background image

 

1592030000 xh50_55p r1.2 gb 2011.06.28.doc 

XH50-55P 

3/5 

 

 

 

 

9.

 

HOTKEY 

The  configuration  of  the  instrument  can  be  done  by  serial  RS485  line  or thanks to the 
HOTKEY DK00000100
 
HOW TO COPY THE PARAMETERS FROM DEVICE TO HOTKEY 
With device powered ON
, insert the hotkey in the 5 pin receptacle, the device notices 
the hotkey presence and the three LEDs flashes for three seconds in order to inform you 
that  the  copy  is  starting.  To  indicate  that  the  procedure  ends  up  with  success  the 
GREEN  LED  will  blink  for  5  seconds  or  otherwise  if  the  procedure  ends  up  without 
success the RED LED will blink for 5 seconds, in this last case it’s necessary to repeat 
the procedure or to change the HOTKEY.  
 
HOW TO COPY THE PARAMETERS FROM HOTKEY TO DEVICE 
With device powered OFF
, insert the hotkey in the 5 pin receptacle and switch on the 
device.  The  procedure  starts  automatically  and  to  indicate  that  the  procedure  ends  up 
with  success  the  GREEN  LED  will  blink  for  5  seconds  or  otherwise  if  the  procedure 
ends up without success the RED LED will blink for 5 seconds. 

10.

 

ANTI-SWEAT HEATERS REGULATION (WITH RELAY 

OUTPUT) 

The  default  factory  settings  permit  to  regulate  the  anti-sweat  heaters with the relay on 
board and the external probe that should be placed on the glass. In case of the default 
parameters aren’t able to give you the optimum performance, we can advise to change 
the following parameters: 
 

 

 

ID 

Descrizione 

Range 

Default 

odr 

 Regulation offset 

[-12.0 ÷ 12.0°C] [-21 ÷ 21°F] 

1.0°C 

Hy 

 Regulation differential 

[0.1 ÷ 25.5°C] [1 ÷ 45°F] 

5.0°C 

tAr 

 PWM period 

10 ÷ 255 min 

10 min 

 

 

The  odr  parameter  is  setted  at  1.0°C  by  default  and  permits  a  small  safety  margin 
during  the  regulation.  The  Hy  parameter  permits  to  set  the  modulation  band  for  the 
power  of  the  heaters.  Reducing  Hy  the  load  stays  OFF  for  more  time  (at  the  same 
temperature and dew-point), increasing Hy we can obtain the opposite functioning. The 
relay commutation is performed on the tAr time. 

11.

 

ANTI-SWEAT HEATERS REGULATION (WITH ANALOG 

OUTPUT) 

The regulation of the anti-sweat heaters through analog output is obtained by changing 
AOC parameter to dEP value. After that, it’s possible to refine the regulation using odr 
and Hy parameters. 

12.

 

CONFIGURATION AS THERMOSTAT 

By  setting  rLC=tER  the relay works as a simple thermostat based on set point. In this 
case, the device works as zone thermostat in heating mode. By changing the parameter 
it’s possible to invert the action. 

13.

 

KNOB (ONLY XH55P) 

In  case  of  XH55P  it’s  present  a  knob  that  permits  to  set  an  offset  respect  to  the  set 
point    of 

3°C  (this  value  can  be  changed  with Ltr and Utr parameters). If the knob is 

completely turned off all the output are switched off. 

14.

 

PARAMETER LIST 

Set 

Regulation set point: is the set point for relay or analog output regulation. 

Hy 

Regulation  differential:    band  for  the  regulation  of  the  relay  or  histeresys  of 
activation/deactivation of relay during thermostatic functioning. 

odr 

Regulation offset: offset for regulation set point. 

HES  Energy saving offset:  is the energy saving offset that is added to the set point 

when the digital input configured as i1F=ES is activated. 

