- ZONE 1: Name of the zone. The user can change the name
using the arrows and the OK button.
5.2.2.
Devices
: The following options are available in this menu:
Review/Add/Delete. Devices are added to the zone and in case
one of them sends a fault signal or a fire alarm signal, the
relevant zone enters condition in accordance (Fire Alarm
condition and/or Fault condition)
5.2.3.
Outputs without delay:
The following options are available:
Review/Add/Delete. Outputs that shall be activated in case of
events in the zone occur.
5.2.4.
Delayed outputs:
The following options are available:
Review/Add/Delete. Outputs that shall be activated with delay,
after some time period, in case of events in the zone occur.
5.2.5.
Panel outputs:
The submenu allows setting activation of certain
panel outputs in case of fire as delayed outputs or outputs
without delay Fig.11 pos. 3
– 6 … 5 – 1 or 2). The following
outputs can be set: Controllable Output 1, Controllable Output 2
and Relay 1 and Relay 2.
5.2.6.
Inputs:
The
following
options
are
available:
Review/Add/Delete. The inputs of input/output devices
(М9000А IO) included in the loop are added in this menu.
EXAMPLE:
Let’s assume that devices are allocated in a building as follows:
1. Automated fire detectors - 10 devices on each floor. A1R, A1S, SR, MSR
2. Manual call points MCP
– 3 on each floor
3. Sound and light indicator S9000A
– 2 on each floor
We assume that each device has been addressed and has an individual address (point 4). Each device
has a name (p.5) For example, the manual call point at building’s entrance on floor 1 has been assigned the
name MCP Entrance. The manual call point near the stairs
– MCP Stairs Floor 1, etc. The same logic is
applied to automated fire detectors.
The zones may get names like: FLOOR 1, FLOOR 2, FLOOR 3.
The addressable devices shall be added to the relevant floor. The sound and light indicators shall be added
to zone addressable outputs. The location of the relevant zone and the path for evacuation shall be carefully
considered here. Example: In case of FIRE in zone FLOOR 1, zones FLOOR 2 and FLOOR 3 must be
evacuated; therefore, the sound and light indicators shall be activated on all three floors.
For this purpose all sounders shall be added to zone 1 FLOOR 1, using submenu Outputs w/t Delay (if we
want them activated immediately). Analogically, for floor 2, all sounders available on floor 2 and 3 shall be
added. For floor 3
– only the sounders available on floor 3.
2 Devices
3 Outputs w/t Delay
4 Delayed Outputs
>5 Panel Outputs
>1 Review
2 Add
3 Delete
>1 Contr Output 1: OFF
2 Contr Output 2: OFF
3 Relay 1: OFF
4 Relay 2: OFF