2W-BLX/2WT-BLX ADDRESSABLE 

SMOKE DETECTOR

Specifications

Operating Voltage 

12 Vdc (Nominal)

Standby Current 

11 mA

Alarm Current 

31 mA

Maximum Ripple 

 30% (V) peak to peak

Operating Temperature (Ambient Room)
  2W-BLX 

32°F to 120°F 

2WT-BLX 

32°F to 100°F

Operating Humidity Range 

 0 to 95% RH non-condensing

Heat Sensor (2WT-BLX Only)  135°F
Power Up Time  

80 seconds

Sensitivity Photoelectric 

2.5%/ft. max.

Detector Dimensions 

 

Diameter 

5.3 inches 

Height 

2.0 inches 

Weight 

6.3 ounces 

Ordering Information

2W-BLX/10 

Photoelectric smoke detector

2WT-BLX/10 

Photoelectric smoke detector with 

 

 

 

fixed-temperature thermal detector

Certifications

California State Fire Marshal (CSFM)
Underwriters Laboratories (UL) Listed
  ANSI/UL 268 Smoke-Automatic Fire Detectors

I N T R U S I O N   •   F I R E  •   A C C E S S  •   N E T W O R K S

2500 North Partnership Boulevard

Springfield, Missouri 65803-8877

800.641.4282  |  DMP.com

ADDITIONAL INFORMATION (CONTINUED) 

GREEN LED

RED LED

Power-Up

Blink 10 seconds

Blink 10 seconds

Normal (Standby)

Blink 5 seconds

— 

Out of Sensitivity

Blink 5 seconds

Alarm

Solid

Table 1: Detector LED Modes

Built-In Drift Compensation 

The detector automatically adjusts its sensitivity back to the factory setting when it becomes more sensitive due to 

contaminants settling in its chamber. In order for this feature to work properly, the chamber must never be opened while 
power is applied to the smoke detector. This includes cleaning, maintenance, or screen replacement.

LED Operation

After power-up has completed and the detector is 

functioning normally within its listed sensitivity range, the 

Green LED blinks once every five seconds. 
If the detector needs maintenance because its sensitivity 

has shifted outside the limits, the Red LED blinks once 

every five seconds. See Table 1. 
The LED indication must not be used in lieu of the tests 

specified under Testing.