Technical User Guide
DOL 51
7
Have specialists carry out the annual inspection and sensitivity check.
Replace the dust filter in front of the sensor element, if clogged. A clogged filter prolongs the re-
sponse time of the sensor element. This affects the sensitivity. The dust filter must always be re-
placed prior to checking the sensitivity.
DOL 51 must be removed during cleaning and disinfection.
Do not expose the DOL 51 housing to air in the livestock house without the sensor element mounted, it is how-
ever, okay to replace the element in the livestock house.
Cleaning
Clean the sensor surface with lukewarm water. Check for mechanical damage.
Transport
The sensor must be transported in the original packing in air traffic. Otherwise the sensor may
lose its measuring sensitivity.
9 Technical data
DOL 51, 0-10V, 4-20mA,
0-50ppm NH
3
Specification
Parameter
Unit
Output
Voltage range
0 – 10
VDC
Power range
4 – 20
mA
Load for voltage output
> 500 - < 10M
Ω
Recommended load, voltage output
> 100
kΩ
Load for current output
> 100 - < 470
Ω
NH3
Measurement range
0 – 50
ppm NH
3
Voltage resolution
0.2
V/ppm NH
3
Resolution
0.32
mA/ppm
Signal transmission resolution
0.5
ppm NH
3
Accuracy
1.5 ppm or +10% of the
measured value
ppm NH
3
Long term drift
< +10% of the mea-
sured value
%
Time constant: T50
< 30
sec.
Supply voltage
22 – 26
VDC
Supply current
< 200
mA
Temperature, operation
0 – +50
o
C
Temperature, storage
-20 – +60
o
C
Humidity
15 – 100
%RH
Pressure
700 – 1300
hPa