XTL Installation Guide
Digital Monitoring Products
11
ComPlIanCe
False Alarm Reduction Programmable Options ANSI/SIA CP-01-2007
18.1 Shipping Defaults and Recommended Programming
SIA CP-01 FEATURE
PARAGRAPH # AND
DESCRIPTION
DMP PROGRAMMING
GUIDE LT-1108
SECTION #
REQUIREMENT
RANGE
SHIPPING
DEFAULT
RECOMMENDED
PROGRAMMING*
4.2.2.1 Exit Time
8.6 Exit Delay
Required
(Programmable) 45 sec. - 250 sec.
60
Seconds
60 Seconds
4.2.2.2 Progress
Annunciation
13.14 Prewarn
Address
Allowed
Individual keypads
may be disabled per
zone
All
keypads
enabled
All keypads enabled
4.2.2.3 Exit Time
Restart
8.6 Exit Delay
Required Option
For re-entry during
exit time
Enabled
Enabled
4.2.2.5 Auto Stay Arm
on Unvacated Premises
8.17 Occupied
Premise -
See Install
Guide
Required Option
(except for
remote arming)
Occupied Premise
NO/YES option
Enabled
Enabled Yes
for Residential
Applications
4.2.4.4 Exit Time and
Progress Annunciation/
Disable - for Remote
Arm
Not Available on
Remote Arming
Allowed Option
Progress Annunciation
Always disabled for
Remote Arming
Not
Available
Remote Arming not
allowed for CP-01
installations.
4.2.3.1 Entry Delay(s)
8.5 Entry Delay
Required
(Programmable) 30 sec. – 240 Sec.
**
30
Seconds
At least 30 Seconds
**
4.2.5.1 Abort Window –
for Non-Fire Zones
3.3 Transmit Delay
Required Option Disable by zone or
zone type
Enabled
NT DY
EX Zone
Enabled
4.2.5.1 Abort Window
Time – for Non-Fire
Zones
3.3 Transmit Delay
Required
(Programmable)
20 sec., 30 sec., or
40 sec.
**
30
Seconds
At least 20 Seconds
**
4.2.5.1.2 Abort
Annunciation
3.3 Transmit Delay
Required Option
Annunciate that
no alarm was
transmitted
Yes
Yes
4.2.5.4.1 Cancel
Annunciation
Always Enabled - Not
Programmable
Required Option
Annunciate that
a Cancel was
transmitted (S49)
Always
Enabled
Yes
4.2.6.1 & 4.2.6.2
Duress Feature
User Code + 1 =
Ambush Code Not
Available
Allowed Option
No 1 + derivative of
another user code/no
duplicates with other
user codes
Code +1
Always
Disabled
Not Programmable
4.3.2 Swinger Shutdown Not Available —
Always On
Required
For all non-fire
zones, shut down
after 1 trip
Always
On
Always On
4.3.2 Swinger Shutdown
Disable
13.13 Swinger Bypass
Allowed
For non-police
response zones
Yes
Enabled (all zones)
4.3.3 Fire Alarm
Verification
13.5 Zone Type
Required Option
FV Type Zone
No
Yes as required
(unless sensors can
self verify)
* Programming at installation may be subordinate to other listed requirements for the intended application.
** For listed Installations, combined Entry Delay and Transmit Delay should not exceed 1 minute.