dixell XH460L Operating Instructions Download Page 3

Dixell

 

Operating instructions 

1592002910

 

 

1592002910 XH460L GB R1.0 18.05.04 

 

XH460L 

3/5 

7.8

 

ON/OFF FUNCTION 

 

By pushing the 

ON/OFF

 key, the instrument shows “OFF” for 5 sec. and the ON/OFF LED 

is switched ON. 
During the OFF status, all the relays are switched OFF and the regulations are stopped;  

N.B. During the OFF status the LED4  button is lighted. 

 

 

8.

 

PARAMETER LIST 

REGULATION 

dbt

  half dead band width for temperature:

 (0,1÷25,5°C; 1÷45°F) this band is place below and above 

the  temperature  set  point  (SET_T). The  compressor  is  enabled  when the temperature increases 
and reaches the SET_T + dbt value. It is turned off when it comes back to the SET_T. The heating 
output is enabled when temperature is less than SET_T -dbt value and disabled when the SET_T is 
reached.

 

dbH

 half  dead  band  width  for  humidity:

  (0,5÷25,5RH)  this  band  is  place  below  and  above  the 

humidity set point (SET_RH). The dehumidifying action is enabled when the humidity increases and 
reaches  the  SET_RH  +  dbH  value.  It  is  stopped  when  it  comes  back  to  the  SET_RH.  The 
humidifying  output is enabled when humidity is less than SET_RH -dbH value and disabled when 
the SET_RH is reached.

 

LS  Minimum temperature set point limit: 

(-50,0°C SET; -58°F÷SET) Sets the minimum acceptable 

value for the set point. 

US  Maximum temperature set point limit: 

(SET 110°C; SET÷230°F) Set the maximum acceptable 

value for set point. 

OdS  Outputs activation delay at start up:

 (0÷255 min) This function is enabled at the initial start up of 

the instrument and inhibits any output activation for the period of time set in the parameter. (Light 
can work) 

AC  Anti-short cycle delay: 

(0÷30 min) interval between the compressor stop and the following restart. 

tHu  Kind of de-humidifying: db

: only with de-humidifier relay (oA1= dEH) 

cHu

 with de-humidifier and compressor relay (oA1= dEH) 

c-H: 

without de-humidifier relay, by means of compressor and heating relays

 

(oA1  dEH)

LSH  Minimum  humidity set point limit: 

(

Lci ÷ Set H

) Sets the minimum acceptable value for the 

humidity set point. 

USH Maximum  humidity  set  point  limit: 

(

Set  H  ÷  uci

)  Set  the  maximum  acceptable  value  for 

humidity set point. 

 

DISPLAY AND KIND OF REGULATION 
CF  Measurement unit: °C

= Celsius; 

°F

= Fahrenheit 

rES  Resolution (for °C)

: allows decimal point display. 

dE

 = 0,1°C; 

in

 = 1 °C  

rEH  Resolution for RH%:

 in = integer; Hd= half digit. 

trC  Kind of behaviour after the end of the cycle 
 

trC=co 

the controller goes on working, and maintains the temperature and humidity of the proving 

phase, till the controller is stopped. 

 

trC=in 

at the end of the proving phase the controller gives the “End” message, the buzzer is turned 

on, and the regulation is stopped. 

 

trC=cL 

at the end of the proving phase the controller gives the “End” message, the buzzer is turned 

on, and the regulation restarts from the freezing phase 

 

trC=cLE 

at the end of the proving phase the regulation restarts from the freezing phase.

 

 

DEFROST 
tdF   Defrost type: rE

 = electrical heater (Compressor OFF) 

in

 = hot gas (Compressor and defrost relays ON) 

EdF  Defrost mode:

  

in

 = 

interval mode

. The defrost starts when the time “

Idf

” is expired. 

Sd

  = 

Smartfrost  mode

.  The  time  IdF  (interval  between  defrosts)  is  increased  only  when  the 

compressor is running (even non consecutively).  

SdF  Set point for SMARTFROST

: (-30 30 °C/ -22 86 °F) evaporator temperature which allows the IdF 

counting (interval between defrosts) in SMARTFROST mode. 

dtE   Defrost  termination  temperature:

  (-50,0÷110,0°C;  -58÷230°F)  (Enabled  only  when  the 

evaporator probe is present) sets the temperature measured by the evaporator probe which causes 
the end of defrost. 

IdF  Interval between defrosts: 

(1÷120h) Determines the time interval between the beginning of two 

defrost cycles. 

MdF Duration of defrost: 

(0÷255 min) When 

P2P = n

, no evaporator probe, it sets the defrost duration, 

when 

P2P = y

, defrost end based on temperature, it sets the maximum length for defrost. 

dFd  Display during defrost:  
 

rt

 = real temperature; 

it

 = temperature reading at the defrost start; 

Set

 = set point; 

dEF

 = “dEF” label; 

 

dEG

 = “dEG” label;

 

dAd  Defrost display time out:

 (0 255 min) Sets the maximum time between the end of defrost and the 

restarting of the real room temperature display. 

Fdt   Drain down time:

 (0÷60 min.) time interval between reaching defrost termination temperature and 

the restoring of the control’s normal operation. This time allows the evaporator to eliminate water 
drops that might have formed due to defrost.

 

dPO First defrost after start-up:  y 

= Immediately; 

n

 = after the IdF time 

Hud  Humidity control during defrost:

 

no

: the humidity control is stopped during the defrost; 

yES

 the 

humidity control works also during the defrost. 

FANS 
FnC  Fan operating mode: C-n

 = running when a load is on, OFF during the defrost;  

C-y

 = running when a load is on, ON during the defrost; 

O-n

 = continuous mode, OFF during the defrost; 

O-y

 = continuous mode, ON during the defrost; 

TEMPERATURE ALARMS 
ALC  Temperature alarm configuration: rE

 = High and Low alarms related to Set Point  

Ab

 = High and low alarms related to the absolute temperature. 

ALL  Low temperature alarm setting:

 

ALC = rE 

, 0   50 °C or 90°F 

 

ALC = Ab 

, - 50°C or -58°F   ALU 

 

when this temperature is reached and after the ALd delay time, the LA alarm is enabled,. 

ALU  High temperature alarm setting:

  

ALC= rE

, 0 

 

50°C or 90°F 

 

ALC= Ab

, ALL   110°C or 230°F 

 

when this temperature is reached and after the ALd delay time the HA alarm is enabled. 

 

ALH  Temperature  alarm  recovery  differential: 

(0,1÷25,5°C;  1÷45°F)  Intervention  differential  for 

recovery of temperature alarm.

 

ALd  Temperature alarm delay:

 (0÷255 min) time interval between the detection of an alarm condition 

and the corresponding alarm signalling. 

dAO Delay of temperature alarm at start-up:

 (0min÷23h 50min) time interval between the detection of 

the temperature alarm condition after the instrument power on and the alarm signalling.

 

EdA  Alarm  delay  at  the  end  of  defrost: 

(0 255  min)  Time  interval  between  the  detection  of  the 

temperature alarm condition at the end of defrost and the alarm signalling. 

dot   Delay  of  temperature  alarm  after  closing  the  door  : 

(0 255  min)  Time  delay  to  signal  the 

temperature alarm condition after closing the door. 

HUMIDITY ALARMS 
AHC Humidity alarm configuration: rE

 = High and Low alarms related to humidity Set Point  

Ab

 = High and low alarms related to the “absolute” humidity. 

AHL  Low humidity alarm setting: 

(with AHC = rE: 

0 ÷ 50

. With AHC = Ab: 

Lci ÷ AHu)

 

 

when this humidity is reached and after the AHd delay time, the HLA alarm is enabled,. 

AHu  High humidity alarm setting:

 (with AHC = rE: 0÷50°C. with AHC = Ab: 

AHL ÷ uci

 

 

when this humidity is reached and after the AHd delay time the HHA alarm is enabled. 

AHH Humidity alarm recovery differential: 

(0.5÷20.0) Intervention differential for recovery of humidity 

alarm.

 

AHd  Humidity alarm delay:

 (0÷255 min) time interval between the detection of an alarm condition and 

the corresponding alarm signalling. 

dHo Delay of humidity alarm at start-up:

 (0min÷23h 50min) time interval between the detection of the 

humidity alarm condition after the instrument power on and the alarm signalling.

 

doH  Alarm  delay  at  the  end  of  defrost: 

(0 255  min)  Time  interval  between  the  detection  of  the 

humidity alarm condition at the end of defrost and the alarm signalling. 

doA  Open door alarm delay:

(0÷255 min) delay between the detection of the open door condition and 

its alarm signalling: the flashing message “

dA

” is displayed. 

tbA  Alarm relay status after pushing a key: on= 

the relay remains on

; off= 

the relay is switched off. 

nPS  Pressure switch number:

 (0  15) Number of activation of the pressure switch, during the “

did

” 

interval, before signalling the alarm event (I2F= PAL). 

If the nPS activation in the “did” time is reached, switch off and on the instrument to restart 
normal regulation. 

 

PROBE INPUTS 
Ot  Thermostat  probe  calibration: 

(-12.0 12.0°C/  -21 21°F)  allows  to  adjust possible offset of the 

thermostat probe. 

OE    Evaporator probe calibration: 

(-12.0 12.0°C/ -21 21°F) allows to adjust possible offsets of the 

evaporator probe. 

O3    Humidity probe calibration: 

(-10 10 RH) allows to adjust possible offsets of the humidity probe. 

P2P  Evaporator  probe  presence:  n

=  not  present:  the  defrost  stops  only  by  time; 

y=

  present:  the 

defrost stops by temperature and time. 

P3P  Humidity probe presence: n

= not present; 

y=

 present. 

LCI   Readout with 4 mA

 : (-999 ÷ 999). Adjustment of  read out corresponding to 4mA signal. 

UCI   Readout with 20 mA

 : (-999 ÷ 999). Adjustment of  read out corresponding to 20mA signal. 

  

 

DIGITAL INPUTS 
i1P  Digital input polarity: CL

 : the digital input is activated by closing the contact;  

OP

 : the digital input 

is activated by opening the contact 

i1F  Digital input operating mode:

 configure the digital input function: 

 EAL 

=  generic  alarm; 

bAL 

serious alarm mode; 

PAL 

= Pressure switch; 

 Ht 

= heating relay safety; 

dor

 = door switch

 

odc  Outputs status when open door:

 

on

 = normal; 

Fan

 = Fan OFF; 

oFF

 = all the loads off  

rrd  Outputs restarting after doA alarm: no = 

outputs not affected by the doA alarm;  

yES = 

outputs 

restart with the doA alarm;  

did   Time interval/delay for digital input alarm:

(0 255 min.) Time interval to calculate the number of 

the pressure switch activation when I1F=PAL. If I1F=EAL or bAL (external alarms), “did” parameter 
defines the time delay between the detection and the successive signalling of alarms. 

OTHER 
oA1

 

Light relay configuration

 (

XH460L terminals 3-4

): 

ALr 

= alarm; 

dEH 

= dehumidifier; 

onF 

= on/off 

relay: close with instrument on, open with instrument off; 

Lig 

= light, 

ESt, dEF not select

 

Adt  RS485 serial address for temperature loads 

(0÷247) identifies the instrument within a control or 

supervising system.

 

AdH  RS485  serial  address  for  humidity  loads 

(0÷247)  identifies  the  instrument  within  a  control  or 

supervising system.

 

Ptb   Parameter table:

 (read only) it shows the original code of the 

dIXEL

 parameter map. 

rEL   Software release:

 (read only) Software version of the microprocessor. 

Prd   Probes display: 

(read only) display the temperature values of the evaporator probe Pb2. 

Pr2   Access to the protected parameter list 

(read only). 

 

9.

 

DIGITAL INPUT  

One digital input is present configurable by user by means of the i1F parameter according to the following 
descriptions.  

9.1

 

DOOR SWITCH (I2F = dor) 

It signals the door status and the corresponding relay output status through the “

odc

” parameter: 

no

 = 

normal (any change); 

Fan

 = Fan OFF; 

oFF

 = all the loads are switched off. 

 

Since the door is opened, after the delay time set through parameter “

dOA

”, the alarm output is enabled 

and the display shows the message “

dA

”.  

The status of loads depends on the “

rrd” 

parameter:  

with 

rrd=no 

outputs are not affected by the doA alarm;  

with 

rrd=yES = 

outputs restart with the doA alarm; 

The alarm stops as soon as the external digital input is disabled again. During this time and then for the 
delay “

dot

” and 

“doH” 

after closing the door, the temperature and humidity alarms are disabled. 

9.2

 

GENERIC ALARM (I1F = EAL) 

As soon as the digital input is activated the unit will wait for “

did

” time delay before signalling the “

EAL

” 

alarm  message.  The  outputs  status  don’t  change.  The  alarm  stops  just  after  the  digital  input  is  de-
activated. 

9.3

 

SERIOUS ALARM MODE (I2F = BAL) 

When  the  digital  input  is  activated,  the  unit  will  wait  for  “

did

”  delay  before  signalling  the  “

bAL

”  alarm 

message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-
activated. 

Summary of Contents for XH460L

Page 1: ...ng temp SET_T dbt and dehumidifying RH SET_RH dbH the cooling action has the priority over the dehumidifying action only the compressor relay is energised till the SET_T is reached at this point also the heating relay is enabled 2 If is simultaneously present a request of heating temp SET_T dbt and dehumidifying RH SET_RH dbH the dehumidifying action has the priority over the heating action both t...

Page 2: ... The defrost is enabled LED 3 FLASHING Drip time in progress LED 2 FLASHING Programming Phase flashing with LED3 ON Heating enabled temp FLASHING Temperature Set programming phase ON ALARM signal ON Fan is running ON RH ON Dehumidifying enabled ON Humidifying enabled umid FLASHING Humidity Set programming phase ON Freezing phase is in progress FLASHING Proving phase is in progress FLASHING Setting...

Page 3: ...etection of an alarm condition and the corresponding alarm signalling dAO Delay of temperature alarm at start up 0min 23h 50min time interval between the detection of the temperature alarm condition after the instrument power on and the alarm signalling EdA Alarm delay at the end of defrost 0 255 min Time interval between the detection of the temperature alarm condition at the end of defrost and t...

Page 4: ...Outputs unchanged dA Door switch alarm Outputs depending on the odC parameter EAL External alarm Other outputs unchanged BAL Serious external alarm Outputs OFF PAL Pressure switch alarm Outputs OFF The alarm message is displayed until the alarm condition recoveries All the alarm messages are showed alternating with the room temperature except for the P1 which is flashing To reset the EE alarm and ...

Page 5: ...arm delay 0 250 min dHo 1 3 Pr2 Delay of humidity alarm at start up 0 0 23 5 h doH 20 Pr2 Alarm delay at the end of defrost 0 250 min doA 20 Pr2 Open door alarm delay 0 250 min 250 nu tbA oFF Pr2 Relay status after pushing a key on oFF nPS 15 Pr2 Pressure switch number 0 15 ot 0 0 Pr1 Thermostat probe calibration 12 0 12 0 oE 0 0 Pr2 Evaporator probe calibration 12 0 12 0 o3 0 0 Pr1 Humidity probe...

Reviews: