5. Technical data
minimum
typical
maximum
Power supply
AC
rated voltage
195 V
AC
230 V
AC
265 V
AC
current input
0.025 A
current input (at switching moment)
0.25 A
Control inputs
Control voltage AC/DC
1)
12 V @ 25 °C
20 V @ -25 °C
230 V
Rated power
1.4 VA
1.6 VA
1.9 VA
control pulse duration
60 ms
push-button bounce time
10 ms
relay outputs
3 signal relays (toggle pos blocked signal)
AC/
DC
Voltage
2)
230 V
UC
Nominal power
60 VA
rated current
see load curve
Mains relay (remote tripping of RCCB)
AC
voltage
230 V
AC
250 V
AC
fixed test residual
operating current I
Δn
0.5 A
switching duration
400 ms
Terminals
type
screw terminal with strain-relief clamp
terminal cross-section
0.4 mm Ø
2.5 mm²
tightening torque
0.6 Nm
Housing
type
distribution board housing in accordance with DIN 43880
for mounting on support rail in accordance with DIN EN 60715
Dimensions
W 72 mm (4 TE) ×
H
85 mm ×
D
76 mm
material
polyamide (PA)
General data
Operating temperature
3)
-25 °C
+60 °C
humidity
max. 85% (exposure to dew not permissible)
type of protection
IP 20
Standards
DIN EN 50557, DIN EN 55014-1
Article numbers / accessories
Remote actuator DFA 2-3 / DFA 2-4
09 100 114 / 09 100 115
Cable for test button function
0,03 A: 09 100 150 / 0,1 A: 09 100 151 / 0,3 A: 09 100 152
1) The control inputs must be wired with the same potential
2) The relay outputs for the toggle positions must be wired with the same potential.
3) The permissible operating temperature of the mounted RCCB must be observed.
EN
DE
25