XTL Installation Guide 

Digital Monitoring Products

11

ComPlIanCe

False Alarm Reduction Programmable Options ANSI/SIA CP-01-2007

18.1  Shipping Defaults and Recommended Programming

SIA CP-01 FEATURE 

PARAGRAPH # AND 

DESCRIPTION

DMP PROGRAMMING 

GUIDE LT-1108 

SECTION #

REQUIREMENT

RANGE

SHIPPING 

DEFAULT

RECOMMENDED 

PROGRAMMING*

4.2.2.1 Exit Time

8.6 Exit Delay

Required 

(Programmable) 45 sec. - 250 sec.

60 

Seconds

60 Seconds

4.2.2.2 Progress 

Annunciation 

13.14 Prewarn 

Address

Allowed

Individual keypads 

may be disabled per 

zone

All 

keypads 

enabled

All keypads enabled

4.2.2.3 Exit Time 

Restart

8.6 Exit Delay

Required Option

For re-entry during 

exit time

Enabled

Enabled

4.2.2.5 Auto Stay Arm 

on Unvacated Premises

8.17 Occupied 

Premise - 

See Install 

Guide 

 

Required Option 

(except for 

remote arming)

Occupied Premise 

NO/YES option

Enabled

Enabled  Yes 

for Residential 

Applications

4.2.4.4 Exit Time and 

Progress Annunciation/

Disable - for Remote 

Arm

Not Available on 

Remote Arming

Allowed Option

Progress Annunciation 

Always disabled for 

Remote Arming

Not 

Available

Remote Arming not 

allowed for CP-01 

installations.

4.2.3.1 Entry Delay(s)

8.5 Entry Delay

Required 

(Programmable) 30 sec. – 240 Sec. 

**

30 

Seconds

At least 30 Seconds 

**

4.2.5.1 Abort Window – 

for Non-Fire Zones

3.3 Transmit Delay

Required Option Disable by zone or 

zone type

Enabled 

NT  DY  

EX Zone

Enabled

4.2.5.1 Abort Window 

Time – for Non-Fire 

Zones

3.3 Transmit Delay

Required 

(Programmable)

20 sec., 30 sec., or 

40 sec. 

** 

30 

Seconds

At least 20 Seconds 

**

4.2.5.1.2 Abort 

Annunciation

3.3 Transmit Delay

Required Option

Annunciate that 

no alarm was 

transmitted 

Yes

Yes

4.2.5.4.1 Cancel 

Annunciation

Always Enabled - Not 

Programmable

Required Option

Annunciate that 

a Cancel was 

transmitted (S49)

Always 

Enabled

Yes

4.2.6.1 & 4.2.6.2 

Duress Feature

User Code + 1 = 

Ambush Code Not 

Available

Allowed Option

No 1 + derivative of 

another user code/no 

duplicates with other 

user codes

Code +1 

Always 

Disabled

Not Programmable

4.3.2 Swinger Shutdown Not Available — 

Always On

Required 

For all non-fire 

zones, shut down 

after 1 trip

Always 

On

Always On

4.3.2 Swinger Shutdown 

Disable

13.13 Swinger Bypass

Allowed 

For non-police 

response zones

Yes

Enabled (all zones)

4.3.3 Fire Alarm 

Verification

13.5 Zone Type

Required Option

FV Type Zone

No

Yes as required 

(unless sensors can 

self verify)

* Programming at installation may be subordinate to other listed requirements for the intended application. 

** For listed Installations, combined Entry Delay and Transmit Delay should not exceed 1 minute.

Summary of Contents for XT Lite

Page 1: ...Inst alla tion Guide XT Lite Panel...

Page 2: ...r Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help Changes or modifications no...

Page 3: ...ndary Power Supply 6 1 Standby Battery 5 6 2 Replacement 5 6 3 Battery Supervision 5 LED Operation 7 1 Backlit Logo 6 Reset Button 8 1 Description 6 Programming Connection 9 1 Programming Connection 6...

Page 4: ...ard Line Security 10 16 2 Remote Disarm 10 16 3 Central Station 10 Household Fire Warning System ANSI UL 985 NFPA 72 Specifications 17 1 Bell Output Definition 10 17 2 Household System 10 17 3 Wireles...

Page 5: ...The XTL panel comes with a SIM card ready for activation with SecureCom Wireless LLC More information is available at www securecomwireless com 1 3 Keypads You can connect up to 4 alphanumeric 9000 S...

Page 6: ...t can be independently armed or disarmed 2 2 Caution Notes Throughout this guide you will see caution notes containing information you need to know when installing the panel These cautions are indicat...

Page 7: ...s dual coverage area selection and sensitivity adjustments 1126C 1126R 1126W PIR Motion Detector Ceiling mount motion detector with panel programmable sensitivity and Disarm Disable functionality 1127...

Page 8: ...e Model 372 500 plug in DC power supply In addition to powering the panel the DC plug in power supply also charges the back up battery The 372 500 must be located within 100 feet of the panel using 22...

Page 9: ...andby Battery Replacement 1 Unplug the battery connector J1 from the XTL panel 2 Loosen the top PCB snaps 3 Lean the panel PCB forward and lift out from the bottom PCB snaps 4 Remove and properly disp...

Page 10: ...ble This provides a quick and easy connection for programming the XTL panel After programming is complete remove the keypad Note The PROG header does not provide a Keypad Data Bus connection On Board...

Page 11: ...firmation During the one minute time period the panel also confirms that programmed keypads are still functioning Wireless Zones 12 1 Description XTL panels provide 28 wireless zones numbered 1 to 28...

Page 12: ...and containing the XTL RU file 3 Start Remote Link and create or open the XTL control panel account that matches the panel to be updated 4 Set the Connection Information Type to Direct with a baud ra...

Page 13: ...ant 14 4 Types Of Service Suitable for Central Station Standard Line Security Suitable for Household Fire and Household Burglary Test weekly 14 5 Bypass Reports The bypass reports must be programmed a...

Page 14: ...TL panel must be programmed to operate steady on burglary alarms and temporal on fire alarms See the XTL Programming Guide 17 2 Household System An alarm sounding device must be installed indoors so t...

Page 15: ...d Programmable 30 sec 240 Sec 30 Seconds At least 30 Seconds 4 2 5 1 Abort Window for Non Fire Zones 3 3 Transmit Delay Required Option Disable by zone or zone type Enabled NT DY EX Zone Enabled 4 2 5...

Page 16: ...ell enabled with a bell cutoff time set to a minimum of 6 minutes to provide a cancel window of 5 minutes or greater This does not apply to manually operated zone types such as Panic and Emergency The...

Page 17: ...ons Revisions to This Document This section explains the changes that were made to this document during this revision This section lists the version section number with heading and a quick summary of...

Page 18: ...ACCESS NETWORKS 2500 North Partnership Boulevard Springfield Missouri 65803 8877 10045 Listings and Approvals FCC Part 15 ID CCKPC0117 Industry Canada ID 5251A PC0117 Underwriters Laboratories UL List...

Reviews: