dead.
Connections between the Dupline signal and earth potential will cause malfunctions and
are not permissible. In addition check for correct polarity of the Dupline signal.
The following table illustrates the connection configuration: 

13. Guarantee

All professionally installed, unaltered devices are covered by warranty during the statu-
tory guarantee period from the day of purchase by the end user. The guarantee is not
applicable to damage incurred during transport or caused by short-circuit or overloading.
In the event of defects in workmanship or material, which are discovered within the guar-
antee period, the company will provide a replacement free of charge.

14. Technical Data

Terminal

Description

Terminal

Description

1

Dupline signal con (D+)

2

Dupline signal conductor - (D-)

Min.

Typ.

Max.

Dupline

Current input

1,3 mA

Input channels 2 input signals (alarm / live Signal)

Output channels None

Inputs

Type integrated

Rated voltage

8 VDC

Trigger resistance

150 k

470 k

Operating Voltage

Rated operating voltage Not required (supplied by Dupline signal line)

Terminals

Type Screw terminals

Contact area

0.4 mm 

0.8 mm²

Housing

Type White surface-mounted housing

Dimensions 70 x 40 x 16 (W x H x D in mm)

Material ABS

General technical data

Ambient temperature

-20°C

+50°C

Encl. protection type /

standards

IP 67

Order number, description 09 501 197, Water sensor DWS 1