14.  CONNECTIONS 

14.1

 

XR01-02CX – 1 X 8A – 12VAC/DC 

 

 

 

14.2

 

XR01-02CX – 20A OR 8A -- 110VAC OR 230VAC 

 

 

 

NOTE: 

The compressor relay is 20(8)A or 8(3)A depending on the model.

 

NOTE: 

120Vac connect to 6-7. 

15.  DEFAULT SETTING VALUES 

 

LAB

EL

 

DESCRIPTION 

RANGE 

DEFAULT 

REGULATION

 

Hy 

Differential 

0.1 ÷ 25°C/1 ÷ 45°F 

2.0°C / 4 °F 

LS 

Minimum Set Point 

-55°C÷SET/-67°F÷SET 

-55 °C /-

55°F 

US 

Maximum Set Point 

SET÷99°C/ SET÷99°F 

99 °C / 

99°F 

ot 

First probe calibration 

-9.9÷9.9°C/-17÷17°F  

0.0 

od 

Outputs activation delay at start up 

0 ÷ 99 min 

AC 

Anti-short cycle delay 

0 ÷ 50 min 

Cy 

Compressor ON time faulty probe 

0 ÷ 99 min 

15 

Cn 

Compressor OFF time faulty probe 

0 ÷ 99 min 

30 

CH

 

Kind of action

 

cL ÷ Ht 

cL 

DISPLAY

 

CF 

Measurement units 

°C - °F 

°C / °F 

rE 

Resolution (only for °C) 

dE 

– in 

dE 

dy 

Display delay 

0 ÷ 15 min 

DEFROST (Only XR02CX)

 

id 

Interval between defrost cycles 

0 ÷ 99 hours 

Md 

Maximum length for defrost 

0 ÷ 99 min. 

30 

dF 

Display during defrost 

rt 

– in – SP – dF 

it 

ALARMS

 

AU 

Maximum temperature alarm 

ALL÷99°C / ALL÷99°F 

99 °C / 99 

°F 

AL 

Minimum temperature alarm 

-55°C÷ALU/-67°F÷ALU 

-55 °C / -55 

°F 

Ad 

Temperature alarm delay 

0 ÷ 99 min 

15 

dA 

Exclusion  of  temperature  alarm  at 
startup 

0 ÷ 99 min 

90 

DIGITAL INPUT

 

iP 

Digital input polarity 

cL 

– oP 

cL 

iF 

Digital input configuration 

EA 

– bA – do – dF – Au 

– Hc 

EA 

di 

Digital input delay 

0 ÷ 99 min 

dC 

Compressor and fan status when open 
door 

no /Fn / cP / Fc 

no 

rd 

Regulation with door open 

– Y 

OTHER 

Pt 

Parameter code table 

Read Only 

- - -  

rL 

Firmware release 

Read Only 

- - -  

 
 

 