CH 

Regulation kind of action:  direct or reverse functioning for the relay. 

rPA 

Regulation  probe  A:  selects  the  first  regulation  probe  between:  nP=not 
present, external probe (Etr) or internal probe (int). 

rPb 

Regulation  probe  B:  selects  the  second  regulation  probe  between:  nP=not 
present, external probe (Etr) or internal probe (int). 

rPE 

Regulation percentage between probes A and B: percentage between probe 
A and probe B. The virtual probe follow the formula: 

 

Value = (rPA*rPE + rPb*(100-rPE))/100 

CF  

Measurement  units:  °C=Celsius;  °F=Fahrenheit.  WARNING:  after  changing 
measurement unit you have to check all the values of all parameters. 

odS  Start up outputs delay: allows starting the output and the regulation with soma 

delay to allow measurement stabilization. 

rHC  Digital humidity sensor presence: enable or disable the humidity sensor. 
orH   Humidity sensor offset: it permits simple reading offset. 
tdC 

Digital temperature sensor activation. 

ot  

Digital temperature sensor offset: it permits simple reading offset. 

AuC  External  temperature  sensor  presence:  it  permits  to  enable/disable  external 

probe. 

oE 

External  temperature  sensor  offset:  it  permits  simple  reading  offset  for 
auxiliary probe. 

AOC  Analog Output working mode: select the working mode for analog output.  

If: 
nP: not present, analog output deactivated. 
Etr:  analog output regulation based on the external temperature probe. 
int: 
analog output regulation based on the internal temperature probe. 
HPr: analog output regulation based on the humidity value. 
dP: analog output regulation based on the dew-point temperature. 
dEP: analog output regulation based on the dew-point. 
MAn: analog output goes on An value. 

 

The value of analog output can change from 0 to 100% inside of the band define 
by LAO and UAO as reported on the following charts. 

--------- --------- --------- --------- --------- --------- --------- 

AoC=Etr, int, HPr, dP and Ant=dir 

 

 

--------- --------- --------- --------- --------- --------- --------- 

Summary of Contents for XH50P

Page 1: ...d FT1 in parallel with inductive loads could be useful 2 DESCRIPTION The XH50P and XH55P devices version with knob are temperature relative humidity probe but their ability to calculate dew point of the ambient where they are placed joined to the available resources relay and analog output depending on the models make them like a regulators Thanks to its features the device can be used a anti swea...

Page 2: ...S ADR 1 ADR 1 ADR 2 ADR 3 ADR 4 ADR 5 ADR 6 ADR 7 ADR 8 ADR 9 ADR 10 ADR 11 ADR 12 ADR 13 ADR 14 ADR 15 ADR 16 ADR 17 ADR 18 ADR 19 ADR 20 ADR 21 ADR 22 ADR 23 ADR 24 ADR 25 ADR 26 ADR 27 ADR 28 ADR 29 ADR 30 ADR 31 With the selectors 6 and 7 it s possible to configure the internal external temperature probe Please see the following table The probe used to calculate the dew point is the internal p...

Page 3: ...mode By changing the parameter it s possible to invert the action 13 KNOB ONLY XH55P In case of XH55P it s present a knob that permits to set an offset respect to the set point of 3 C this value can be changed with Ltr and Utr parameters If the knob is completely turned off all the output are switched off 14 PARAMETER LIST Set Regulation set point is the set point for relay or analog output regula...

Page 4: ... this case the SET and Hy are used For rLC Man the relay works as manual mode its output percentage PWM is roP so if roP 0 the relay is always OFF if roP 100 the relay is always ON Ltr Lower trimmer offset only for XH55P Offset added to setpoint when the trimmer is at minimum value Utr Upper trimmer offset only for XH55P Offset added to setpoint when the trimmer is at maximum value tAr PWM period ...

Page 5: ...g output percentage during probe error 0 100 0 rLS Relay presence no 0 YES 1 YES rLC Relay configuration nP 0 Mod 1 dEP 2 tEr 3 MAn 4 dEP Ltr Lower trimmer offset Only for XH55P 12 0 C Utr 21 F Utr 3 0 Utr Upper trimmer offset Only for XH55P Ltr 12 0 C Ltr 21 F 3 0 tAr PWM cycle Period 10 255 min 10 LrL Minimum PWM percentage 0 urL 0 urL Maximum PWM percentage LrL 100 100 rOP MANUAL MODE Relay out...

Reviews: