Yellow Trouble LED

 turns on when the panel has failed to 

communicate with the central station receiver after 10 

attempts, or when phone line 1 or 2 is in a bad condition. The 

Trouble LED turns off after a successful communication to 

the central station, or when the phone line(s) are restored to 

normal.  The yellow Trouble LED also flashes if the keypad loses 

communication with the panel. 

Green Power LED 

turns on steady when there is AC or DC power 

to the panel, and is off when power is lost. The Power LED 

flashes when the panel’s battery is low or missing. 

Keypad Function Keys

SILENCE 

- Press the 

SILENCE 

key and enter the user code to 

silence a system alarm and the keypad sounder.  You may also 

use the 

SILENCE

 key to silence the bells during the Fire Drill function.

RESET 

- Press the 

RESET

 key and enter the user code (or press COMMAND 47) to reset a zone after an alarm. This 

resets all zone alarm LEDs and momentarily drops power to the panel’s zones 2 to 5 and smoke power output.

TEST 

- Press the 

TEST

 function key and enter the user code (or press COMMAND 41) to initiate the panel’s System 

Test function. This test rings the panel bells for 2 seconds, checks the battery charge level, and sends a system test 

report to the central station on monitored systems.

CODE 

- To change the system user code, press 

CODE

, enter the current user code followed by 0 + 1, and then enter 

the new 4-digit user code. (The user code must always be 4 digits.) 

SPECIAL

- Pressing the 

SPECIAL

 key and entering the user code initiates the Fire Drill function. The Fire Drill sounds 

the alarm bells and keypad sounder for the duration of the Bell Cutoff time. If the Bell Cutoff time is set to zero, the 

Fire Drill will continue until the bells are silenced by entering a code. No keypad LEDs are turned on and no reports 

are sent to the central station during the Fire Drill. In the event of a real fire during a fire drill, the system will send 

a report to the central station and the LED for any zone detecting a fire will glow red on the 692F. 

Manual Fire Alarm

 - To manually initiate a fire alarm, press and hold the 

TEST 

and 

CODE 

keys simultaneously for 

about 2 seconds until the alarm sounds. 

Wiring Specifications

When planning a keypad bus installation, keep in mind the following specifications:

1. DMP recommends using 18 or 22-gauge 

unshielded 

wire for all keypad and LX-Bus circuits.  

Do Not

 use 

twisted pair or shielded wire for LX-Bus and keypad bus data circuits.  To maintain auxiliary power integrity 

when using 22-gauge wire do not exceed 500 feet.  When using 18-gauge wire do not exceed 1,000 feet.  

2. Maximum distance for any one circuit (length of wire) is 2,500 feet regardless of the wire gauge.  This 

distance can be in the form of one long wire run or multiple branches with all wiring totaling no more than 

2,500 feet.  As wire distance from the panel increases, DC voltage on the wire decreases.

3. Maximum number of devices per 2,500 feet circuit is 40.  

 

Note:

  Each panel allows a specific number of supervised keypads.  Add additional keypads in the 

unsupervised mode.  Refer to the panel installation guide for the specific number of supervised keypads 

allowed.  

4. Maximum voltage drop between the panel (or auxiliary power supply) and any device is 2.0 VDC.  If the 

voltage at any device is less than the required level, add a regulated, power limited, power supply listed 

for Fire Protective Signaling at the end of the circuit.  When voltage is too low, the devices cannot operate 

properly.  

Refer to the LX-Bus/Keypad Bus Wiring Application Note (LT-2031) for more information.  Also see the 710/710F 

Module Installation Sheet (LT-0310).  

Specifications

Operating Voltage  8.0 to 16 VDC
Current Draw 

30mA standby, 70mA max

Dimensions 

5.0” H x 6.8” W x 1.1” D

Panel Compatibility  

XR5FC and XR5SL

Listings and Approvals

FCC Part 15
California State Fire Marshal (CSFM)
New York City (MEA)
Underwriters Laboratories (UL) Listed

 

UL  864  Fire Protective Signaling

System LEDs

Zone 
Alarm 
LEDs

Zone Trouble 
LEDs

Function 
Keys

SPECIAL

Key

COMMAND 

Key

Data Entry 
Keys

Figure 2: 692F Keypad

Reviews: