Operating Manual 

 

2/3 

 

8. PARAMETERS 

REGULATION 

 

Hy Differential: 

(0,1°C 

÷

 25°C / 1°F ÷ 45°F) Intervention differential for set point. Compressor Cut 

IN is SET POINT + differential (Hy). Compressor Cut OUT is when the temperature reaches the 

set point. 

LS  Minimum SET POINT:

 (-55°C÷SET/-67°F÷SET): Sets the minimum value for the set point.. 

US  Maximum SET POINT:

 (SET÷99°C/ SET÷99°F). Set the maximum value for set point. 

ot  First probe calibration: 

(-9.9÷9.9°C / -17°F ÷ 17°F) allows to adjust possible offset of the first 

probe. 

P2  Evaporator probe presence:

 

n=

 not present; 

y=

 the defrost stops by temperature. 

oE  Second probe calibration: 

(-9.9÷9.9°C / -17°F ÷ 17°F) allows to adjust possible offset of the 

second probe. 

od  Outputs activation delay at start up:

 (0÷99min) This function is enabled at the initial start up of 

the instrument and inhibits any output activation for the period of time set in the parameter.  

AC   Anti-short  cycle  delay

: (0÷50 min) minimum interval between the compressor stop and the 

following restart. 

Cy  Compressor ON time with faulty probe: 

(0÷99 min) time during which the compressor is active 

in case of faulty thermostat probe. With Cy=0 compressor is always OFF. 

Cn  Compressor OFF time with faulty probe: 

(0÷99 min) time during which the compressor is OFF 

in case of faulty thermostat probe. With Cn=0 compressor is always active. 

 

DISPLAY 

 

CF Measurement 

unit: 

(°C÷°F) 

°C

 =Celsius; 

°F

 =Fahrenheit. 

WARNING

: When the measurement 

unit is changed the SET point and the values  of the parameters Hy, LS, US, oE, o1, AU, AL 

have to be checked and modified if necessary. 

rE  Resolution (only for °C):

(dE ÷ in) 

dE

= decimal between -9.9 and 9.9°C; 

in

= integer 

Ld Default 

display: 

(P1 ÷ P2) P1= thermostat probe; P2= evaporator probe. SP=Set point (only 

XR04CX) 

dy Display 

delay: 

(0

÷

15 min.) when the temperature increases, the display is updated of 1 °C/1°F 

after this time. 

 

DEFROST 

 

td Defrost 

type: 

(EL – in)

 EL= 

 electrical heater, compressor OFF; 

in=

 hot gas, compressor ON;

 

dE  Defrost termination temperature: 

(-55÷50°C / -67÷99°F) if 

P2=Y

 it sets the temperature 

measured by the evaporator probe, which causes the end of defrost. 

 

id  Interval between defrost cycles: 

(0÷99 minutes) Determines the time interval between the 

beginning of two defrost cycles.  

Md  Maximum length for defrost: 

(0÷99 min. with 0 no defrost) when 

P2=n

, (not evaporator probe: 

timed defrost) it sets the defrost duration, when 

P2 = y

 (defrost end based on temperature) it sets 

the maximum length for defrost. 

dd  Start defrost delay: 

( 0÷99min) This is useful when different defrost start times are necessary to 

avoid overloading the plant.

 

dF  Display during defrost: 

(rt / it / SP / dF) 

rt=

 real temperature; 

it=

 start defrost temperature; 

SP=

 

SET-POINT; 

dF=

 label 

dF. 

dt   Drip time: 

(0÷99 min)

 

time interval between reaching defrost termination temperature and the 

restoring of the control’s normal operation. This time allows the evaporator to eliminate water 

drops that might have formed due to defrost. 

dP  Defrost at power –on: 

(y÷n) 

y=

 at power on defrost starts; 

n=

 defrost doesn’t start at power-on 

 

FANS 

 

FC Fans 

operating 

mode: 

(cn, on, cY, oY) 

cn= 

in runs with the compressor, OFF during defrost; 

on=

 continuous mode, OFF during defrost;; 

cY=

 runs with the compressor, ON during defrost; 

oY=

 continuous mode, ON during defrost. 

Fd  Fans delay after defrost: 

(0÷99 min)

 

Interval between end of defrost and evaporator fans start. 

FS  Fans stop temperature: 

(-55÷50°C / -67°F ÷ 99°F) setting of temperature, detected by 

evaporator probe, above which fans are always OFF. 

 

ALARMS

 

 

AU  Maximum temperature alarm: 

(AL÷99°C/99°F) when this temperature is reached  the alarm is 

enabled, after the “

Ad

” delay time. 

AL  Minimum temperature alarm: 

(-55÷AU°C /-67÷AU°F) when this temperature is reached  the 

alarm is enabled, after the “

Ad

” delay time. 

Ad  Temperature alarm delay:

 (0÷99 min) time interval between the detection of an alarm condition 

and alarm signalling. 

dA  Exclusion of temperature alarm at startup: 

(0÷99 min) time interval between the detection of 

the temperature alarm condition after instrument power on and alarm signalling. 

DIGITAL INPUT 

 

iP   Digital input polarity:

 (oP ÷ cL) 

oP

= activated by closing the contact; 

cL

= activated by opening 

the contact; 

iF  Digital input configuration: 

(EA/bA/do/dF/Au/Hc)

 EA= 

external alarm: “EA” message is 

displayed; 

bA

= serious alarm “CA” message is displayed; 

do

= door switch function; 

dF

= defrost 

activation; 

Au 

=not used; 

Hc=

 inversion of the kind of action; 

di  Digital input delay:

 (0÷99 min) with 

iF=EA

 or 

bA

 delay between the detection of the external 

alarm condition and its signalling. . With 

iF=do

 it represents the delay to activate the door open 

alarm. 

dC  Compressor and fan status when open door

: (no/Fn/cP/Fc): 

no

= normal; 

Fn

 = Fans OFF; 

cP

 

=Compressor OFF; 

Fc

 = Compressor and fans OFF; 

rd

 

Regulation with door open

: (n÷y) 

n

 = no regulation if door is opened; 

Y

= when di is elapsed 

regulation restarts even if door open alarm is present; 

OTHER 

 

d1   Thermostat probe display

 

(read only)

  

d2  Evaporator probe display

 

(read only)

 

Pt   Parameter code table 

rL   Software release 

9.  DIGITAL INPUTS (ONLY XR03CX) 

The free voltage digital input is programmable in different configurations by the “

i1F

” parameter. 

 

 

DOOR SWITCH (iF=do) 

 

It signals the door status and the corresponding relay output status through the “

dC

” parameter: 

no

 = 

normal (any change); 

Fn

 = Fan OFF; 

CP

 = Compressor OFF; 

FC

 = Compressor and fan OFF. 

Since the door is opened, after the delay time set through parameter “

di

”, the door alarm is enabled, 

the display shows the message “

dA

” and 

the regulation restarts if rd = y.

 The alarm stops as soon 

as the external digital input is disabled again. With the door open, the high and low temperature alarms 

are disabled. 

 

EXTERNAL ALARM (iF=EA) 

 

As soon as the digital input is activated the unit will wait for “

di

” time delay before signalling the “

EA

” 

alarm message. The outputs status don’t change. The alarm stops just after the digital input is de-

activated. 

 

SERIOUS ALARM (iF=bA) 

When the digital input is activated, the unit will wait for “

di

” delay before signalling the “

CA

” alarm 

message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-

activated. 

 

START DEFROST (iF=dF) 

It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation will 

restart only if the digital input is disabled otherwise the instrument will wait until the “

Md

” safety time is 

expired. 

INVERSION OF THE KIND OF ACTION: HEATING - COOLING  (iF=Hc) 

 

This function allows to invert the regulation of the controller: from cooling to heating and viceversa. 

10.  INSTALLATION AND MOUNTING 

 

Instrument 

XR06CX

 shall be mounted on vertical panel, in a 

29x71 mm hole, and fixed using the special bracket supplied. 
The temperature range allowed for correct operation is 0

÷

60 °C. 

Avoid places subject to strong vibrations, corrosive gases, 

excessive dirt or humidity. The same recommendations apply to 

probes. Let air circulate by the cooling holes. 

 

 

11. ELECTRICAL CONNECTIONS 

The instrument is provided with screw terminal block to connect cables with a cross section up to 2,5 

mm

2

. Before connecting cables make sure the power supply complies with the instrument’s 

requirements. Separate the probe cables from the power supply cables, from the outputs and the 

power connections. Do not exceed the maximum current allowed on each relay, in case of heavier 

loads use a suitable external relay. 

11.1

 

PROBES 

 

The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid 

infiltration. It is recommended to place the thermostat probe away from air streams to correctly 

measure the average room temperature. Place the defrost termination probe among the evaporator 

fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during 

defrost, to prevent premature defrost termination. 

12.  HOW TO USE THE HOT KEY 

12.1

 

HOW TO PROGRAM THE HOT KEY FROM THE INSTRUMENT (UPLOAD) 

1.

 

Program one controller with the front keypad. 

2.

 

When the controller is ON, insert the “Hot key” and push   key; the  "

uP

" message appears 

followed a by flashing “

Ed

” 

3.

 

Push “

SET

” key and the “

Ed

” will stop flashing. 

4.

 

Turn OFF the instrument remove the “Hot Key”, then turn it ON again. 

 

NOTE

: the “

Er

” message is displayed for failed programming. In this case push again o key if you want 

to restart the upload again or remove the “Hot key” to abort the operation. 

12.2

 

HOW TO PROGRAM AN INSTRUMENT USING HOT KEY (DOWNLOAD) 

1.

 

Turn OFF the instrument. 

2.

 

Insert  a 

programmed “Hot Key” into the 5 PIN receptacle

 and then turn the Controller ON. 

3.

 

Automatically the parameter list of the “Hot Key” is downloaded into the Controller memory, the 

do

” message is blinking followed a by flashing “

Ed

”. 

4.

 

After 10 seconds the instrument will restart working with the new parameters.  

5.

 

Remove the “Hot Key”.. 

 

NOTE

: the “

Er

” message is displayed for failed programming. In this case push again o key if you want 

to restart the upload again or remove the “Hot key” to abort the operation. 

13. ALARM SIGNALLING 

Mess.  Cause 

Outputs 

"P1"  

Room probe failure 

Compressor output according to “Cy” e “Cn”  

"P2"  

Evaporator probe failure 

Defrost end is timed 

"HA" 

Maximum temperature alarm 

Outputs unchanged 

"LA" 

Minimum temperature alarm 

Outputs unchanged 

“EA” 

External alarm 

Outputs unchanged 

“CA” 

Serious external alarm 

All outputs OFF 

“dA” 

Door Open 

Compressor and fans restarts  

13.1

 

ALARM RECOVERY 

Probe alarms 

P1

” and “

P2”

 start some seconds after the fault in the related probe; they automatically 

stop some seconds after the probe restarts normal operation. Check connections before replacing the 

probe. Temperature alarms “

HA

” and “

LA

” automatically stop as soon as the temperature returns to 

normal values. 

Alarms 

“EA”

 and 

“CA” 

(with iF=bL)

 

recover as soon as the digital input is disabled. 

14. TECHNICAL DATA 

Housing: 

self extinguishing ABS.

 

Case: 

frontal 32x74 mm; depth 60mm; 

Reviews: