DFL 8 B SK / SK X / SK V / SK X V

Environmental testing

IEC 60068

dry heat

IEC 60068-2-2

damp heat

constant

IEC 60068-2-78

cyclic

IEC 60068-2-30

Cross sections

solid

1 x (4 mm² – 16 mm²); 2 x (4 mm² – 16 mm²)

stranded

1 x (25 mm² – 185 mm²); 2 x (25 mm² – 70 mm²)

Tightening torque

14 Nm

Endurance

mechanical

> 2,000 cycles

electrical

> 2,000 cycles

Design 
 requirements

Overload 

tripping

VDE 0660 / EN 60947-2

Residual 

current 

tripping

VDE 0660 / EN 60947-2 Appendix B

Electromagnetic 

 compatibility

EN 60947-2 Appendix J

Weight

approx. 5,600 g

1)

 DIN VDE 0636, IEC 60269

Auxiliary switch

Load rating

AC-15: 230 V / 6 A; 400 V / 4 A; 500 V / 2 A

DC-13: 24 V / 3 A; 110 V / 0.8 A;  220 V / 0.3 A

Rated operating voltage U

e

230/400 V AC

Rated impulse withstand 

voltage U

imp

6 kV

Rated insulation voltage Ui

500 V

Cross-sections solid and 
flexible with ferrules

1 x (0.75 mm² – 2.5 mm²); 2 x (0.75 mm² – 1.5 mm²)

Characteristics

1000

1

10

100

1000

10000

100000

100

10000

10

Frequenz / Frequenzy in Hz

Fehlerstro

m

/

R

esidual

current

in

mA

DF L 8 B S K / 30 mA

Auslösestromfrequenzgang / Tripping current frequenzy response

1000

1

10

100

1000

10000

100000

100

10000

10

Frequenz / Frequenzy in Hz

Fehlerstro

m

/

R

esidual

current

in

mA

DF L 8 B SK / 300 mA

Auslösestromfrequenzgang / Tripping current frequenzy response

1000

1

10

100

1000

10000

100000

100

10000

10

Frequenz / Frequenzy in Hz

Fehlerstro

m

/

R

esidual

current

in

mA

DF L 8 B S K / 500 mA

Auslösestromfrequenzgang / Tripping current frequenzy response

1000

1

10

100

1000

10000

100000

100

10000

10

Frequenz / Frequenzy in Hz

Fehlerstro

m

/

R

esidual

current

in

mA

DF L 8 B S K / 1000 mA

Auslösestromfrequenzgang / Tripping current frequenzy response

Application instructions and warnings

The following notes and warnings must be observed in order to ensure safe operation:

1.  Installation may only be carried out by an authorised specialist, who is familiar 

with the relevant national installation regulations.

2.  Without an additional protective housing, the circuit-breaker with residual cur

­

rent trip may only be stored and operated in a dry, low-dust environment. An ag

­

gressive atmosphere must also be avoided.

3.  The user must be made aware of repeat testing using the button T.
4.  Using surge current strength CBRs cannot absolutely guarantee to rule out trips 

due to leakage currents caused by surge voltage. In cases where an interruption of 
the power supply may lead to potential dangers for humans and animals or dam

­

age to property, residual current protection should be implemented by means of 
increased surge current strength, selective CBRs and upstream surge arresters. In 
specific cases, the switching status should be monitored by means of an auxiliary 
contactor at the  circuit-breaker and an appropriate signalling device.

Guarantee

All  professionally  installed,  unaltered  devices  are  covered  by  warranty  during  the 
statutory guarantee period from the day of purchase by the end user. The guaran

­

tee is not applicable to damage incurred during transport or caused by short-circuit, 
overloading  or  improper  use.  In  the  event  of  defects  in  workmanship  or  material, 
which are discovered within the guarantee period, the company will provide a repair 
or replacement free of charge. The guarantee will be rendered null and void if the 
device is opened without authorization.

Technical Data

DFL 8 B SK / SK X / SK V / SK X V

Rated current In

100 A

125 A

160 A

200 A

250 A

Rated   residual 
current I

�n

standard

0.03 A

series X

adjustable: 0.3 A, 0.5 A, 1.0 A

Detection range of residual 

current

0 – 100 kHz, 50 or 60 Hz

Rated operat

­

ing voltage Ue

standard

230/400 V AC

series V

290/500 V AC

Rated frequency

50 Hz or 60 Hz

min. 

 operating 

voltage

for detec

­

tion of 

residual 

currents 

Type A/AC

0 V (mains independent)

for detec

­

tion of 

residual 

currents 

Type B

50 V AC

Internal consumption

max. 2.5 – 3 W

operating 
range of  test 

circuit

standard

50 V AC – 400 V AC

series V

50 V AC – 500 V AC

number of poles

four-pole

Dissipation power P

v

 (typ.)

35 W

43 W

55 W

72 W

85 W

Short-circuit fuse 

1)

250 A/gG

Response 

times

standard

1 x I�n ≤ 300 ms; 5 x I�n ≤ 40 ms

series X

Range l = 60 – 120 ms

Range ll = 150 – 250 ms

Range lll = 300 – 420 ms

Range llll = 450 – 600 ms

Non-response 

lag time

standard

undelayed

series X

Range l = < 60 ms

Range ll = < 150 ms

Range lll = < 300 ms

Range llll = < 450 ms

Rated short­circuit discon­

necting capacity limit I

cu

50 kA at 400/415 V AC

Rated operation short-

circuit disconnecting 

capacity I

cs

50 kA at 400/415 V AC

Rated residual current 
short­circuit disconnecting 

capacity I�m

50 kA at 400/415 V AC

Surge current strength

Proof of the resistance of CBRs to unintended tripping 

from surge currents resulting from surge voltages 

EN 60947-2:2003 (B.8.6)

Shock resistance

20 g / 20 ms duration (IEC 60068-2-27)

Vibration resistance

1.0 g (f = 2 – 100 Hz)  (IEC 60068-2-6)

Type of protection

IP 20

Installation position

vertical or tilted by 90°

Supply side

bottom

Ambient temperature

-25 °C to +70 °C

1)

 DIN VDE 0636, IEC 60269

Installation and Operating Manual

for circuit-breakers with residual current trip  

of series DFL 8 B SK

Electrical connection

Guide all active conductors (outer cables L1, L2, L3 and the neutral conductor MP/N) 
through the switch. The energy flow direction must be observed, i. e. the mains or 
consumer unit has to be connected to the lower terminal block. Scrape and grease 
aluminium conductors immediately before connection.

Function and area of application

The devices of the DFL 8 B series are circuit-breakers with residual current trip sensi

­

tive to all current types for the detection of residual currents of type B. They consist 
of a section independent of the mains voltage for the detection of sinusoidal AC and 
pulsing DC residual currents with the rated frequency 50 Hz or 60 Hz and a section de

­

pendent on the mains voltage for the detection of residual currents in the frequency 
range 0 Hz to 100 kHz. 

The devices are intended for use in single and multiple phase AC networks. They are 
not intended for use in DC networks.

In order to ensure protection across the total frequency range covered in the event 
of indirect contact with a maximum contact voltage of 50 V or 25 V respectively, the 

earth resistance must be in accordance with the table given below.

Series

maximum touch voltage 25 V

maximum touch voltage 50 V

DFL 8 B SK

8.3 Ω

16.6 Ω

For frequencies > 1 kHz the tripping current for the DFL 8 B SK is up to approx 3 A. 
This ensures its insensitivity to high leakage currents in the upper frequency range.

Testing and functional check

The testing of all safety measures on commissioning must be carried out according 
to the information in the valid national installation regulations. An insulation test of 
the user equipment is to be carried out in accordance with DIN EN 61557-2. This may 
only be done when the device is switched off. Insulation testing when the device is 
switched on or insulation testing on the input side may lead to incorrect measured 
values. A functional inspection of the circuit-breaker with residual current trip itself 
is possible with connected mains voltage by pressing the test button T and, as in com

­

mercial use (BGV A3), should be carried out at least every six months in the case of 
stationary systems and should be repeated every working day in the case of non-

stationary systems.

The green LED signals that the internal operating voltage is sufficient for AC-DC sen

­

sitive residual current detection (residual currents of type AC, A and B). If the LED 
does  not  illuminate,  then  only  tripping  via  type  AC  and  A  residual  currents  is  still 
guaranteed. The internal supply of the device is via the bottom terminals. At least 
two arbitrary conductors must conduct AC voltage of greater than 50 V in order to 
guarantee AC-DC sensitive residual current detection.

Important information on operation with electronic equipment  
(such as frequency converters, inverters etc.)

1.  Electronic equipment and its associated EMC protective provisions, such as e. g. 

integrated or in series-connected EMC filters, as well as shielded cables, can give 
rise to high capacitive leakage currents.

2.  The maximum number of items of electronic equipment connected downstream 

of the device is based on the level of leakage currents that occur. Excessive leak

­

age currents may lead to undesired tripping in spite of the tripping current fre

­

quency response of the device. Relevant information concerning the discharge 
currents that are produced can be requested from the manufacturers of the elec

­

tronic equipment.

3.  During operation with frequency converters long, shielded motor cables may lead 

to high discharge currents in the event of the controller release of the frequency 
converter, which lead to undesired tripping. If necessary, a sinusoidal output filter 
should then be used directly behind the frequency converter (before the shielded 
motor cable).

4.  According to the instructions, a conventional 3-conductor EMC filter should only 

be connected in series with the relevant electronic equipment. So that the filter ef

­

fect is not impaired, under no circumstances should further single-phase consum

­

ers such as incandescent bulbs be connected on the output side of the EMC filter.

5.  As a rule, different clock frequencies (chopper) can be selected in the case of elec

­

tronic equipment. In an unfavourable case, the clock frequency may lead to a ten

­

dency to oscillation in an upstream EMC filter and therefore to greatly increased 
leakage currents, which then result in a tripping of the device. In this case, the 
clock frequency must be changed.