two parts bottom with screw terminal block and cover containing PCB display and the knob The bottom part is fixed by 2 or 4 screws to any flat surface or a flush mounting box Ø 50 mm At...

Page 4: ... only at the sides of the display part not at the top nor bottom Display A large 60 x 60 mm display clearly shows actual room temperature and controller status with 7 segment digits and standard Day Night Off and Time scheduler symbols Active output is indicated by a heating symbol In the upper part there are week days used for time scheduler setup Other symbols are not used LCD symbol set ...

Page 5: ... air conditioning systems It must not be used for protection of persons against health risks or death as a safety element or in applications where its failure could lead to physical or property damage or environmental damage All risks related to device operation must be considered together with design installation and operation of the entire control system which the device is part of ...

Page 6: ...6 08 2018 Subject to technical changes domat UC905 Changes in versions 10 2017 The first datasheet version 08 2018 Minor changes ...

Reviews: