Installing and Operating Instructions

 

release  7.0

 
4. “

Pr2

”: includes all the instrument’s parameters (at installer level). It can be accessed through a security 

code. Hence it is possible to modify all parameters and add or remove parameters from “Pr1” (user level) 
by pressing 

“SET”

 + 

“DOWN”

. When a parameter is enabled at user level, LED 

 (Alarm LED) is on. 

5. “

LOC

”: keyboard lock. When enabled the “POF” flashing message is displayed for a few seconds then the 

keys are locked . Only the set point display is enabled. 

6. “

Out

”: exits from menu. 

 

From functions “dFt” and “Pt2” the instrument will go back to “Functions Menu” by time out. From the all other 
functions the instrument will display again the room temperature by time out. 

5.3 Exit Timeout 

If no key is pressed within 15 seconds the instrument switches back to room temperature display mode. 

5.4  Accessing “Pr2” and SECURITY CODE input 

To access parameters in “

Pr2

” a security code is required. 

1.  Enter Function Menu, select label “Pr2” and press the “

SET

” key. The “PAS” flashing message is 

displayed, shortly followed by “0 - -” with a flashing zero. 

2. Use 

“UP”

 or 

“DOWN”

 to input the security code in the flashing digit; 

3.  Confirm the figure by pressing “

SET

”.  

4.  Repeat operations 2 and 3 for the other digits. 
5.  If the security code is correct the access to “Pr2” is enabled by pressing “

SET

” on the last digit, otherwise 

the security code input process restarts from the beginning. 

 
If no key is pressed within 15 seconds the instrument reverts to room temperature display mode. 

SECURITY CODE is  

321 

NOTE

: each parameter in “Pr2” can be removed or put into “Pr1” (user level) by pressing 

“SET”

 + 

“DOWN”

When a parameter is present in “Pr1” LED 

 is on. 

5.5  Changing a parameter’s value 

Each parameter is identified by a special alphanumeric code (label). 
To change the parameter’s value operate as follows: 
1.  Enter the Function Menu and select the parameters’ list you require: “

Pr1”

 or “

Pr2”

2.  Browse the parameters’ list using “

UP

” or “

DOWN

” until the required parameter is displayed. 

3.  Press the “

SET

” key to display its value. 

4. Use “

UP

” or “

DOWN

” to change its value. 

5. Press “

SET

” to store the new value and skip to the following parameter. 

 

TO EXIT

: Press “

SET

”+”

UP

” or  wait 15s without pressing a key. 

NOTE

: the set value is stored even when the procedure is exited by waiting the timeout to expire. 

6.  LIST OF PARAMETERS 

Hy  Differential

: (0,2°C ÷ 12,0°C / 2°F ÷120°F) Intervention differential for set point, always positive. 

Compressor Cut IN is Set Point Plus Differential (Hy). Compressor Cut OUT is when the temperature 
reaches the set point. 

LS   Minimum set point

: (-57°C÷SET/-57°F÷SET): Sets the minimum acceptable value for the set point. 

US   Maximum set point

: (SET÷99°C/SET÷196°F). Set the maximum acceptable value for set point. 

AC   Anti-short cycle delay

: (0

÷

30 min) minimum interval between the compressor stop and the following 

restart. 

ALC  Temperature alarms configuration

: (0 = temperature alarm are related to SET, alarm relay and buzzer 

works in parallel; 1 = temperature alarms are referred to absolute values; alarm relay and buzzer work in 
parallel; 2= referred to set, alarm relay is active when the alarm is active; 3= absolute temperature, alarm 
relay is active when the alarm is active) determines if temperature alarms are referred to set point or if 
alarms are referred to absolute temperatures. 

 

952057-58

 

XR160C - XR170C - XR160D - XR170D - XR162C - XR172C 

5/

י

 

 

Summary of Contents for XR160C

Page 1: ...________________ 4 5 1 Function Menu_______________________________________________________ 4 5 2 List of functions ______________________________________________________ 4 5 3 Exit Timeout___________...

Page 2: ...eful 2 GENERAL DESCRIPTION Models XR160C and XR170C 32x74 mm format are microprocessor based controllers suitable for applications on medium or low temperature refrigerating units They are provided wi...

Page 3: ...ing defrost After defrost there is a timed fan delay allowing for drip time set by means of the Fnd parameter FnC 2 fans will switch ON and OFF with the compressor and run during defrost FnC 3 fans wi...

Page 4: ...le LED MODE Function ON Compressor enabled FLASHING Programming Phase flashing with LED Anti short cycle delay enabled ON Fan enabled FLASHING Programming Phase flashing with LED ON Defrost enabled FL...

Page 5: ...put into Pr1 user level by pressing SET DOWN When a parameter is present in Pr1 LED is on 5 5 Changing a parameter s value Each parameter is identified by a special alphanumeric code label To change...

Page 6: ...hich causes the end of defrost dFd Temperature displayed during defrost 0 real temperature 1 temperature at defrost start 2 set point 3 dEF label dAd MAX display delay after defrost 0 120 min Sets the...

Page 7: ...iquid infiltration It is recommended to place the thermostat probe away from air streams to correctly measure the average room temperature Place the defrost termination probe among the evaporator fins...

Page 8: ...starts Alarms dEA and FF automatically stop after 30 minutes 10 TECHNICAL DATA Housing self extinguishing ABS Case XR160C XR162C XR172C frontal 32x74 mm depth 60mm XR170C frontal 32x74 mm depth 70mm X...

Page 9: ...172C buzzer for an acoustic signal of alarms Data storing on the non volatile memory EEPROM Operating temperature 0 60 C Relative humidity 20 85 no condensing Storage temperature 30 85 C Measuring and...

Page 10: ...F 1 120 Pr2 6 dSd 1 120 Pr2 0 MdF 0 120 Pr2 30 dtE 57 50 C o 196 F Pr2 8 46 dFd 0 Real 1 Start 2 Set 3 dEF Pr2 1 dAd 0 120 Pr2 30 tdF 0 Eletrical 1 Hot gas Long Time 2 Relay OFF 3 Relay ON Short time...