Configurable Safety System SAFEMASTER PRO
43
0265525 / 16.05.19 en / 101A
OUTPUT MODULE OSSD UG 6912.02 AND UG 6912.04
OUTPUT MODULE OSSD UG 6912.04/100
Type:
UG 6912.02
UG 6912.04
SFF:
(IEC 61508: 2
nd
edition)
99.8 %
99.8 %
PFH
d
:
4.09E-9
5.84E-9
MTTF
d
:
EN ISO 13849-1: 2008
948.88
683.38
DC
avg
:
98.9 %
99 %
Nominal voltage:
24 V DC
±
20 % / PELV, PREDective Class III; UL: Supply from class 2 (LVLE)
Nominal consumption:
Max. 3 W
Inrush current:
Max. 10 A, 0.3 ms
Digital status outputs (No. / description):
2
4
Programmable - PNP active high, max. 100 mA at 24 V DC
Inputs for Node selection NODE_SEL0/1
(No. / description):
2 / „Type 2“ acc. to EN 61131-2 IN: 7 to 10 mA at DC 24 V
OSSD (No. / description)
2
4
Solid state safety outputs: PNP active high; max. 400 mA at 24 V DC
Input FBK/RESTART
(No. / description):
2
4
EDM control / possible Automatic or Manual operation with RESTART button
„Typ 2“ acc. to EN 61131-2, IN: 7 to 10 mA at DC 24 V
Connection to control unit:
Proprietary 5-pole DOLD IN-RAIL-BUS
Weight:
190 g
Approvals:
SFF:
(IEC 61508: 2
nd
edition)
99,9%
PFH
d
:
8.64E-9
MTTF
d
:
EN ISO 13849-1: 2008
395,20
DC
avg
:
99,1%
Nominal voltage:
24 V DC
±
20 % / PELV, PREDective Class III; UL: Supply from class 2 (LVLE)
Nominal consumption:
Max. 4 W
OSSD output current
Max. 2 A per channel *
)
Number of safety outputs (OSSD):
4 single channels (or 2 dual channels), Cat. 4
Input FBK/RESTART
(No. / description):
4 / EDM control / possible Automatic or Manual operation with RESTART button
„Type 2“ acc. to EN 61131-2, IN: 7 to 10 mA at DC 24 V
Digital outputs (No. / description):
8 / programmable output / PNP active high
Response time:
12 ms
Connection to control unit:
Proprietary 5-pole DOLD IN-RAIL-BUS
Weight:
190 g
Approvals:
*
)