ALU  MAXIMUM temperature alarm

: (with 

ALC = 0

 or 

2

, from 0 to 50°C/90°F; with 

ALC = 1

 o 

3

, from 

ALL

÷

99°C/196°F) when this temperature is reached  the alarm is enabled, after the ALd delay time. 

ALL  Minimum temperature alarm

:  (with

 ALC = 0

 or 

2

, from 0 to 50°C/90°F; with  

ALC = 1

 or 

3

, from -

57°C/°F to ALU) when this temperature is reached  the alarm is enabled, after the ALd delay time. 

ALd  Temperature alarm delay

: (0

÷

120 min) time interval between the detection of an alarm condition and 

alarm signalling. 

dAO  Delay of temperature alarm at startup

: (from 0 min to 720 min; res. 10min) time interval between the 

detection of the temperature alarm condition after instrument power on and alarm signalling. 

OdS Outputs activation delay at start up: 

(0÷120min) This function is enabled at the initial start up of the 

instrument and inhibits any output activation for the period of time set in the parameter.  

CCt  Compressor ON time during fast freezing

: (0÷990min; res. 10 min) allows to set the length of the 

continuous cycle. Can be used, for instance, when the room is filled with new products. 

dAF Defrost delay after fast freezing

: (with tdF=0 or 1: 0÷120min; with tdF=2 or 3: 0

÷

120sec) time interval 

between the end of the fast freezing and the following defrost related to it. 

IdF   Interval between defrost cycles

: (with tdF=0 or 1: 0÷120h; with tdF=2 or 3: 0

÷

120min) Determines the 

time interval between the beginning of two defrost cycles. 

dSd Start defrost delay

:(with tdF=0 or 1: 0÷59min; with tdF=2 or 3: 0

÷

59sec) This is useful when different 

defrost start times are necessary to avoid overloading the plant.  

MdF (Maximum) length for defrost

:(with tdF=0 or 1: 0÷120min; with tdF=2 or 3: 0

÷

120sec) When 

EdF = 0

(not evaporator probe: timed defrost) it sets the defrost duration, when 

EdF = 1

 (defrost end based on 

temperature) it sets the maximum length for defrost. 

dtE  Defrost termination temperature

: (-57 

÷

 99°C/-57

÷

196°F) (Enabled only when EdF=1) sets the 

temperature measured by the evaporator probe, which causes the end of defrost. 

dFd   Temperature displayed during defrost

: (0 = real temperature; 1 = temperature at defrost start; 2 = set 

point; 3 = “dEF” label) 

dAd   MAX display delay after defrost

: (0

÷

120 min). Sets the maximum time between the end of defrost and 

the restarting of the real room temperature display. 

tdF Defrost type

:  

(0 = electrical heater, long time; 1 = hot gas, long time; 2=OFF compressor, short 

time; 3= ON compressor, short time) 

EdF Evaporator probe presence

: (0 = Not present: timed defrost end; 1=present: defrost end based on 

temperature)

 

Fdt   Drain  time

: (with tdF=0 or 1: 0÷120min; with tdF=2 or 3: 0÷120sec) time interval between reaching 

defrost termination temperature and the restoring of the control’s normal operation. This time allows the 
evaporator to eliminate water drops that might have formed due to defrost. 

dPO  First defrost after startup

: (0 = Immediately; 1 = after the IdF time) 

FnC  Fan operating mode

: (0 = runs with the compressor, OFF during defrost; 1 = continuous mode, OFF 

during defrost; 2 = runs with the compressor, ON during defrost; 3 = continuous mode, ON during 
defrost; 4 = fan relay is used as 2° compressor output) 

FSt  Fan stop temperature

: (-57

÷

99°C/196°F) setting of temperature, detected by evaporator probe, above 

which the fan is always OFF. 

Fnd  Fan delay after defrost:

 (with tdF=0 or 1: 0÷120min; with tdF=2 or 3: 0

÷

120sec) The time interval 

between end of defrost and evaporator fans start.

 

Ot  Thermostat probe calibration

: (-12.0

÷

12.0°C; -120

÷

120°F) allows to adjust possible offset of the 

thermostat probe. 

OE  Evaporator probe calibration

: (-12.0

÷

12.0°C; -120

÷

120°F) allows to adjust possible offsets of the 

evaporator probe. 

CF  Temperature measurement unit

:  0 = Celsius; 1 = Fahrenheit.  

WARNING: When the measurement unit is changed the SET point and the values  of the parameters Hy, 
LS, US, ALU, ALL, dtE, FSt, Ot and OE have to be modified 

COn Compressor ON time with faulty probe

 (0

÷

120 min) time during which the compressor is active in case 

of faulty thermostat probe. With COn=0 compressor is always OFF. 

COF Compressor OFF time with faulty probe

 (0

÷

120 min) time during which the compressor is off in case 

of faulty thermostat probe. With COF=0 compressor is always active. 

 

 

952057-58

 

XR160C - XR170C - XR160D - XR170D - XR162C - XR172C 

6/

י

 

 

Summary of Contents for XR160C

Page 1: ...________________ 4 5 1 Function Menu_______________________________________________________ 4 5 2 List of functions ______________________________________________________ 4 5 3 Exit Timeout___________...

Page 2: ...eful 2 GENERAL DESCRIPTION Models XR160C and XR170C 32x74 mm format are microprocessor based controllers suitable for applications on medium or low temperature refrigerating units They are provided wi...

Page 3: ...ing defrost After defrost there is a timed fan delay allowing for drip time set by means of the Fnd parameter FnC 2 fans will switch ON and OFF with the compressor and run during defrost FnC 3 fans wi...

Page 4: ...le LED MODE Function ON Compressor enabled FLASHING Programming Phase flashing with LED Anti short cycle delay enabled ON Fan enabled FLASHING Programming Phase flashing with LED ON Defrost enabled FL...

Page 5: ...put into Pr1 user level by pressing SET DOWN When a parameter is present in Pr1 LED is on 5 5 Changing a parameter s value Each parameter is identified by a special alphanumeric code label To change...

Page 6: ...hich causes the end of defrost dFd Temperature displayed during defrost 0 real temperature 1 temperature at defrost start 2 set point 3 dEF label dAd MAX display delay after defrost 0 120 min Sets the...

Page 7: ...iquid infiltration It is recommended to place the thermostat probe away from air streams to correctly measure the average room temperature Place the defrost termination probe among the evaporator fins...

Page 8: ...starts Alarms dEA and FF automatically stop after 30 minutes 10 TECHNICAL DATA Housing self extinguishing ABS Case XR160C XR162C XR172C frontal 32x74 mm depth 60mm XR170C frontal 32x74 mm depth 70mm X...

Page 9: ...172C buzzer for an acoustic signal of alarms Data storing on the non volatile memory EEPROM Operating temperature 0 60 C Relative humidity 20 85 no condensing Storage temperature 30 85 C Measuring and...

Page 10: ...F 1 120 Pr2 6 dSd 1 120 Pr2 0 MdF 0 120 Pr2 30 dtE 57 50 C o 196 F Pr2 8 46 dFd 0 Real 1 Start 2 Set 3 dEF Pr2 1 dAd 0 120 Pr2 30 tdF 0 Eletrical 1 Hot gas Long Time 2 Relay OFF 3 Relay ON Short time...

Reviews: