3.

 

Automatically the parameter list of the “Hot Key” is downloaded into the Controller memory, the 
doL” message is blinking followed a by flashing “End”. 

4.

 

After 10 seconds the instrument will restart working with the new parameters.  

5.

 

Remove the “Hot Key”.

 
NOTE the message “Err” is displayed for failed programming. In this case turn the unit off and then on if 
you want to restart the download again or remove the “Hot key” to abort the operation. 

12.

 

ALARM SIGNALLING 

Message  Cause 

Outputs 

“P1”   Thermostat probe failure 

Compressor and heating outputs off 

“P2”   Evaporator probe failure 

Defrost and by time 

“P3” 

Humidity  probe failure 

Humidity regulation off 

“HA” 

High temperature alarm 

Outputs unchanged 

“LA” 

Low temperature alarm 

Outputs unchanged 

“HHA”  High humidity alarm 

Outputs unchanged 

“HLA”  Low humidity alarm 

Outputs unchanged 

“dA” 

Door switch alarm 

Outputs depending on the odC parameter 

“EAL”  External alarm 

Other outputs unchanged 

“BAL”  Serious external alarm 

Outputs OFF 

“PAL” Pressure 

switch alarm 

Outputs OFF 

 
The alarm message is displayed until the alarm condition recoveries. 
All the alarm messages are showed alternating with the room temperature except for the “P1” which is 
flashing. To reset the “EE” alarm and restart the normal functioning press any key, the “rSt” message is 
displayed for about 3s. 

12.1

 

SILENCING BUZZER 

Once the alarm signal is detected the buzzer, if present, can be silenced by pressing any key.  

12.2

 

ALARM RECOVERY 

Probe alarms : “P1” (probe1 faulty), “P2”, “P3”; they automatically stop 10s after the probe restarts 
normal operation. Check connections before replacing the probe. 
Temperature alarms “HA” and “LA” automatically stop as soon as the thermostat temperature returns 
to normal values or when the defrost starts. 
Humidity alarms  “HHA” and “LHA” automatically stop as soon as the humidity returns to normal 
values. 
Door switch alarm “dA”  stop as soon as the door is closed. 
External alarms “EAL”, “BAL”  stop as soon as the external digital input is disabled  
Pressure switch alarm PAL” alarm is recovered by switching OFF the instrument

13.

 

TECHNICAL DATA 

Housing: self extinguishing ABS. 
Case: XH260L: 
facia 38x185 mm; depth 76mm;  XH260V: facia 100x64 mm; depth 76mm 
Mounting: XH260L: panel mounting in a 150x31 mm panel cut-out with two screws. 

 3 x 2mm. 

Distance between the holes 165mm 
XH260V: panel mounting in a 56x72 mm panel cut-out with two screws. 

 3x2mm. Distance 

between the holes 40mm 

Protection: IP20. 
Frontal protection:
 IP65 with optional frontal gasket mod. RG-L (XH260L); RGW-V (XH260V).. 
Connections: Screw terminal block 

 2,5 mm

2

 heat-resistant wiring and 6,3mm Faston 

Power supply: 230Vac or 110Vac 

±

 10%; Power absorption: 7VA max. 

Display: double d icons.  
Inputs: 1 NTC probe +  4÷20mA probe 
Digital input: 1 free voltage 
Relay outputs: compressor:   XH260L: relay SPST 20(8) A, 250Vac;  

XH260V: relay SPST 8(3) A, 250Vac  

heather: relay SPST 8(3) A, 250Vac;   defrost: relay SPST 8(3) A, 250Vac  
fans: relay SPST 8(3) A, 250Vac; humidifier: relay SPST 8(3) A, 250Vac  
de-humidifier: relay SPST 8(3) A, 250Vac  

Other output : alarm buzzer  (optional) 
Data storing: on the non-volatile memory (EEPROM). 
Kind of action: 1B.; Pollution grade: normal; Software class: A. 
Operating temperature: 
0÷60 °C.; Storage temperature: -25÷60 °C.  
Relative humidity: 20

÷

85% (no condensing) 

Measuring and regulation range:  

NTC probe: -40÷110°C (-58÷230°F) 

Resolution: 0,1 °C or 1°C or 1 °F (selectable). 
Accuracy (ambient temp. 25°C):  ±0,5 °C ±1 digit 

14.

 

WIRING CONNECTIONS 

14.1

 

XH260L 

 

R

oom

11

9 10

12 13

17

16

18 19

21 22 23

14 15

L

N

Comp

20(8)A

250V

~

6

2

7

3

8

4 5

1

Fan

8(3)A

250V

~

8(3)A

250V

~

8(3)A

250V

~

8(3)A

250V

~

De

f

20

Heater

Hum

8(3)A

250V

~

Def

NC

 

Supply 115Vac: 14-15 terminals 

14.2

 

XH260V 

8(3)A250V

~

MAX

20A

Comp

Def

N.C.

Fan

Ro

om

De

f.

Heater

8(

3)A

8(

3)A

8(

3)A

8(

3)A

8(

3)A

C

Hum

 

 

 

Supply 115Vac: 2-3 terminals

 

15.

 

DEFAULT SETTING VALUES  

Label  Value  Menu 

Description 

Range 

Set T 

5.0 

- - -  Temperature Set Point  

LS ÷ uS ( nu = temperature 

regulation disabled ) 

Set H 

50.0 

- - -  Humidity Set Point  

LSH ÷ uSH ( nu = humidity 

regulation disabled) 

dbt 

2.0 

Pr1  Half dead band width for temperature 0.1°C 

1°F ÷ 25°C o 77°F 

dbH 

5.0 

Pr1  Half dead band width for humidity 

0.5 ÷ 50 

LS 

-40 

Pr2  Minimum temperature set point limit 

-50.0°C o –58°F ÷ Set T  

uS 

110 

Pr2  Maximum temperature set point limit 

Set T ÷  110°C o 230°F  

odS 

Pr2  Outputs activation delay at start up 

0 ÷ 250 min 

Ac 

Pr1  Anti-short cycle delay 

0 ÷ 30 min 

tHu 

db Pr2 

Humidity 

regulation 

db = dehumidifier relay.; cHu 

= dehum+ compr.; c-H= 

without dehum. relay 

LSH 

0.0 

Pr2  Minimum humidity set point limit 

Lci ÷ Set H  

uSH 

100.0 

Pr2  Maximum humidity set point limit 

Set H ÷ uci 

cF 

°C 

Pr2  Measurement unit 

°C ÷°F 

rES 

dE 

Pr2  Resolution (for °C): 

in = integer / dE = decimal 

rEH 

Hd 

Pr2  Resolution for RH%: 

in = integer / Hd = half digit 

tdf 

rE 

Pr2  Defrost type 

rE,  rT,  in  

EdF 

in 

Pr2  Defrost mode 

In, Sd 

SdF 

Pr2  Set point for SMART DEFROST 

-30 ÷ +30°C / -22÷+86°F 

dtE 

Pr2  Defrost termination temperature  

-50,0÷110°C/ -58÷230°F 

idF 

Pr1  Interval between defrosts 

1 ÷ 120 h 

MdF 

20 

Pr1  Duration of defrost 

0 ÷ 250 min 

dFd 

it 

Pr2  Display during defrost 

rt / it / SEt / dEF / dEG 

dAd 

30 

Pr2  Defrost display time out 

0 ÷ 250 min 

Fdt 

0 Pr2 

Draining 

time 

0÷60 

min. 

dPo 

no 

Pr2  First defrost after start up 

n ÷ y 

Hud 

no Pr2 

Humidity 

control during defrost 

no; yES 

Fnc 

c-n 

Pr2  Fan operating mode 

c-n / c-Y / o-n / o-Y 

ALc 

Ab 

Pr2  Temperature alarm configuration 

rE = relative / Ab = absolute 

ALL 

-40.0 

Pr1  Low temperature alarm setting 

0°C ÷ 50.0°C / -50.0°C ÷ ALu 

ALu 

110 

Pr1  High temperature alarm setting 

0°C ÷ 50.0°C / ALL ÷ 110°C  

ALH 

1.0 

Pr2  Temperature alarm recovery differential 

0.1°C o 1°F ÷ 25°C o 77°F 

ALd 

15 

Pr2  Temperature alarm delay 

0 ÷ 250 min 

dAo 

1.3 

Pr2  Delay of temperature alarm at start-up 

0.0 ÷ 23.5 h 

EdA 

20 

Pr2  Alarm delay at the end of defrost 

0 ÷ 250 min 

dot 

20 

Pr2  Delay of temperature alarm after closing the 

door 

0 ÷ 250 min 

AHc 

Ab 

Pr2  Humidity alarm configuration 

rE = relative / Ab = absolute 

AHL 

0.0 

Pr1  Low humidity alarm setting 

0 ÷ 50 / Lci ÷ AHu  

AHu 

100 

Pr1  High humidity alarm setting 

0 ÷ 50 / AHL ÷ uci 

AHH 

2.0 

Pr2  Humidity alarm recovery differential 

0.5 ÷ 25 

AHd 

15 

Pr2  Humidity alarm delay 

0 ÷ 250 min 

dHo 

1.3 

Pr2  Delay of humidity alarm at start-up 

0.0 ÷ 23.5 h 

doH 

20 

Pr2  Alarm delay at the end of defrost 

0 ÷ 250 min 

nPS 

Pr2  Pressure switch number 

0÷15 

doA 

20 

Pr2  Open door alarm delay 

0 ÷ 250 min ( 250 = nu ) 

ot 

0.0 

Pr1  Thermostat probe calibration 

-12.0 ÷ 12.0 

oE 

0.0 

Pr2  Evaporator probe calibration 

-12.0 ÷ 12.0 

o3 

0.0 

Pr1  Humidity probe calibration 

-10 ÷ 10 

P2P 

no 

Pr2  Evaporator probe presence  

no = absent / YES = present 

P3P 

YES 

Pr2  Humidity probe presence 

no = absent / YES = present 

Lci 

Pr2  Readout with 4 mA 

-999 ÷ 999 

uci 

100 

Pr2  Readout with 20 mA 

-999 ÷ 999 

i1P 

oP 

Pr2  Digital input polarity 

cL =open / oP = close 

i1F 

dor 

Pr2  Digital input configuration 

dor / PAL / EAL / bAL / Ht 

odc 

oFF 

Pr2  Outputs status when open door 

on / Fan / oFF 

rrd 

YES 

Pr2  Outputs restarting after doA alarm 

no = no / YES = yes 

did 

Pr2  Digital input alarm delay 

0÷255 min. 

oA1 

Lig Pr2 

Light relay configuration  (XH260L 
terminals 3-4, XH260V terminals. 11-12
):  

ALr = alarm; dEH 

dehumidifier; onF = on/off; 

Lig = light, ESt, dEF not 

select 

Adr 

Pr2 

Serial address 

0÷247 num 

Ptb 

Pr2  Parameter table 

- - -  

rEL 

0.1 

Pr2  Software release  

- - -  

Prd 

-- Pr2 

Probes 

display 

Pb1÷Pb3 