Dixell
Operating instructions
1592002711
1592002711 XH260L-V GB r1.0 12.01.04
XH260L - XH260V
4/5
3.
Automatically the parameter list of the “Hot Key” is downloaded into the Controller memory, the
“doL” message is blinking followed a by flashing “End”.
4.
After 10 seconds the instrument will restart working with the new parameters.
5.
Remove the “Hot Key”..
NOTE the message “Err” is displayed for failed programming. In this case turn the unit off and then on if
you want to restart the download again or remove the “Hot key” to abort the operation.
12.
ALARM SIGNALLING
Message Cause
Outputs
“P1” Thermostat probe failure
Compressor and heating outputs off
“P2” Evaporator probe failure
Defrost and by time
“P3”
Humidity probe failure
Humidity regulation off
“HA”
High temperature alarm
Outputs unchanged
“LA”
Low temperature alarm
Outputs unchanged
“HHA” High humidity alarm
Outputs unchanged
“HLA” Low humidity alarm
Outputs unchanged
“dA”
Door switch alarm
Outputs depending on the odC parameter
“EAL” External alarm
Other outputs unchanged
“BAL” Serious external alarm
Outputs OFF
“PAL” Pressure
switch alarm
Outputs OFF
The alarm message is displayed until the alarm condition recoveries.
All the alarm messages are showed alternating with the room temperature except for the “P1” which is
flashing. To reset the “EE” alarm and restart the normal functioning press any key, the “rSt” message is
displayed for about 3s.
12.1
SILENCING BUZZER
Once the alarm signal is detected the buzzer, if present, can be silenced by pressing any key.
12.2
ALARM RECOVERY
Probe alarms : “P1” (probe1 faulty), “P2”, “P3”; they automatically stop 10s after the probe restarts
normal operation. Check connections before replacing the probe.
Temperature alarms “HA” and “LA” automatically stop as soon as the thermostat temperature returns
to normal values or when the defrost starts.
Humidity alarms “HHA” and “LHA” automatically stop as soon as the humidity returns to normal
values.
Door switch alarm “dA” stop as soon as the door is closed.
External alarms “EAL”, “BAL” stop as soon as the external digital input is disabled
Pressure switch alarm “PAL” alarm is recovered by switching OFF the instrument.
13.
TECHNICAL DATA
Housing: self extinguishing ABS.
Case: XH260L: facia 38x185 mm; depth 76mm; XH260V: facia 100x64 mm; depth 76mm
Mounting: XH260L: panel mounting in a 150x31 mm panel cut-out with two screws.
∅
3 x 2mm.
Distance between the holes 165mm
XH260V: panel mounting in a 56x72 mm panel cut-out with two screws.
∅
3x2mm. Distance
between the holes 40mm
Protection: IP20.
Frontal protection: IP65 with optional frontal gasket mod. RG-L (XH260L); RGW-V (XH260V)..
Connections: Screw terminal block
≤
2,5 mm
2
heat-resistant wiring and 6,3mm Faston
Power supply: 230Vac or 110Vac
±
10%; Power absorption: 7VA max.
Display: double d icons.
Inputs: 1 NTC probe + 4÷20mA probe
Digital input: 1 free voltage
Relay outputs: compressor: XH260L: relay SPST 20(8) A, 250Vac;
XH260V: relay SPST 8(3) A, 250Vac
heather: relay SPST 8(3) A, 250Vac; defrost: relay SPST 8(3) A, 250Vac
fans: relay SPST 8(3) A, 250Vac; humidifier: relay SPST 8(3) A, 250Vac
de-humidifier: relay SPST 8(3) A, 250Vac
Other output : alarm buzzer (optional)
Data storing: on the non-volatile memory (EEPROM).
Kind of action: 1B.; Pollution grade: normal; Software class: A.
Operating temperature: 0÷60 °C.; Storage temperature: -25÷60 °C.
Relative humidity: 20
÷
85% (no condensing)
Measuring and regulation range:
NTC probe: -40÷110°C (-58÷230°F)
Resolution: 0,1 °C or 1°C or 1 °F (selectable).
Accuracy (ambient temp. 25°C): ±0,5 °C ±1 digit
14.
WIRING CONNECTIONS
14.1
XH260L
R
oom
11
9 10
12 13
17
16
18 19
21 22 23
14 15
L
N
Comp
20(8)A
250V
~
6
2
7
3
8
4 5
1
Fan
8(3)A
250V
~
8(3)A
250V
~
8(3)A
250V
~
8(3)A
250V
~
De
f
20
Heater
Hum
8(3)A
250V
~
Def
NC
Supply 115Vac: 14-15 terminals
14.2
XH260V
8(3)A250V
~
MAX
20A
Comp
Def
N.C.
Fan
Ro
om
De
f.
Heater
8(
3)A
8(
3)A
8(
3)A
8(
3)A
8(
3)A
C
Hum
Supply 115Vac: 2-3 terminals
15.
DEFAULT SETTING VALUES
Label Value Menu
Description
Range
Set T
5.0
- - - Temperature Set Point
LS ÷ uS ( nu = temperature
regulation disabled )
Set H
50.0
- - - Humidity Set Point
LSH ÷ uSH ( nu = humidity
regulation disabled)
dbt
2.0
Pr1 Half dead band width for temperature 0.1°C
o
1°F ÷ 25°C o 77°F
dbH
5.0
Pr1 Half dead band width for humidity
0.5 ÷ 50
LS
-40
Pr2 Minimum temperature set point limit
-50.0°C o –58°F ÷ Set T
uS
110
Pr2 Maximum temperature set point limit
Set T ÷ 110°C o 230°F
odS
1
Pr2 Outputs activation delay at start up
0 ÷ 250 min
Ac
1
Pr1 Anti-short cycle delay
0 ÷ 30 min
tHu
db Pr2
Humidity
regulation
db = dehumidifier relay.; cHu
= dehum+ compr.; c-H=
without dehum. relay
LSH
0.0
Pr2 Minimum humidity set point limit
Lci ÷ Set H
uSH
100.0
Pr2 Maximum humidity set point limit
Set H ÷ uci
cF
°C
Pr2 Measurement unit
°C ÷°F
rES
dE
Pr2 Resolution (for °C):
in = integer / dE = decimal
rEH
Hd
Pr2 Resolution for RH%:
in = integer / Hd = half digit
tdf
rE
Pr2 Defrost type
rE, rT, in
EdF
in
Pr2 Defrost mode
In, Sd
SdF
0
Pr2 Set point for SMART DEFROST
-30 ÷ +30°C / -22÷+86°F
dtE
8
Pr2 Defrost termination temperature
-50,0÷110°C/ -58÷230°F
idF
8
Pr1 Interval between defrosts
1 ÷ 120 h
MdF
20
Pr1 Duration of defrost
0 ÷ 250 min
dFd
it
Pr2 Display during defrost
rt / it / SEt / dEF / dEG
dAd
30
Pr2 Defrost display time out
0 ÷ 250 min
Fdt
0 Pr2
Draining
time
0÷60
min.
dPo
no
Pr2 First defrost after start up
n ÷ y
Hud
no Pr2
Humidity
control during defrost
no; yES
Fnc
c-n
Pr2 Fan operating mode
c-n / c-Y / o-n / o-Y
ALc
Ab
Pr2 Temperature alarm configuration
rE = relative / Ab = absolute
ALL
-40.0
Pr1 Low temperature alarm setting
0°C ÷ 50.0°C / -50.0°C ÷ ALu
ALu
110
Pr1 High temperature alarm setting
0°C ÷ 50.0°C / ALL ÷ 110°C
ALH
1.0
Pr2 Temperature alarm recovery differential
0.1°C o 1°F ÷ 25°C o 77°F
ALd
15
Pr2 Temperature alarm delay
0 ÷ 250 min
dAo
1.3
Pr2 Delay of temperature alarm at start-up
0.0 ÷ 23.5 h
EdA
20
Pr2 Alarm delay at the end of defrost
0 ÷ 250 min
dot
20
Pr2 Delay of temperature alarm after closing the
door
0 ÷ 250 min
AHc
Ab
Pr2 Humidity alarm configuration
rE = relative / Ab = absolute
AHL
0.0
Pr1 Low humidity alarm setting
0 ÷ 50 / Lci ÷ AHu
AHu
100
Pr1 High humidity alarm setting
0 ÷ 50 / AHL ÷ uci
AHH
2.0
Pr2 Humidity alarm recovery differential
0.5 ÷ 25
AHd
15
Pr2 Humidity alarm delay
0 ÷ 250 min
dHo
1.3
Pr2 Delay of humidity alarm at start-up
0.0 ÷ 23.5 h
doH
20
Pr2 Alarm delay at the end of defrost
0 ÷ 250 min
nPS
0
Pr2 Pressure switch number
0÷15
doA
20
Pr2 Open door alarm delay
0 ÷ 250 min ( 250 = nu )
ot
0.0
Pr1 Thermostat probe calibration
-12.0 ÷ 12.0
oE
0.0
Pr2 Evaporator probe calibration
-12.0 ÷ 12.0
o3
0.0
Pr1 Humidity probe calibration
-10 ÷ 10
P2P
no
Pr2 Evaporator probe presence
no = absent / YES = present
P3P
YES
Pr2 Humidity probe presence
no = absent / YES = present
Lci
0
Pr2 Readout with 4 mA
-999 ÷ 999
uci
100
Pr2 Readout with 20 mA
-999 ÷ 999
i1P
oP
Pr2 Digital input polarity
cL =open / oP = close
i1F
dor
Pr2 Digital input configuration
dor / PAL / EAL / bAL / Ht
odc
oFF
Pr2 Outputs status when open door
on / Fan / oFF
rrd
YES
Pr2 Outputs restarting after doA alarm
no = no / YES = yes
did
0
Pr2 Digital input alarm delay
0÷255 min.
oA1
Lig Pr2
Light relay configuration (XH260L
terminals 3-4, XH260V terminals. 11-12):
ALr = alarm; dEH =
dehumidifier; onF = on/off;
Lig = light, ESt, dEF not
select
Adr
1
Pr2
Serial address
0÷247 num
Ptb
1
Pr2 Parameter table
- - -
rEL
0.1
Pr2 Software release
- - -
Prd
-- Pr2
Probes
display
Pb1÷Pb3