START ADDRESS

The DMX start address can be selected using the start address switches. Also, special
programming of the interface is performed using the adress range beyond 512 (see chap-
ter „Setup“). The adress 000 is not a valid start adress and will be decoded as 001 instead.

DALI adressing cannot be changed and is fixed from 1 thru 4* (64). The same applies to DALI
group adressing.

*= pre-configured to 4 addresses (data slots) . User-reprogrammable zo 4...64 addresses / data slots (see chapter „SET-
UP“ below).

DALI

Please note, that DALI is much, much slower than DMX: controlling two DALI addresses simultan-
eously requires about the same time as transmitting a complete DMX telegram containing 512 data
slots. That’s what the DALI guys call „DALI Delay“.

Thus only up to four individual DALI units may be controlled simultaneously without a too big delay.
The decoder, however,  can be configured to output data for up to 64 adresses sequentially - but
for the reason outlined above the default setting is four (4). If more units are to be controlled simul-
taneously we recommend to change to group address setting, or use multiple decoders and multi-
ple DALI links in parallel. We also recommend to re-program connected DALI responders to a fade
time of at least 0,7 sec (fade time parameter set to 1 or 2) to allow a smooth response. You may do
so using your preferred DALI programmer (or our USB-DALI tool).

The DALI protocol can be set to individual adressing or group adressing mode using adresses 1
thru 4 (64). DALI data are derived from the incoming DMX data. Please note that the maximum in-
tensity -as used by DMX- is 255, whereas the maximum intensity on the DALI line is 254. (In the
DALI standard, value 255 is reserved for “MASK“ [no operation]). Thus the maximum level is clip-
ped from 255 to 254*.

The DALI output is intended for connection to a DALI bus system. The DALI bus must be fed from
a DALI power supply (DALI PSU) and may be loaded with up to 64 bus participants. If required, ad-
ressing on the DALI bus must be performed using a suitable addressing tool (e.g. our USB-DALI in-
terface). The 7044B-H does not perform any adressing of bus participants by itself.

*= pre-configured to 254 . User-reprogrammable zo MASK value 255 (see chapter „SETUP“ below).

Signalanzeigen

The decoder status is signalled using three LED indicators:.

green:

on when DMX signal present
blinks when DMX signal present but DALI bus fails or is smissing

red:

ERROR

normally off

blinks when DMX signal is missing or contains invalid data

yellow:

Steady: 

DALI Bus  missing or unpowered

random blink: activity

Summary of Contents for soundlight 7044B-H

Page 1: ...CKED CAREFULLY AND ARE BELIEVED TO BE ACCURATE HOWEVER SOUNDLIGHT DOES NOT ASSUME ANY RESPONSIBI LITY FOR ERRORS OR OMISSIONS THE USER HAS TO CHECK THE SUITABILITY OF THE EQUIP MENT FOR THE INTENDED U...

Page 2: ...mpatible The 7044B H is compatible to DALI bus systems simple supply The power supply is from standard mains voltage 230V AC signal loss In the case of a loss of the drive signal a pre definable actio...

Page 3: ...u re do ne Cage clamp connectors accept both stranded and so lid wires We recommend to use ferrules with stranded wi res whenever poosible The decoder 7044B H consits of connectors for these inputs an...

Page 4: ...to re program connected DALI responders to a fade time of at least 0 7 sec fade time parameter set to 1 or 2 to allow a smooth response You may do so using your preferred DALI programmer or our USB D...

Page 5: ...o meet your individual needs More information regarding DALI programming and the USB DALI interface can be found in the USB DALI manual It is not necessary to use the USB DALI programmer Any DALI prog...

Page 6: ...programmed into the interface both status LEDs are blinking alternatively several times As soon as the programming sequence is completed upower the decoder re set the desired DMX start address and re...

Page 7: ...5 address mode etc 864 set to enable 64 address mode NOTE Pls note that converting more than 4 adresses simultaneously may cause significant delays due to the limited DALI bus speed TECHNICAL DATA Dim...

Page 8: ...ace in a closed conductive e g metal housing which must be connected to GND Please make sure that shielded data cable is used and the shield is connected properly to the GND pin Shield must never make...

Page 9: ...ign manuals are available from www ma nuals soundlight de Additional RDM information for RDM enabled devices only is available from www rdm soundlight de If you have any comments which may be worth co...

Reviews: