domat UC220
03/2017 Subject to technical changes.
6
Connection
Connection of power and communication. Suitable cable types are LAM DATAPAR 2x0.8
(cross-section in mm
2
), JYTY 2x1 (diameter in mm) etc. If communication and power are
in the same cable, use 4-core LAM DATAPAR 2x2x0.8, JYTY 4x1. Up to 100-120 meters,
parallel lines of 24 V and data bus are no problem. Regarding to EMC it is better if the
pairs are twisted, such as with the LAM DATAPAR or Belden 8205 cable.
A terminal is designed for maximum 3 wires of 0.8 mm
2
.
Temperature
compensation
After switching the unit on, allow about 90 mins to dissipate the heat inside of the
housing. Then the sensor is measuring correctly. Do not change the sensor correction
variable immediately after powering the device on.
RoHS notice
The device contains a non-rechargeable battery which backups the real-time clock and
part of the memory. After the device is not operable, please return it to the
manufacturer or dispose of it in compliance with local regulations.