14
BN 5930.48/203, /204 / 22.01.19 en / 106A
Input
Nominal voltage U
N
:
AC 110 V* / DC 60 V* or
AC 230 V* / DC 110 V*
over terminal A1 - A2
other voltages on request
Voltage range:
AC 0.85 ... 1.1 U
N
at 10% residual ripple:
DC 0.9 ... 1.1 U
N
at 48% residual ripple:
DC 0.85 ... 1.1 U
N
Nominal consumption:
approx. 3.9 VA at AC 230 V
Nominal frequency:
50 / 60 Hz
Control voltage T12, T22:
same as nominal voltage
Control current:
approx. 12 mA for K1 and K2
at AC 230 V
Fusing of the device:
internal with PTC
Output
Contacts
BN 5930.48:
3 NO, 1 NC contacts
The contacts 13...33 / 14...34 are safety contacts.
The contact 41-42 can only be used for monitoring.
Response / release time
of K1 and K2:
35 ms / 35 ms
Release delay of K3:
approx. 250 ms
Contact type:
relay, forcibly guided
Output nominal voltage:
AC 400 V / DC 230 V
Thermal current I
th
:
see continuous current limit curve
(max. 10 A in one contact path)
Switching capacity
to AC 15
NO contact:
3 A / AC 250 V
IEC/EN 60 947-5-1
NC contact:
2 A / AC 250 V
IEC/EN 60 947-5-1
to AC 15
NO contact:
6 A / AC 230 V at 0.25 Hz
NC contact: 2 A / AC 230 V at 0.25 Hz
to DC 13
NO contact:
2 A / DC 24 V
IEC/EN 60 947-5-1
NC contact:
2 A / DC 24 V
IEC/EN 60 947-5-1
to DC 13
NO contact:
6 A / DC 24 V at 0.1 Hz
NC contact:
6 A / DC 24 V at 0.1 Hz
Electrical life
at AC 230 V, 6 A cos
ϕ
= 1:
> 5 x 10
5
switching cycles
Permissible switching
frequency:
6000 switching cycles / h
Short circuit strength
max. fuse rating:
6 A gG / gL
IEC/EN 60 947-5-1
max. line circuit breaker:
C 10 A
Mechanical life:
10 x 10
6
switching cycles
BN 5930.48/204 AC 230 V 50/60 Hz
Article number:
0045350
•
With cross fault detection
by connecting to phase and neutral, max. 230 V
•
Output:3 NO, 1 NC contacts
•
Nominal voltage U
N
:
AC 230 V / DC 110 V
•
Width:
100 mm
BN 5930 .48
/_ _ _ AC 230 V 50/60 Hz
Nominal frequency
Nominal voltage
Variant, if required
Contacts
Type
General Data
Operating mode:
Continuous operation
Temperature range
Operation:
- 15 ... + 55°C
at max. 90 % air humidity
Storage :
- 25 ... + 85
°
C
Altitude:
< 2.000 m
Clearance and creepage
distances
rated impulse voltage /
pollution degree:
4 kV / 2 (basis insulation) IEC 60 664-1
EMC
IEC/EN 62 061
Interference suppression:
Limit value class B
EN 55 011
Degree of protection:
Housing:
IP 40
IEC/EN 60 529
Terminals:
IP 20
IEC/EN 60 529
Housing:
Thermoplast with V0 behaviour
according to UL subject 94
Vibration resistance:
Amplitude 0.35 mm
frequency 10 ... 55 Hz IEC/EN 60 068-2-6
Climate resistance:
15 / 055 / 04
IEC/EN 60 068-1
Terminal designation:
EN 50 005
Wire fixing:
Flat terminals with self-lifting
clamping piece
IEC/EN 60 999-1
Removable terminal strip
Mounting:
DIN rail
IEC/EN 60 715
Weight:
590 g
Dimensions
Width x heigth x depth:
100 x 74 x 121 mm
A1(+)T11 T33
X2
X3
T12 T12 T22
41
13
23
33
A2(-)
M6771_a
T34 X1
42
14
24
34
K1
K2.1
K1.1
K3.1
K3.2
K1.3
K2.3
K2.4
K3.4
K1.4
K2.2
K1.2
VDR
K3.3
K3
Mains
K2
K2
K1
BN 5930.48/203
BN 5930.48/204 (with cross fault detection)
A1(+)T11 T33
X2
T12 T12 T22
41
13
23
33
A2(-)
M6772_a
T34 X1 S23
42
14
24
34
K1
K2.1
K1.1
K3.1
K3.2
K1.3
K2.3
K2.4
K3.4
K1.4
K2.2
K1.2
VDR
K3
Mains
K2
K2
K1
Block Diagrams
Technical Data
Technical Data
Ordering Example
Standard Type