The security code is “321”.

5.

 

If the security code is correct the access to “Pr2” is
enabled by pressing “SET” on the last digit.

Another possibility is the following:
After switching ON the instrument, within 30 seconds, push
SET + 

8

8

 keys together for 3s: the Pr2 menu will be entered.

5.12

 

HOW TO MOVE A PARAMETER FROM THE

“PR2” MENU TO “PR1” AND VICEVERSA.

Each parameter present in “Pr2” MENU can be removed or put
into “Pr1”, user level, by pressing “SET + 

8

8

.

In “Pr2” when a parameter is present in “Pr1” the LED 

 is

on.

5.13

 

HOW TO CHANGE A PARAMETER

To change a parameter value operates as follows:
1.

 

Enter the Programming mode

2.

 

Select the required parameter.

3.

 

Press the “SET” key to display its value.

4.

 

Use “UP” or “DOWN” to change its value.

5.

 

Press “SET” to store the new value and move to the

following parameter.

TO EXIT: Press SET + UP or wait 15s without pressing a key.
NOTE: the set value is stored even when the procedure is
exited by waiting the time-out to expire.

5.14

 

HOW TO LOCK THE KEYBOARD

1. 

 

Keep pressed for more than 3 s the the 

9

9

and 

8

8

 keys.

2. 

 

The “POF” message will be displayed and the keyboard
will be locked. At this point it will be possible only to see
the set point or the MAX o Min temperature stored

3. 

 

If a key is pressed more than 3s the “POF” message will
be displayed.

5.15

 

TO UNLOCK THE KEYBOARD

Keep pressed together for more than 3s the the 

9

9

and 

8

8

keys, till the “Pon” message will be displayed.

5.16

 

ON/OFF FUNCTION

TO SWITCH THE INSTRUMENT ON/OFF: If the function is
enabled (par. onF=yES), by pressing the SET key for more
than 4s the controller is switched OFF. To switch the
instrument on again press the SET key.

6.

 

PROBES AND MEASURING RANGE

Probe

Down Scale

Full Scale

NTC

-40°C/-40°F

110°C / 230 °F

PTC

-50°C / -58°F

150°C / 302°F

Pt100

-200°C / -328°F

600°C / 1112°F

TcK

0°C / 32°F

1300°C / 1999°F

TcJ

0°C / 32°F

600°C / 1112°F

TcS

0°C / 32°F

1400°C / 1999°F

7.

 

LIST OF PARAMETERS

REGULATION

Hy1 Intervention differential for set point1 (-Full Sc. / Full

Sc.). It can be set with positive value or with negative
value. The kind of action depends on the S1C parameter:
dir = direct or in = inverse.

Hy2 Intervention differential for set point2: (-Full Sc. / Full

Sc.). It can be set with positive value or with negative
value. The kind of action depends on the S2C parameter:
dir = direct or in = inverse.

LS1 Minimum set point1: (Down Sc.÷ Set1) Sets the

minimum acceptable value for the set point1.

LS2 Minimum set point2: (Down Sc.÷ Set2) Sets the

minimum acceptable value for the set point2.

US1 Maximum set point1: (Set1÷ Full Sc.) Sets the maximum

acceptable value for set point1.

US2 Maximum set point2: (Set2÷ Full Sc.) Sets the maximum

acceptable value for set point2.

ouC Output connections (diP=dependent;  ind=independent)

select if SET2 is independent from SET1 or if the SET2
depends on SET1 (so Set2= SET1+SET2).

S1C  Action type output 1S1C=in  inverse action (heating/

humidifying /increase pressure); S1C=dir  direct action
(cooling / dehumidifying /decrease pressure).

S2C Action type output 2S2C=in  inverse action (heating/

humidifying /increase pressure); S2C=dir  direct action
(cooling / dehumidifying /decrease pressure).

AC  Anti-short cycle delay: (0÷250 sec) Minimum time

between the switching off and the following switching on

on Minimum time a stage stays switched ON (0÷250 sec)
ono:Minimum time between 2 following switching ON of

the same load (0÷120 min).

CYCLE REGULATION

trd Cycle length setting  (0÷19.59h)
trM Regulation setting

oFF the regulation is enabled only during the cycle.
on the regulation is always active, the cycle consists of
starting the timer and signalling when this has expired.

trS Timer exhausted signallin

no  the buzzer is not activated; yES: the buzzer is
activated.

ALARMS

ALC Alarms configuration: it determines if alarms are relative

to set point1 or referred to absolute values.
rE relative to set point1; Ab absolute temperature

ALL  Minimum alarm:

with ALC=rE: relative to set point1, (0÷|Down Sc.-Set1|)
this value is subtracted from the set point1. The alarm
signal is enabled when the temperature goes below the
“SET1-ALL” value.
with ALC=Ab absolute temperature, (Down Scale ÷ ALu)
minimum alarm is enabled when the temperature goes
below the “ALL” value.

ALU  Maximum alarm:

with ALC=rE: alarm relative to set point1, (0÷|Full Sc.-
Set1|) Maximum alarm is enabled when the temperature
exceeds the “SET1+ALU” value.
with ALC=Ab: absolute alarm, (ALL÷Full Sc.) Maximum
alarm is enabled when the temperature exceeds the
“ALU” value.

ALH Temperature alarm for alarm recovery: (0,1÷Full scale)

Differential for alarm reset, always positive.

ALd Alarm  delay:(0÷999 min) time interval between the

detection of an alarm condition and alarm signalling.

dAo Delay of alarm at start-up: (0÷23.5h) time interval

between the detection of the alarm condition after
instrument power on and alarm signalling.

So1 Output 1 status with faulty probe: So1=oFF open;

So1=on closed.

So2 Output 2 status with faulty probe: So2=oFF open;

So2=on closed.

tbA Status of alarm relay after pushing a key. (XT221C

only): oFF = relay disabled; on = relay enabled.

AS Alarm relay configuration (XT221C only): cL = 5-6

terminals open with alarm; oP = 5-6 terminals closed with
alarm.

PROBES AND DISPLAY

LCI  Start of scale, only with current or voltage input:

(-1999÷1999) Adjustment of  read out corresponding to
4mA or 0V input signal.

UCI  End of scale, only with current or voltage input

(-1999÷1999) Adjustment of  read out corresponding to
20mA or 1V or 10V input signal.

oPb Probe calibration: (-Full sc.÷Full sc.) allows to adjust

possible offset of the probe.

rES Decimal point ON/OFF: (rES=in OFF; rES=dE ON; rES=

cE with 2 decimal points, only for current or voltage input)
select the resolution of the controller.
NOTE:  the decimal point selection is not available on
models with thermocouple input.

UdM  Measurement unit: it depends on models:

for temperature:°C = Celsius; °F = Fahrenheit.
with 4÷20mA, 0÷1V, 0÷10V input : 0= °C; 1= °F, 2=
%RH, 3=bar, 4=PSI, 5=no measurement unit.

PbC Probe selection: it sets the kind of probe. It depends on

models
for temperature NTC/PTC: Ptc = PTC; ntc = ntc.
for temperature standard: Pt= Pt100, = J
thermocouple, 

c = K thermocouple, = S thermocouple;

Ptc = PTC; ntc = ntc.
with 4÷20mA, 0÷1V, 0÷10V input : cur=4÷20mA, 0-1=
0÷1V, 10= 0÷10V.

P3F Third wire presence for Pt100 probe: for using 2 or 3

wires Pt100 probes: no = 2 wires probe; yES = 3 wires
probe.

DIGITAL INPUT

HES Set point 1 changes during the Energy Saving cycle:

(Down Sc./Full Sc.) sets the variation of the set point 1
during the Energy Saving cycle.

i1F Digital input operating mode: configure the digital input

function: c-H = to invert the kind of action: direct - reverse;
oFF = to switch the controller off.; AUS = Not used; HES =
Energy Saving;  EAL = generic external alarm;

bAL  =

serious external alarm: it switches off the loads.

i1P Digital input polarity:

CL : the digital input is activated by closing the contact;
OP : the digital input is activated by opening the contact

did Digital input alarm delay: (0

÷

120 min) delay between

the detection of the external alarm condition (i1F= EAL or
i1F = bAL) and its signalling.

OTHER

Adr RS485 serial address (0÷247) identifies the instrument

within a control or supervising system.

onF Swithching ON/OFF enabling  from keyboard: (no  =

disabled; yES=enabled) It permits the switching ON/OFF
of the instrument by pressing the SET1 key for more than
4s.

Ptb Parameters table: (read only) Shows the code of the

parameters map.

rEL Software release: (read only)
Pr2 To access the Pr2 parameter programming menu.

8.

 

INSTALLATION AND MOUNTING

Instrument XT220C and XT221C shall be mounted on vertical
panel, in a 29x71 mm hole, and fixed using the special
brackets supplied.

To obtain an IP65 protection grade use the front panel rubber
gasket (mod. RG-C).
The temperature range allowed for correct operation is 0

÷

60

°C. Avoid places subject to strong vibrations, corrosive gases,
excessive dirt or humidity. The same recommendations apply
to probes. Let air circulate by the cooling holes.

9.

 

ELECTRICAL CONNECTIONS

The instruments are provided with screw terminal block to
connect cables with a cross section up to 2,5 mm

2

. Before

connecting cables make sure the power supply complies with
the instrument’s requirements. Separate the input connection
cables from the power supply cables, from the outputs and the
power connections. Do not exceed the maximum current
allowed on each relay, in case of heavier loads use a suitable
external relay.

10.

 

SERIAL CONNECTIONS

All models can be connected to the monitoring and supervising
system XJ500 using the serial port. The external XJ485 serial
module to interface the instrument with the monitoring and
supervising system XJ500 is required.
The standard ModBus RTU protocol it is used.
NOTE: Instruments with current or voltage input and 230V
or 115V supply, cannot be connected to the XJ485 serial
module.

11.

 

HOW TO USE THE HOT KEY

11.1

 

HOW TO PROGRAM A HOT KEY FROM THE

INSTRUMENT (UPLOAD)

1.

 

Program one controller with the front keypad.

2.

 

When the controller is ON, insert the “Hot key” and push

9

9

 key; the  "uPL" message appears followed a by

flashing “End”

3.

 

Push “SET” key and the End will stop flashing.

4.

 

Turn OFF the instrument remove the “Hot Key”, then
turn it ON again.

NOTE: the “Err” message is displayed for failed programming.
In this case push again 

9

9

 key if you want to restart the upload

again or remove the “Hot key” to abort the operation.

11.2

 

HOW TO PROGRAM AN INSTRUMENT USING

A HOT KEY (DOWNLOAD)

1.

 

Turn OFF the instrument.