background image

Dixell

 

Operating instructions 

1592002910

 

 

1592002910 XH460L GB R1.0 18.05.04 

 

XH460L 

1/5 

XH460L 

TEMPERATURE AND HUMIDITY CONTROLLER 

FOR FREEZING – PROVING CABINETS 

 

1.

 

GENERAL WARNING 

1.1

 

PLEASE READ BEFORE USING THIS MANUAL 

 

This  manual  is  part  of  the  product  and  should  be  kept  near  the  instrument  for  easy  and  quick 
reference. 

 

The instrument shall not be used for purposes different from those described hereunder. It cannot 
be used as a safety device. 

 

Check the application limits before proceeding. 

 

1.2

 

 SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do  not  expose  to  water  or  moisture:  use  the  controller  only  within  the  operating  limits  avoiding 
sudden temperature changes with high atmospheric humidity to prevent  formation of condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be opened. 

 

In case of failure or faulty operation send the instrument back to the distributor or to “Dixell s.r.l.” 
(see address) with a detailed description of the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure that the wires for probes, loads and the power supply are separated and far enough from 
each other, without crossing or intertwining. 

 

In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel 
with inductive loads could be useful. 

2.

 

GENERAL DESCRIPTION 

The 

XH460L,

 

38x185 

format, is a microprocessor controller, designed for freezing and proving cabinets- 

units.  It  controls  both  humidity  and  temperature.  It  has  6  output  relays  to  control compressor, heating 
elements, defrost, fan de-humidifier and humidifier. It has 2 NTC inputs one for thermostat the other one 
for  defrost.  It’s  also  present  a  4÷20mA  input  for  humidity.  There  is  one  digital  input  (free  contact) 
configurable  by  parameter.  An    output  allows  the  user  to programme the parameter list with the 

“Hot 

Key”.

 

 

3.

 

TEMPERATURE REGULATION 

The temperature regulation is performed through neutral zone using compressor and heater output 
relays. 

Set point

OFF

ON

 

• 

Heating

 output: CUT IN is “SET_T-dbt”, CUT OUT is when the temperature reaches the set point. 

• 

Compressor

 output CUT IN is “ SET_T +dbt”, CUT OUT is when the temperature reaches the set point. 

3.1

 

DEFROST  

Two defrost modes are available through the “

tdF

” parameter: defrost with electrical heater or hot gas. 

The defrost interval is control by means of parameter “

EdF

”: (EdF=in) the defrost is made every “

IdF

” 

time, (EdF=Sd) the interval “IdF” is calculate through Smart Defrost algorithm (only when the compressor 
is ON).  
To 

disable 

the defrost set the 

MdF

 parameter to 

zero

 

 
Humidity regulation during a defrost depends on the 

Hud 

parameter. 

With  

Hud=no

 humidity regulation is disabled.  

Con 

Hud=yES

 humidity regulation is performed also during a defrost. 

 

4.

 

HUMIDITY REGULATION 

The humidity regulation is performed through neutral zone, by humidifying dehumidifying actions. 
Humidity  control  can  be  disabled  setting the SET_RH to “nu” value. In this case only the temperature 
control is perform. 

4.1

 

HUMIDIFYING ACTION 

The  humidifying  action  is  done  enabling  the  humidifier  relay  when  the  humidity  is  lower  than  the 
“SET_RH-dbH” value. 
The relay is switch off when humidity reaches the set values. 
 

4.2

 

DEHUMIDIFYING ACTION WITHOUT DEHUMIDIFIER RELAY (OA1 DIFFERENT FROM DEH) - 

STANDARD 

In this case the dehumidifying action is performed by setting the following parameters in this way: 

tHu = c-H kind of dehumidifying by means of heating and compressor relays 
oA1 different from dEH:  

The heating and compressor outputs are activated together when humidity is higher than dbH 
value. Outputs are disabled when humidity comes back to the SET_RH value. 

 

4.2.1  Relation between cooling, heating and dehumidifying 

1.

 

If  is  simultaneously  present  a  request  of  cooling  (temp>SET_T+dbt)  and  dehumidifying  (RH  > 
dbH):  the  cooling  action  has  the  priority  over  the  dehumidifying  action:  only  the 
compressor  relay  is  energised  till  the  SET_T  is  reached  at  this  point  also  the  heating  relay  is 
enabled. 

  
2.

 

If  is  simultaneously  present  a  request  of  heating  (temp<  SET_T-dbt)  and  dehumidifying  (RH  > 
dbH):  the  dehumidifying  action  has  the  priority  over  the  heating  action:  both  the 
compressor and the heating relays are energised till the humidity set is reached at this point only 
the heating relay is enabled. 

 

4.3

 

DEHUMIDIFYING ACTION WITH DEHUMIDIFIER RELAY (OA1 = DEH) 

The configurable relay is used, 

(XH460L terminals 3-4) 

setting the parameter 

oA1 =dEH.

 

NOTE: 

the LIGHT button is not more available; 

Two kinds of de-humidifying are available: 

4.3.1  Dehumidifying action with ONLY de-humidifier relay 

By setting the parameter 

tHu 

db

 the de-humidifying action is performed by enabling the de-humidifier 

relay when the humidity is higher than SET_RH

 

+  dbH. 

The relay is switch off when humidity comes back to the SET_RH value. 

 

4.3.2  Dehumidifying action with de-humidifier and compressor relays 

By setting the parameter 

tHu 

cHu

 the de-humidifying action is performed by enabling the de-humidifier 

and compressor relays together. when the humidity is higher than SET_RH

 

+  dbH. 

The relays are switched off when humidity comes back to the SET_RH value. 
 
