Designed, engineered, and
manufactured in Springfield, MO
using U.S. and global components.
LT-1364 1.01 20052
2W-BLX/2WT-BLX ADDRESSABLE
SMOKE DETECTOR
Specifications
Operating Voltage
12 Vdc (Nominal)
Standby Current
11 mA
Alarm Current
31 mA
Maximum Ripple
30% (V) peak to peak
Operating Temperature (Ambient Room)
2W-BLX
32°F to 120°F
2WT-BLX
32°F to 100°F
Operating Humidity Range
0 to 95% RH non-condensing
Heat Sensor (2WT-BLX Only) 135°F
Power Up Time
80 seconds
Sensitivity Photoelectric
2.5%/ft. max.
Detector Dimensions
Diameter
5.3 inches
Height
2.0 inches
Weight
6.3 ounces
Ordering Information
2W-BLX/10
Photoelectric smoke detector
2WT-BLX/10
Photoelectric smoke detector with
fixed-temperature thermal detector
Certifications
California State Fire Marshal (CSFM)
Underwriters Laboratories (UL) Listed
ANSI/UL 268 Smoke-Automatic Fire Detectors
I N T R U S I O N • F I R E • A C C E S S • N E T W O R K S
2500 North Partnership Boulevard
Springfield, Missouri 65803-8877
800.641.4282 | DMP.com
ADDITIONAL INFORMATION (CONTINUED)
GREEN LED
RED LED
Power-Up
Blink 10 seconds
Blink 10 seconds
Normal (Standby)
Blink 5 seconds
—
Out of Sensitivity
—
Blink 5 seconds
Alarm
—
Solid
Table 1: Detector LED Modes
Built-In Drift Compensation
The detector automatically adjusts its sensitivity back to the factory setting when it becomes more sensitive due to
contaminants settling in its chamber. In order for this feature to work properly, the chamber must never be opened while
power is applied to the smoke detector. This includes cleaning, maintenance, or screen replacement.
LED Operation
After power-up has completed and the detector is
functioning normally within its listed sensitivity range, the
Green LED blinks once every five seconds.
If the detector needs maintenance because its sensitivity
has shifted outside the limits, the Red LED blinks once
every five seconds. See Table 1.
The LED indication must not be used in lieu of the tests
specified under Testing.