Patented quality product (Immersion sensor patent no. DE 10 2012 017 500.0)
Calibratable temperature measuring transducer
THERMASGARD
®
TM 43
with eight switch-
able measuring ranges, continuous linear output, straight protective tube, housing made from
impact-resistant plastic with snap-on lid. Calibratable temperature measuring transducer
THERMASGARD
®
TM 65
with eight switchable measuring ranges, continuous linear output,
straight protective tube, housing made from impact-resistant plastic with quick-locking
screws,
with ⁄ without optional display
. For the detection of temperatures in liquid or gaseous
media. For aggressive media, stainless steel immersion sleeves must be used. It is used e.g.
in piping systems, in heating technology, in storage tanks, in district heating compact
stations, in hot-water and cold-water systems, in oil and lubricant circulation systems, in
mechanical, apparatus and plant engineering as well as in the entire industrial sector. The
sensor is factory-calibrated; an environmental precision adjustment by an expert is possible.
TECHNICAL DATA
Power supply:
24 V AC ⁄ DC (± 10 %) for U variant
15...36 V DC for I variant, depending on working resistance,
residual ripple stabilised ± 0.3 V
Working resistance:
R
a
(ohm) = (U
b
-14 V) ⁄ 0.02 A for I variant
Load resistance:
R
L
> 5 kOhm for U variant
Power consumption:
< 1.0 VA ⁄ 24 V DC; < 2.2 VA ⁄ 24 V AC
Sensor:
Pt1000, DIN EN 60751, class B (
Perfect Sensor Protection
)
Measuring ranges:
multi-range switching with 8 switchable measuring ranges,
see table (other ranges optional)
with manual zero point correction (± 10 K)
Deviation, temperature: typically ± 0.2 K at +25 °C
Output:
0 - 10 V or 4...20 mA
Ambient temperature: measuring transducer –30...+70 °C
Connection type:
2- or 3-wire connection
Housing:
plastic, UV-stabilised, material polyamide, 30 % glass-globe
reinforced, colour traffic white (similar to RAL 9016),
TM 43
with snap-on lid
TM 65
with quick-locking screws
(slotted ⁄ Phillips head
combination), housing cover for display is transparent!
Housing dimensions:
72 x 64 x 37.8 mm (Tyr 1 / Tyr 01 without display)
72 x 64 x 43.3 mm (Tyr 1 with display)
Cable connection:
cable gland, plastic (M 16 x 1.5; with strain relief,
exchangeable, max. inner diameter 10.4 mm)
Electrical connection:
0.14 - 1.5 mm² via terminal screws on circuit board
Protective tube:
stainless steel,
V4A
(1.4571), Ø = 6 mm,
inserted length (EL) = 50 - 400 mm (see table)
Humidity:
< 95 % r. H., non-precipitating air
Protection class:
III (according to EN 60 730)
Protection type:
TM 43 IP 54
(according to EN 60 529)
*
Housing tested,
TÜV SÜD, Report No. 713160960A (Tyr 01)
TM 65 IP 67
(according to EN 60 529)
*
Housing tested,
TÜV SÜD, Report No. 713139052 (Tyr 1)
*
Housing in the built-in state
Standards:
CE conformity, electromagnetic compatibility according to EN 61326, according to EMC directive 2014 ⁄ 30 ⁄ EU
Optional: two-line
display with illumination
, cutout approx. 36 x15 mm (W x H), for displaying the
ACTUAL temperature
and the
internal diagnostics
(measuring range exceeded, measuring range not reached, sensor breakage, sensor short circuit)
ACCESSORIES
MF - 15 - K
Mounting flange,
plastic, 56.8 x 84.3 mm, Ø = 15.2 mm tube gland, T
max
= +100 °C
TH 08 - ms ⁄ xx
Immersion sleeve, brass, nickel-plated,
Ø = 8 mm, T
max
= +150 °C, p
max
= 10 bar
TH 08 - VA ⁄ xx
Immersion sleeve, stainless steel, V4A
(1.4571), Ø = 8 mm, T
max
= +600 °C, p
max
= 40 bar
TH 08 - VA ⁄ xx ⁄ 90
Immersion sleeve, stainless steel, V4A
(1.4571), with neck tube (90 mm), Ø = 8 mm, T
max
= +600 °C, p
max
= 40 bar
G
THERMASGARD
®
TM 43 ⁄ TM 65
Rev. 2020 - V16
Connecting scheme
TM 65 - I
Connecting scheme
TM 65 - U
-
+
+
-
1 2 3
230V AC
PLC
Working
resistance
24V DC
+UB 2
4V DC
Output
4...2
0mA GND
(optional f
or L
CD
backlighting)
-
+
+
-
1 2 3
230V AC
24V AC/DC
PLC
PC
+UB 2
4V AC/DC
Output
0
-1
0
V
-UB AC/DC GND