background image

Digital Monitoring Products 

1165/1165H/1165HS Detectors Installation Sheet

6

Maintaining the Detector

The 1165/1165H/1165HS detectors are designed for easy field service and maintenance. When installed and used 

properly, they require minimal maintenance. The smoke detector should be functionally tested per NFPA 72 2013 Table 

14.4.3.2 for system type smoke detectors. See 

Testing the Detector Sensitivity 

and 

Smoke Testing the Smoke Detector

When an 1165/1165H/1165HS detector requires maintenance, it extinguishes its LED.

WARNING

Smoke alarms CANNOT provide warnings for fires resulting from explosions, smoking in bed or other furniture, 

ignition of flammable liquids, vapors and gases, children playing with matches or lighters.

NFPA 72 Guidelines

Total (Complete) Coverage. 

If required, total coverage shall include all rooms, halls, storage areas, basements, 

attics, lofts, spaces above suspended ceilings, and other subdivisions and accessible spaces; and the inside of all 

closets, elevator shafts, enclosed stairways, dumbwaiter shafts, and chutes. Inaccessible areas shall not be required 

to be protected by detectors. (For exceptions, refer to NFPA 72.)

Partial Coverage. 

If required, partial detection systems shall be provided in all common areas and work spaces, such 

as corridors, lobbies, storage rooms, equipment rooms, and other tenantless spaces in those environments suitable 

for proper detector operation in accordance with this code.

Selective Coverage. 

Where codes, standards, laws, or authorities having jurisdiction require the protection of 

selected areas only, the specified areas shall be protected in accordance with this code.

Supplementary (Non required) Coverage. 

Where installed, detection that is not required by an applicable law, code, 

or standard, whether total (complete), partial, or selective coverage, shall conform to the requirements of this 

code. (For exceptions, refer to NFPA 72 Spacing Requirements.)
Where non required detection devices are installed for a specific hazard, additional non required detection devices 

shall not be required to be installed 

throughout an entire room or building.

Heat-Sensing Fire Detectors. 

Heat-sensing fire detectors shall be installed in all areas where required by the NFPA 

codes and standards or by the authority having jurisdiction.

Detection in New Apartment Buildings. 

Approved, single-station smoke alarms shall be installed in accordance with 

7-6.2.10 of NFPA 101 outside every sleeping area in the immediate vicinity of the bedrooms and on all levels of the 

dwelling unit including basements. (For exceptions, refer to this section of NFPA 72.)

Detection in Existing Apartment Buildings. 

Approved, single-station smoke alarms shall be installed in accordance 

with 7-6.2.10 of NFPA 101 outside every sleeping area in the immediate vicinity of the bedrooms and on all levels of 

the dwelling unit including basements. (For exceptions, refer to this section of NFPA 72.)

WARNING! Limitations of Smoke Detectors

Wireless smoke alarms are very reliable, but may not work under all conditions. No fire alarm provides total 

protection of life or property. Smoke alarms are not a substitute for life insurance.

Smoke alarms require a source of power to work. 

This smoke alarm will not operate and the alarm will not sound 

if batteries are dead or not installed properly.

Smoke alarms may not be heard. 

A sound sleeper or someone who has taken drugs or alcohol may not awaken if the 

alarm is installed outside a bedroom. Closed or partially closed doors and distance can block sound. This alarm is not 

designed for the hearing impaired.

Smoke alarms may not always activate and provide warning early enough. 

Smoke alarms only activate when 

enough smoke reaches the alarm. If a fire starts in a chimney, wall, roof, on the other side of closed doors, or on a 

different level of the property enough smoke may not reach the alarm for it to alarm.

Smoke alarms are a significant help in reducing loss, injury and even death. However, no matter how good a 

detection device is, nothing works perfectly under every circumstance and we must warn you that you cannot 

expect a smoke alarm to ensure that you will never suffer any damage or injur

y.

Fire Prevention and Escape

The purpose of an early warning smoke alarm is to detect the presence of fire in its early stages and sound an alarm 

giving the occupants time to exit the premises safely.

Summary of Contents for 1165

Page 1: ...eration extends battery life for transmitters A missing message may display on the keypad until the transmitter sends a supervision message Transmitted Signal Outputs The smoke detector provides the signals listed in the table Signal Keypad Display Alarm ALARM Alarm restore OK Low battery LOBAT Selecting the Proper Location LED Survey Operation The 1165 1165H 1165HS Transmitter provides a survey c...

Page 2: ...ng tile the tile must be secured with the appropriate fastener to prevent tile removal Locations to Avoid Do not install smoke alarms detectors In or near areas where combustion particles are normally present such as in kitchens garages near furnaces hot water heaters or gas space heaters On the ceiling in rooms next to kitchens where there is no transom between the kitchen and such rooms In damp ...

Page 3: ...rews and anchors provided mount the base 7 Line up the raised tab on the lip of the detector with the slot on the lip of the mounting base See Figure 4 Important The control panel alarm and all auxiliary functions should be verified for a complete test of the system Smoke Testing the Smoke Detector Smoke detectors should be tested in place annually using one of the following methods A Use DMP Mode...

Page 4: ...g and Removing the Detector Attach the smoke detector to its mounting base as follows 1 Line up the raised alignment tab on the lip of the smoke detector with arrow on the mounting base See Figure 4 2 Insert the smoke detector into the base and turn clockwise approximately 15 degrees It should snap firmly into place To remove the detector from the mounting base grasp the detector and turn it count...

Page 5: ...ssary clean the detector interior and replace the smoke chamber as follows 1 Remove the detector from its mounting base See Attaching and Removing the Detector 2 Remove the batteries See Replacing the Batteries 3 Slide a flat blade screwdriver in the slot on the detector cap and gently push the handle down to pry the cap up and off See Figure 6 4 Press the sides of the smoke chamber in where indic...

Page 6: ...ire room or building Heat Sensing Fire Detectors Heat sensing fire detectors shall be installed in all areas where required by the NFPA codes and standards or by the authority having jurisdiction Detection in New Apartment Buildings Approved single station smoke alarms shall be installed in accordance with 7 6 2 10 of NFPA 101 outside every sleeping area in the immediate vicinity of the bedrooms a...

Page 7: ...r carefully feel the door and door knob to see if undue heat is present If they seem cool brace your foot against the bottom of the door with your hip against the door and one hand against the top edge Open it slightly If a rush of hot air is felt slam the door quickly and latch it Unvented fire tends to build up considerable pressure Be sure all members of the household realizes and understands t...

Page 8: ... Note This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may caus...

Reviews: