Commercial Fire

Transmitters must be programmed as supervised. Refer to Table 1 for specific supervision times. The maximum line 

impedance of the 4-wire bus is 16.2 Ohms for 1, 000 feet (305 meters). The recommended wire gauge for panel to 

receiver connection is 22 AWG.
After all transmitters are in position, the WLS option of the panel’s Walk Test must be operated and all transmitters 

programmed for Fire (FI) or Supervisory (SV) must show that their check-in message was received. Refer to the panel 

programming guide for Trip Counter for DMP Wireless Check-in Test (WLS) which describes that both numbers of the 

counter must match. If not and a failed wireless zone is displayed at END, decrease that transmitter’s range with the 

receiver and perform the Wireless Walk Test again. 

LISTED COMPLIANCE SPECIFICATIONS 

Transmitter Supervision Time

For UL Listed installations, program the transmitter supervision time in panel zone programming as listed in the following 

table. Refer to the panel programming guide for complete wireless programming information.

UL Listing

Listed Accessories

Supervision Time

UL 268 Smoke-Automatic Fire Detectors

1100R Repeater

1164 Wireless Synchronized Smoke Detector

3

UL 365 Police Station Connected Burglar Accessory

1100R Repeater

1103 Universal Transmitter

60

UL 521 Heat Detectors for Fire Protective Signaling 

Systems

1100R Repeater

1183-135F, 1183-1353R Heat Detector

3

UL 609 Local Burglar Alarm Units and System Accessory

1100R Repeater

1103 Universal Transmitter

60

UL 634 Connections and Switches for use with Burglar 

Alarm Systems Accessory

1100R Repeater

1101, 1102, 1103, 1106 Universal Transmitters

60

UL 636 Holdup Alarm Units and Systems Accessory

1142 Two-Button Holdup Transmitter

60

UL 639 Intrusion Detection Units Accessory

1100R Repeater

1127W, 1127C PIR Motion Detectors

60

UL 864 Fire Protective Signaling Systems

1100R Repeater

1103 Universal Transmitter

3

UL 985 Household Fire Warning System Accessory

1100R Repeater

1135 Wireless Sounder

9060, 9063 Wireless Keypads

240

UL 1023 Household Burglary System Units Accessory

1100R Repeater

1101, 1102, 1103, 1106 Universal Transmitters

1127W, 1127C PIR Motion Detectors

1135 Wireless Sounder

1142 Two-Button Holdup Transmitter

9060, 9063 Wireless Keypads

9862 Wireless Graphic Touchscreen Keypad

60

UL 1076 Proprietary Burglar Alarm Units Accessory

1100R Repeater

1103 Universal Transmitter

9862 Wireless Graphic Touchscreen Keypad

60

UL 1610 Central Station Burglar Alarm Units Accessory

1100R Repeater

1103 Universal Transmitter

1135 Wireless Sounder

9060, 9063 Wirless Keypads

9862 Wireless Graphic Touchscreen Keypad

60

UL 2075 Gas and Vapor Detectors and Sensors

1184 Wireless Carbon Monoxide Detector

240

Table 3: Wireless Transmitter Supervision Times

Reviews: