DEFAULT SETTING VALUES

COD

Name

Range

°C/°F Lev

Set1 Set point1

LS1÷US1

0/32

-

Set2 Set point2

LS2÷US2

1/34

-

Hy1

Differential 1

-Full Sc./ Full Sc.

-1/-2

Pr1

Hy2

Differential 1

-Full Sc./ Full Sc.

-1/-2

Pr1

LS1

Minimum set point1

Down Sc./ Set1

min

Pr2

LS2

Minimum set point2

Down Sc./ Set2

min

Pr2

US1 Maximum set point1

Set1/ Full Sc.

max

Pr2

US2 Maximum set point2

Set2/ Full Sc.

max

Pr2

ouC Output configuration

ind= independent;
diP = dependent

ind

Pr2

S1C Action type output 1

in= Inverse; dir=direct

in

Pr2

S2C Action type output 2

in= Inverse; dir=direct

in

Pr2

Ac

Anti-short cycle delay:

0÷250 sec

0

Pr2

on

Minimum time a stage
stays switched ON

0÷250 sec

0

Pr2

ono

Minimum time between 2
following switching ON of
the same load

0÷120 min

0

Pr2

trd

Cycle length setting

0 ÷ 19:59 ( 0 =
disable )

0,00 Pr2

trM

Regulation setting

oFF = stop
regulation
on = regulation
continues

oFF Pr2

trS

Timer exhausted
signalling

no = buzzer off
yES = buzzer on

Yes Pr2

ALC Alarm configuration

rE=relat.; Ab= absolute

rE

Pr2

ALL Minumum alarm (ALC=rE)

                         (ALC=Ab)

0 ÷ |Start Sc.-Set1|
Start Sc.÷ ALu

10.0/

20

Pr2

ALU Maximum alarm (ALC=rE)

                          (ALC=Ab)

0 ÷ |Full Sc.-Set1|.
ALL÷ Full Scale

10.0/

20

Pr2

ALH Alarm recovery differential 0÷Full scale

2.0/4 Pr2

ALd Alarm delay

0÷999 min

15

Pr2

dAO Alarm delay at start up

0÷23h 50min

1.3

Pr2

So1

Out1 status with faulty pr. oFF=open  on=closed

oFF

Pr2

So2

Out2 status with faulty pr. oFF=open  on=closed

oFF

Pr2

tbA

1

Alarm relay disabling

no; yES

yES

Pr2

AS

1

Alarm relay polarity

CL÷oP

oP

Pr2

Lci

2

Start scale with current or
voltage input

-1999÷1999

various Pr1

Uci

2

End scale with current or
voltage input

-1999÷1999

various Pr1

OPb Probe calibration

-Full Sc./ Full Sc.

0.0

Pr1

rES

Resolution

in=NO; dE=0,1;
cE=0,01

in

Pr2

UdM Measurement unit (temp.)

        (current/voltage)

°C=°C; °F= °F;
0=°C; 1=°F; 2=RH;
3=bar; 4=PSI, 5=off

various Pr1

PbC Kind of probe

Pt=Pt100; J=tcJ; c= tck;
S=tcS; Ptc=PTC; ntc=
NTC; 0-1=0÷1V; 10=
0÷10V; cur=0÷20mA

various Pr1

P3F

3

rd

 wire presence

no=2 wires;
yES=3 wires

no

Pr2

HES Energy saving differential Down Sc./ Full Sc.

0.0

Pr2

i1F

Digital input configuration c-H / oFF / AuS / HES

/ EAL / bAL

EAL

Pr2

i1P

Digital input polarity

cL=closing;
oP=opening

cL

Pr2

did

Alarm delay for dig. input 0÷120m

0

Pr2

Adr

Serial address

RS485 address

1

Pr2

OnF oFF function enabling

no=not enabled;
oFF=enabled

no

Pr2

Ptb

Parameter table

Readable only

--

Pr2

rEL

Software release

Readable only

---

Pr2

Pr2

To access the Pr2

Readable only

321

Pr1

Only for XT221C; 

2

 Only for instrument with 4÷20mA or 0÷1V

or 0÷10V

Dixell s.r.l.  Z.I. Via dell’Industria, 27
32010 Pieve d’Alpago (BL) ITALY
tel. +39 - 0437 - 98 33  -  fax +39 - 0437 - 98 93 13
E-mail: [email protected]  -  http://www.dixell.com