If  is  simultaneously  present  a  request  of  cooling  (temp>SET_T+dbt)  and  dehumidifying  (RH  > 
dbH):  the  cooling  action  has  the  priority  over the dehumidifying action: only the compressor 
relay is energised till the SET_T is reached at this point also the de-humidifier is enabled. 

5.

 

 FA NS 

The fan control mode is selected by means of the “

FnC

” parameter: 

FnC=C-n

   fans will switch ON and OFF with the compressor and

 not run

 during defrost

:

FnC= O-n

  fans will run continuously, but not during defrost  

FnC=C-y

   fans will switch ON and OFF with the compressor and 

run

 during defrost; 

FnC=O-y

   fans will run continuously also during defrost 

6.

 

FREZING –PROVING CYCLE  

 

FREEZING

PROVING

HOLDING

(optional)

 

The diagrams displays a typical freezing and proving cycle with the holding phase. 

FREEZING PHASE

 lasts for the T1 time, usually without  humidity control 

PROVING PHASE

 lasts for the T2 time, both temperature and humidity are controlled.  

The  end  of  the  proving  phase  is  signalled  by  the  internal  buzzer  and  by  the  “End”  message  on  the 
display. 

After 

the 

PROVING PHASE

 the behaviour of the controller depends on the parameter 

trc, 

 according to 

the following settings: 

trc

 = 

co 

controller maintains the set points of the proving phase (

HOLDING) 

trc

 = 

in 

controller stop the regulation at all. 

trc

 = 

cL 

controller performs the freezing and proving phase till is stopped manually. 

trc

 = 

cLE 

 as (

trc

 = 

cL

) plus at the end of each cycle the 

End

 label is displayed and the buzzer 

is switched on. 

 

6.1

 

 HOW TO SET THE DURATION OF THE FREEZING AND PROVING CYCLE  

1.

 

Push  the 

CLOCK

  key,  the  display  shows  on  the  bottom  display  the  “tM1”  message,  while  the 

“hourglass” start flashing. 

2.

 

Push again the 

CLOCK

 the duration of the freezing phase is shown, hh:mm. 

3.

 

To set the duration push the 

UP 

 and 

DOWN

 keys.  

4.

 

Push again the 

CLOCK

 to confirm the time and pass to the setting of the proving phase: the “tM2” 

message is displayed. 

5.

 

Push the 

CLOCK

 key to see its duration and use the 

UP

 and 

DOWN

 keys to set it. 

6.

 

Confirm the value by pushing again the 

CLOCK 

key and pass to the humidity display. 

 

NOTE: 

If the phase length is modified during a cycle, the modification is performed also in the next cycle. 

6.2

 

HOW TO SET THE TARGET HUMIDITY OF THE FREEZING AND PROVING CYCLE 

1.

 

Push the 

SET_RH

 key, the display shows on the bottom display the “SH1” message, while the “set 

” icon starts flashing. 

2.

 

Push again the 

SET_RH

 the humidity set point of the freezing phase is shown. Set it using the 

UP 

 

and 

DOWN

 keys. To 

disable

 the humidity control during the freezing phase set it to “

nu

”. 

3.

 

Push  again  the 

SET_RH

  to  confirm  the  value  and  pass  to  the  setting  of  the  proving  phase:  the 

“SH2” message is displayed. 

4.

 

Push the 

SET_RH

 key to see its value and use the 

UP

 and 

DOWN

 keys to set it. 

 

Summary of Contents for XH460L

Page 1: ...ng temp SET_T dbt and dehumidifying RH SET_RH dbH the cooling action has the priority over the dehumidifying action only the compressor relay is energised till the SET_T is reached at this point also the heating relay is enabled 2 If is simultaneously present a request of heating temp SET_T dbt and dehumidifying RH SET_RH dbH the dehumidifying action has the priority over the heating action both t...

Page 2: ... The defrost is enabled LED 3 FLASHING Drip time in progress LED 2 FLASHING Programming Phase flashing with LED3 ON Heating enabled temp FLASHING Temperature Set programming phase ON ALARM signal ON Fan is running ON RH ON Dehumidifying enabled ON Humidifying enabled umid FLASHING Humidity Set programming phase ON Freezing phase is in progress FLASHING Proving phase is in progress FLASHING Setting...

Page 3: ...etection of an alarm condition and the corresponding alarm signalling dAO Delay of temperature alarm at start up 0min 23h 50min time interval between the detection of the temperature alarm condition after the instrument power on and the alarm signalling EdA Alarm delay at the end of defrost 0 255 min Time interval between the detection of the temperature alarm condition at the end of defrost and t...

Page 4: ...Outputs unchanged dA Door switch alarm Outputs depending on the odC parameter EAL External alarm Other outputs unchanged BAL Serious external alarm Outputs OFF PAL Pressure switch alarm Outputs OFF The alarm message is displayed until the alarm condition recoveries All the alarm messages are showed alternating with the room temperature except for the P1 which is flashing To reset the EE alarm and ...

Page 5: ...arm delay 0 250 min dHo 1 3 Pr2 Delay of humidity alarm at start up 0 0 23 5 h doH 20 Pr2 Alarm delay at the end of defrost 0 250 min doA 20 Pr2 Open door alarm delay 0 250 min 250 nu tbA oFF Pr2 Relay status after pushing a key on oFF nPS 15 Pr2 Pressure switch number 0 15 ot 0 0 Pr1 Thermostat probe calibration 12 0 12 0 oE 0 0 Pr2 Evaporator probe calibration 12 0 12 0 o3 0 0 Pr1 Humidity probe...

Reviews: