domat UC300
01/2019 Subject to technical changes.
5
Change of setpoints and controller time:
Switch to the settings mode with a super long push (>2.5 s). The controller switches to
settings mode (flashing thermometer icon).
Turning the knob selects between following settings:
-
Controller time and day of week (Clock icon, Day of week)
-
Setpoint temp. Heating Day mode (Temperature, Heating, Day are flashing)
-
Setpoint temp. Heating Night mode (Temperature, Heating, Night are flashing)
-
Setpoint temp. Heating Off mode (Temperature, Heating, Empty house are
flashing)
-
Setpoint temp. Cooling Day mode (Temperature, Cooling, Day are flashing)
-
Setpoint temp. Cooling Night mode (Temperature, Cooling, Night are flashing)
-
Setpoint temp. Cooling Off mode (Temperature, Cooling, Empty house are
flashing)
Select the requested value by a short push. Turn knob to change value. Confirm by a
short push again.
If there is no user activity for 30 s, the controller goes to the basic display mode.
Default values:
Default values as well as all other settings (PI parameters, address, baud rate...) can be
set by the configuration program, ModComTool, and a USB/RS485 or RS232/RS485
converter
–
see Related products.
Display
A large (60 x 60 mm) display clearly shows
actual room temperature and controller
status with 7-segment digits and standard
Day, Night, Off, and Time scheduler
symbols. Active output is indicated by a
heating symbol. In the upper part, there
are week days used for time scheduler
setup. Other symbols are not used.
LCD symbol set