Technical User Guide
DOL 20R
3
LED indication
Sensor status
LED ON
Relay activated (NC) – output OFF
4 User Guide
When there is material in front of the sensor, the output is in the reference position NO. When the material dis-
appears, the timer, starts, and the output will change to NCafter the set delay.
The status of the sensor is indicated with a yellow LED.
The sensor sensitivity and delayed disconnection can be adjusted on two trimmers.
Relay activated (NC) Relay in default position (NO)
Sensor
LED
Contact
ON
ON
OFF
OFF
NO
NC
Delayed disconnection:
fixed delay
or
delay can be adjusted on the trimmer.
Delayed connection:
fixed delay
or
delay can be adjusted on the trimmer.
Sensitivity:
fixed distance
or
Distance can be adjusted on the trimmer.
MaxRun-timer:
DOL 20R Settings on the trimmer: Off, Period 1, Period 2
5 Maintenance
If the sensor is located in a particularly dirty environment, it may be necessary to clean the area around the
sensor.
Otherwise, no additional maintenance is required.
6 Technical data
Electrical
Rated voltage (Ue)
V AC
90-250
Frequency
Hz
50-60
Consumption (max.)
W, 230 V AC
0.9
Rated relay current at 250
V AC
A RMS
A RMS
0.5, Inductive
1, Resistive
Time delay, start-up
ms
< 300
Time delay OFF
s
0-600*
Time delay ON
s
1*
Indication for output ON (if
installed)
Yellow LED