For applications that must conform to a National Recognized Testing Laboratory certified system, read the information
below for additional information.
Commercial Fire
Transmitters must be programmed as supervised. Refer to Table 1 for specific supervision times. The maximum line
impedance of the 4-wire bus is 16.2 Ohms for 1, 000 feet (305 meters). The recommended wire gauge for panel to
receiver connection is 22 AWG.
After all transmitters are in position, the WLS option of the panel’s Walk Test must be operated and all transmitters
programmed for Fire (FI) or Supervisory (SV) must show that their check-in message was received. Refer to the panel
programming guide for Trip Counter for DMP Wireless Check-in Test (WLS) which describes that both numbers of the
counter must match. If not and a failed wireless zone is displayed at END, decrease that transmitter’s range with the
receiver and perform the Wireless Walk Test again.
LISTED COMPLIANCE SPECIFICATIONS
Transmitter Supervision Time
For UL Listed installations, program the transmitter supervision time in panel zone programming as listed in the following
table. Refer to the panel programming guide for complete wireless programming information.
UL Listing
Listed Accessories
Supervision Time
UL 268 Smoke-Automatic Fire Detectors
1100R Repeater
1164 Wireless Synchronized Smoke Detector
3
UL 365 Police Station Connected Burglar Accessory
1100R Repeater
1103 Universal Transmitter
60
UL 521 Heat Detectors for Fire Protective Signaling
Systems
1100R Repeater
1183-135F, 1183-1353R Heat Detector
3
UL 609 Local Burglar Alarm Units and System Accessory
1100R Repeater
1103 Universal Transmitter
60
UL 634 Connections and Switches for use with Burglar
Alarm Systems Accessory
1100R Repeater
1101, 1102, 1103, 1106 Universal Transmitters
60
UL 636 Holdup Alarm Units and Systems Accessory
1142 Two-Button Holdup Transmitter
60
UL 639 Intrusion Detection Units Accessory
1100R Repeater
1127W, 1127C PIR Motion Detectors
60
UL 864 Fire Protective Signaling Systems
1100R Repeater
1103 Universal Transmitter
3
UL 985 Household Fire Warning System Accessory
1100R Repeater
1135 Wireless Sounder
9060, 9063 Wireless Keypads
240
UL 1023 Household Burglary System Units Accessory
1100R Repeater
1101, 1102, 1103, 1106 Universal Transmitters
1127W, 1127C PIR Motion Detectors
1135 Wireless Sounder
1142 Two-Button Holdup Transmitter
9060, 9063 Wireless Keypads
9862 Wireless Graphic Touchscreen Keypad
60
UL 1076 Proprietary Burglar Alarm Units Accessory
1100R Repeater
1103 Universal Transmitter
9862 Wireless Graphic Touchscreen Keypad
60
UL 1610 Central Station Burglar Alarm Units Accessory
1100R Repeater
1103 Universal Transmitter
1135 Wireless Sounder
9060, 9063 Wirless Keypads
9862 Wireless Graphic Touchscreen Keypad
60
UL 2075 Gas and Vapor Detectors and Sensors
1184 Wireless Carbon Monoxide Detector
240
Table 3: Wireless Transmitter Supervision Times