background image

Designed, engineered, and 

manufactured in Springfield, MO 

using U.S. and global components.

LT-1875 19063  1.01

711S ZONE EXPANSION MODULE

Specifications

Operating Voltage 

8.8 to 15.0 VDC

Operating Current
 

Standby  

 

4.2 mA

 

Alarm  

 

4.7 mA

Zone Voltage 

 

5 VDC, max 2 mA

EOL Value 

 

1k Ohm

Dimensions 

 

1.25” W x 2.75” H

Compatibility

All DMP panels with zone expansion capability

Certifications

Commercial Burglar and Fire Accessory Zone Expander
Signaling Device
ANSI/UL 365 

Police Station Connect Burglar Alarm Systems

ANSI/UL 609 

Local Burglar Alarm Units & Systems

ANSI/UL 864 

Fire Protective Signaling Systems

ANSI/UL 985 

Household Fire Warning System Units

ANSI/UL 1023 

Household Burglar Alarm System Units

ANSI/UL 1076 

Proprietary Burglar Alarm Units & Systems

ANSI/UL 1610 

Central Station Burglar Alarm Units

ANSI/UL 1635 

Digital Alarm Communication System Units

ULC Subject-C1023 

Household Burglar

ULC/ORD-C1076 

Proprietary Burglar

ULC S304  

Central Station Burglar

ULC S545 

Household Fire

I N T R U S I O N   •   F I R E  •   A C C E S S  •   N E T W O R K S

2500 North Partnership Boulevard

Springfield, Missouri 65803-8877

888-436-7832|  DMP.com

4

Wiring Specifications for Keypad and LX-Bus

1. DMP recommends using 18 or 22-gauge 

unshielded 

wire for all keypad and LX-Bus 

circuits. 

Do Not

 use twisted pair or shielded wire for LX-Bus and Keypad Bus data 

circuits. To maintain auxiliary power integrity when using 22-gauge wire do not 

exceed 500 feet. When using 18-gauge wire do not exceed 1,000 feet. Install an 

additional power supply to increase the wire length or add devices.

2. Maximum distance for any one circuit (length of wire) is 2,500 feet regardless of 

the wire gauge. This distance can be in the form of one long wire run or multiple 

branches with all wiring totaling no more than 2,500 feet. As wire distance from 

the panel increases, DC voltage on the wire decreases.

3. Maximum number of devices per 2,500 feet circuit is 40.
4. Maximum voltage drop between the panel (or auxiliary power supply) and any 

device is 2.0VDC. If the voltage at any device is less than the required level, add 

an auxiliary power supply at the end of the circuit. When voltage is too low, the 

devices cannot operate properly.
Refer to the panel installation guide and LX-Bus/Keypad Bus Wiring Application 

Note (LT-2031).

Red - Auxiliary Power 
Yellow - Data
Green - Data 
Black - Common

To next module

1K Ohm EOL

All wiring is Power Limited 

and Supervised.  See 

Wiring the 711S 

Module.

Keypad Bus or LX-Bus 

wiring from panel 

White - Positive
Brown - Negative

Protection Zone Supervised 5V, Class B, Style A

The maximum impedance is 100 Ohms 

Ground fault detected at less than 1200 Ohms

Normal operating range is 650-1200 Ohms

Figure 3: 711S Module Wiring

Compliance Listing Specifications

UL

To comply with ANSI/UL 365 Police-Connected Burglary System or ANSI/UL 609 Local Burglary Alarm Systems, the 
module must be mounted in a listed enclosure with a tamper installed.
The keypad and LX-Bus are rated Class B, Style 3.5.

ULC Commercial Burglary (XR150/XR550 Series panels)

Place the 711S and other zone expander modules in a listed enclosure and connect a DMP Model 307 Clip-on Tamper 

Switch to the enclosure programmed as a 24-Hour zone.

The 711S zone can only be used in Low Risk applications. Medium or High Risk applications must use panel zone inputs.

ZONE PROGRAMMING

You can program the 711S zone with any panel Burglary or Fire zone type or as an Arming zone type when used with 

keyswitches.

Zone Expander Data LED

The 711S LED flashes each time the module responds to a poll from the panel. If there is a problem with the panel, panel 

programming, or the Green data wire between the panel and the zone expander module, the LED stops flashing.

3

Reviews: