Fig.1
–
This option is obtained by cutting the bridge on the board with mounting chucks. (Fig. 2)
–
Install the cover of the upper supports to the base and, with slight pressure, close the fire detector;
Fig. 2
3.
Testing and maintenance
Testing:
–
Apply voltage;
–
Raise the protective cover;
–
Press working surface at the indicated with arrows place.
–
The operating element must fail where it will appear and the graphic indication of the operating element
for operated detector and will light up and the red LED on the front.
–
To restore, place the key in the opening on the top of the fire detector and press until the work item
moves to the top position. The hatch must hide and the LED turn off.
–
Keep detector key for periodic testing and recovery after emergency operation.
Maintenance
– Visual inspection for mechanical damage and pollution:
-
quarterly
–
Performance check:
-
еyearly
4.
Warranty obligations
The manufacturer guarantees the conformity of the device with standards EN 54-11:2006. The warranty period is
36 months from the date of sale , provided that:
– the conditions of storage and transport have been followed;
– release is performed by authorized persons;
– the requirements for operation stated in this instruction have been abode.
– defects are not caused by natural phenomena and accidents of the plug socket.