domat UC220 Manual Download Page 3

 

domat UC220 

03/2017 Subject to technical changes. 

DIP switches 
 

 

Back of the PCB 
 
BUS END: if ON, the bus is terminated (if last 
device on the line) 
 
USR: 

   not used, reserved for future 

applications 
 
INIT: 

sets the controller into default state 

and sets bus address to 1, baud rate to 9600. 
To init, proceed as follows: 
- connect the device over RS485 to a PC with 
ModComTool config tool 
- set INIT to ON 
- apply power (use only the connector 
without bottom) 
- find the controller in the tool (Scan) 
- set INIT to OFF 
- in the ModComTool tool, open the 
controller window 
- click the Init button in the tool 
- remove and apply power. 
 

Installation 

 

 

Units  are  intended  for  operating  in  a  normal  and  chemically  non-aggressive 
environment. They do not need any servicing or maintenance. Install them in a vertical 
position at places where  they  can be operated easily and measure correct values  of 
temperature, i.e. in the height of about 150 cm, with no direct sunlight or other heat / 
cool source (AHU outlets, refridgerator, electrical appliances). The  device  consists of 
two parts: bottom with screw terminal block and cover containing PCB, display, and the 
knob. The bottom part is fixed by 2 or 4 screws to any flat surface or a flush-mounting 
box Ø 50 mm. At the back of the bottom there is an aperture for cabling. The bottom 
should be installed and cabling connected first, and the upper part inserted after the 
construction works have been finished to prevent damage to the unit.  
 
Seal the conduits to avoid influencing the sensor by draught. Use insulating pad when 
installing the  sensor on cold walls. Avoid sensor exposition to sunlight or other  heat 
sources. 

 

 

Opening the 
cover 

When removing the display part, proceed as follows: 
 

-

 

press gently the side parts of the unit and pull the right of the display part by 
several milimeters 

-

 

pull the left of the display part 

-

 

pull the display part and remove it from the bottom. 

Summary of Contents for UC220

Page 1: ...s set by short push of the knob The room temperature is measured in the range of 20 to 70 C Measured and set values are processed in a PI algorithm which is brought to sequence block and two 0 10 V DC outputs All values are displayed on a large LCD display The functionality and control parameters i e P and I constants and hysteresis can be set with ModComTool the configuration software which is fr...

Page 2: ...nt correction according to configuration 10 to 1 K Communication RS485 separation Baud rate 2 wire RS485 Modbus RTU slave optically separated up to 1000 V selectable 1200 9600 115200 bps Display LCD 60 x 60 mm Terminals screw terminals for 0 14 1 5 mm2 wires Cover ABS RAL9010 other colours Weight 0 13 kg Dimensions see below Terminals 1 2 3 4 5 6 7 8 9 Terminals as seen from above in the bottom pa...

Page 3: ...sure correct values of temperature i e in the height of about 150 cm with no direct sunlight or other heat cool source AHU outlets refridgerator electrical appliances The device consists of two parts bottom with screw terminal block and cover containing PCB display and the knob The bottom part is fixed by 2 or 4 screws to any flat surface or a flush mounting box Ø 50 mm At the back of the bottom t...

Page 4: ...he weekday 1 to 7 Then short push to confirm the selection Turn the knob to select the event large number 1 to 6 Each event displays the mode activated by this event Short push to confirm the event selection Turn the knob to select the operation mode Day Night Off Event inactive invoked by this event If the event is not active the operation mode is not changed at the set time Short push to confirm...

Page 5: ... are flashing Setpoint temp Cooling Off mode Temperature Cooling Empty house are flashing Select the requested value by a short push Turn knob to change value Confirm by a short push again If there is no user activity for 30 secs the controller goes to the basic display mode Default values The default values as well as all other settings PI parameters address baud rate can be set by the configurat...

Page 6: ...5 cable A terminal is designed for maximum 3 wires of 0 8 mm2 Temperature compensation After switching the unit on allow about 90 mins to dissipate the heat inside of the housing Then the sensor is measuring correctly Do not change the sensor correction variable immediately after powering the device on RoHS notice The device contains a non rechargeable battery which backups the real time clock and...

Page 7: ...to technical changes 7 Changes in versions 09 2016 Changed reference to the configuration software and deleted Related products 03 2017 Added picture and description of the installation and link on the datasheet with other colours ...

Reviews: