2W-BLX AND 2WT-BLX  INSTALLATION GUIDE     |     DIGITAL MONITORING PRODUCTS 

MOUNT THE DETECTOR

Wiring the Detector

1.  Pull wire through electrical box, then through the 

detector’s mounting base center opening.

2.  Connect the 4-wire harness to the 4-pin header 

according to the wiring diagram in Figure 4.

Note:

  

Tie the red wire (smoke power) to the smoke 

terminal (SMK) of the panel. The other wires 

go to the LX-Bus™ for addressing.

4

5

TEST THE DETECTOR

Detectors must be tested after installation and following maintenance. After power up, allow 80 seconds for 

the detector to stabilize before testing.

Figure 4:  2W-BLX/2WT-BLX Wiring

Black 

(common)

Green 

(data)

Yellow 

(data)

Red 

(smoke power)

To LX-Bus

S2

0

1 2

3

4

5

6

7

8

9

S1

TENS 

J3

0

1 2

3

4

5

6

7

8

9

ONES 

A

B

Figure 5:  Mounting Detector Head

Figure 6:  Sensitivity Testing 

the 2W-BLX/2WTBLX

Push resessed 

switch with a 

0.18” maximum 

diameter tool

Sensitivity Test Switch

1.   Insert a small screwdriver or allen wrench (0.18” 

max.) into the test switch opening located on the 

detector housing. Push and hold (See Figure 6).

2.   If the detector is within the listed sensitivity limits, 

the detector’s Red LED should turn on within five 

seconds.

3.  To measure the detector’s sensitivity, use the 

System Sensor i

3

 Series Model SENS-RDR Infrared 

Sensitivity Reader® tool.

Smoke Entry Test

Hold a smoldering stick or cotton wick at the side of the 

detector and gently blow through the detector until it 

alarms.

Caution:

 Be sure to properly extinguish the smoke 

source after testing. 

Direct Heat Method (Model 2WT-BLX only)

Direct the heat of a 1000-1500 watt hair dryer toward either of the thermistors. Thermistors are located on 

each side of the screen/sensing chamber. Hold the heat source about 12 inches from the detector to avoid 

damage to the plastic.

Note:

 For the above tests, the detector will reset only after a Sensor Reset is performed.

If the detector fails any of the above tests, check the wiring and clean the detector as outlined in the 

Maintenance Section. If the detector still fails, it should be replaced.

Mounting the Detector

1.  Place detector on the base and rotate clockwise. 

The detector will drop into the base and lock into 

place with a click. See Figure 5.

2.  After all the detectors have been installed, apply 

power to the control panel.