Instruction manual
Fire Alarm Panel FP9000A
DMTech LTD, 16 N.Haytov Street, Pleven Tel.: 0889992660 e-mail:[email protected] page - 10 - of 20
ISO 9001:2015 Certified Company
2.2.3. Description of main PCB
LCD 4 x 20
USB
BATT
B4
B3
B1
B2
B5
B6
B4
Loop 1
Relay 3
NO
NO
Relay Fault
Line
Relay 2
Relay 1
Out 2
Out 1
4.7k
4.7k
4.7k
28V
+
+
+
+
+
+
-
-
-
-
-
Fig. 6
– Main PCB of the fire alarm panel
Terminal strip description (from left to right):
•
LOOP 1
(-LOOP+ / +ERT / -LOOP+)
– Terminal strip for connecting Loop 1 to the fire alarm panel.
•
LINE
– Conventional line
•
FAULT
– Potential output connecting external devices, 24 VDC/ 0.3А. It is deactivated in fault condition
of in the system.
•
28V
– User power supply
•
RELAY FAULT -
the fault relay is activated when the panel is in fault mode
– 3 positions provided for Nc
(default) condition and No condition
•
OUT1
–
Monitored output
OUT1
– a 4.7 кОhm terminating resistor shall be connected in parallel to the
device far off from the panel
•
OUT2 -
Monitored output
OUT2 - a 4.7
кОhm terminating resistor shall be connected in parallel to the
device far off from the panel
•
RELAY 1
– Programmable relay 1 – the relay function shall be assigned in settings menu
•
RELAY 2
– Programmable relay 2 – the relay function shall be assigned in settings menu
•
RELAY 3
– The relay is activated in fire mode. 3 No terminals are provided, Normally open contact, Nc
normally closed contact and center.
•
USB
–USB B/ micro connector; communication with the fire alarm panel from a computer via specialized
software
•
BATT
–
Pin connector (red and black pins) for connection to the storage battery. An additional
Ø5mm
cable ear connector is installed to each cable terminal (M5)