16.
DEFAULT SETTING VALUES
COD
Name
Range
°C/°F Lev
Set1 Set point1
LS1÷US1
0/32
-
Set2 Set point2
LS2÷US2
1/34
-
Hy1
Differential 1
-Full Sc./ Full Sc.
-1/-2
Pr1
Hy2
Differential 1
-Full Sc./ Full Sc.
-1/-2
Pr1
LS1
Minimum set point1
Down Sc./ Set1
min
Pr2
LS2
Minimum set point2
Down Sc./ Set2
min
Pr2
US1 Maximum set point1
Set1/ Full Sc.
max
Pr2
US2 Maximum set point2
Set2/ Full Sc.
max
Pr2
ouC Output configuration
ind= independent;
diP = dependent
ind
Pr2
S1C Action type output 1
in= Inverse; dir=direct
in
Pr2
S2C Action type output 2
in= Inverse; dir=direct
in
Pr2
Ac
Anti-short cycle delay:
0÷250 sec
0
Pr2
on
Minimum time a stage
stays switched ON
0÷250 sec
0
Pr2
ono
Minimum time between 2
following switching ON of
the same load
0÷120 min
0
Pr2
trd
Cycle length setting
0 ÷ 19:59 ( 0 =
disable )
0,00 Pr2
trM
Regulation setting
oFF = stop
regulation
on = regulation
continues
oFF Pr2
trS
Timer exhausted
signalling
no = buzzer off
yES = buzzer on
Yes Pr2
ALC Alarm configuration
rE=relat.; Ab= absolute
rE
Pr2
ALL Minumum alarm (ALC=rE)
(ALC=Ab)
0 ÷ |Start Sc.-Set1|
Start Sc.÷ ALu
10.0/
20
Pr2
ALU Maximum alarm (ALC=rE)
(ALC=Ab)
0 ÷ |Full Sc.-Set1|.
ALL÷ Full Scale
10.0/
20
Pr2
ALH Alarm recovery differential 0÷Full scale
2.0/4 Pr2
ALd Alarm delay
0÷999 min
15
Pr2
dAO Alarm delay at start up
0÷23h 50min
1.3
Pr2
So1
Out1 status with faulty pr. oFF=open on=closed
oFF
Pr2
So2
Out2 status with faulty pr. oFF=open on=closed
oFF
Pr2
tbA
1
Alarm relay disabling
no; yES
yES
Pr2
AS
1
Alarm relay polarity
CL÷oP
oP
Pr2
Lci
2
Start scale with current or
voltage input
-1999÷1999
various Pr1
Uci
2
End scale with current or
voltage input
-1999÷1999
various Pr1
OPb Probe calibration
-Full Sc./ Full Sc.
0.0
Pr1
rES
Resolution
in=NO; dE=0,1;
cE=0,01
in
Pr2
UdM Measurement unit (temp.)
(current/voltage)
°C=°C; °F= °F;
0=°C; 1=°F; 2=RH;
3=bar; 4=PSI, 5=off
various Pr1
PbC Kind of probe
Pt=Pt100; J=tcJ; c= tck;
S=tcS; Ptc=PTC; ntc=
NTC; 0-1=0÷1V; 10=
0÷10V; cur=0÷20mA
various Pr1
P3F
3
rd
wire presence
no=2 wires;
yES=3 wires
no
Pr2
HES Energy saving differential Down Sc./ Full Sc.
0.0
Pr2
i1F
Digital input configuration c-H / oFF / AuS / HES
/ EAL / bAL
EAL
Pr2
i1P
Digital input polarity
cL=closing;
oP=opening
cL
Pr2
did
Alarm delay for dig. input 0÷120m
0
Pr2
Adr
Serial address
RS485 address
1
Pr2
OnF oFF function enabling
no=not enabled;
oFF=enabled
no
Pr2
Ptb
Parameter table
Readable only
--
Pr2
rEL
Software release
Readable only
---
Pr2
Pr2
To access the Pr2
Readable only
321
Pr1
1
Only for XT221C;
2
Only for instrument with 4÷20mA or 0÷1V
or 0÷10V
Dixell s.r.l. Z.I. Via dell’Industria, 27
32010 Pieve d’Alpago (BL) ITALY
tel. +39 - 0437 - 98 33 - fax +39 - 0437 - 98 93 13
E-mail: [email protected] - http://www.dixell.com