background image

Dixell

 

Operating instructions 

1592002711

 

 

1592002711 XH260L-V  GB r1.0 12.01.04 

 

XH260L - XH260V 

2/5 

 

+

 

 

To exit the programming mode. 

6.1

 

ICONS AND SYMBOLS 

Each LED function is described in the following table. 
 

LED2

LED3

LED4

Temperature Display 

Humidity Display 

 

 

LED 

MODE 

FUNCTION 

Led 4 

ON 

- Instrument in stand by.  
- In “Pr2” indicates that the parameter is also present in “Pr1”. 

 

ON °C 

°F

 

ON °C 

 

ON 

The compressor is running 

 

FLASHING 

- Anti-short cycle delay enabled 

 

LED 3 

ON 

The defrost is enabled 

 

LED 3 

FLASHING 

Drip time in progress 

LED 2 

FLASHING 

Programming Phase (flashing with LED3) 

 

ON Heating 

enabled 

 (temp) 

FLASHING 

Temperature Set programming phase 

 

ON 

- ALARM signal 

 

ON 

Fan is running 

 

ON 

The light is on 

 

ON RH% 

 

ON Dehumidifying 

enabled 

 

ON Humidifying 

enabled 

 (umid) 

FLASHING 

Humidity Set programming phase 

 

6.2

 

HOW TO SEE AND MODIFY THE SET POINT (TEMPERATURE AND  HUMIDITY) 

 

1.

 

Push and immediately release the SET  key: the display will show the Set point 
valueand the correspondant set icon starts flashing; 

2.

 

To change the Set value push the 

or 

n

 arrows within 10s. 

3.

 

To memorise the new set point value push the SET key again or wait 10s. 

6.3

 

TO START A MANUAL DEFROST 

 

 
1. Push 

the 

DOWN key for more than 2 seconds and a manual defrost will start. 

6.4

 

TO ENTER IN PARAMETERS LIST “PR1” 

To enter the parameter list “Pr1” (user accessible parameters) operate as follows: 
 

 

+

 

 
1.

 

Enter the Programming mode by pressing the SET_RH

for few 

seconds. (LED2&3 start flashing) 

2.

 

The instrument will show the first parameter present in “Pr1” 

 
 
 
 

6.5

 

TO ENTER IN PARAMETERS LIST “PR2” 

To access parameters in “Pr2”: 
1.

 

Enter the “Pr1” level. 

2.

 

Select “Pr2” parameter and press the “ SET_RH ” key.  

3.

 

The “PAS” flashing message is displayed, shortly followed by “0 - -” with a flashing zero. 

4.

 

Use 

o

 or 

n

 to input the security code in the flashing digit; confirm the figure by pressing “ 

SET_RH ”.  

The security code is “321“. 

5.

 

If the security code is correct the access to “Pr2” is enabled by pressing “ SET_RH ” on the last 
digit. 

 
Another possibility is the following: after switching ON the instrument the user can push SET_RH + 

n

 keys within 30 seconds. 

 
NOTE: each parameter in “Pr2” can be removed or put into “Pr1” (user level) by pressing SET_RH + 

n

. When a parameter is present in “Pr1” LED 4 is on. 

6.6

 

TO CHANGE PARAMETER VALUES 

1.

 

Enter the Programming mode. 

2.

 

Select the required parameter with 

o

 or 

n

3.

 

Press the “ SET_RH ” key to display its value (LED2&3 start blinking). 

4.

 

Use 

o

 or 

n

 to change its value. 

5.

 

Press “ SET_RH ” to store the new value and move to the following parameter. 

To exit: Press SET_RH + UP or wait 15s without pressing a key. 
NOTE: the new programming is stored even when the procedure is exited by waiting the time-out. 

6.7

 

HOW TO LOCK THE KEYBOARD 

 
 

 

1.  

Keep the 

o

 and 

n

 keys pressed together for more than 3 s the 

o

 and 

n

 keys. 

2.  

The “POF” message will be displayed and the keyboard is locked. At this point it is 
only possible the viewing of the set point or the MAX o Min temperature stored and 
to switch ON and OFF the light, the auxiliary output and the instrument. 

 

TO UNLOCK THE KEYBOARD 
Keep the 

o

 and 

n

 keys pressed together for more than 3s. 

 

6.8

 

ON/OFF FUNCTION 

 

By pushing the ON/OFF key, the instrument shows “OFF” for 5 sec. and the ON/OFF 
LED is switched ON. 
During the OFF status, all the relays are switched OFF and the regulations are stopped;  

N.B. During the OFF status the LED4  button is lighted.  

 

7.

 

PARAMETER LIST 

REGULATION 

dbt

 half dead band width for temperature: (0,1÷25,5°C; 1÷45°F) this band is place below and 

above the temperature set point (SET_TEMP). The compressor is enabled when the temperature 
increases and reaches the SE dbt value. It is turned off when it comes back to the 
SET_TEMP. The heating output is enabled when temperature is less than SET_TEMP -dbt value 
and disabled when the SET_TEMP is reached. 

dbH

 half dead band width for humidity: (0,5÷25,5RH) this band is place below and above the 

humidity set point (SET_RH). The dehumidifying action is enabled when the humidity increases 
and reaches the  dbH value. It is stopped when it comes back to the SET_RH. The 
humidifying  output is enabled when humidity is less than SET_RH -dbH value and disabled when 
the SET_RH is reached. 

LS  Minimum temperature set point limit: (-50,0°C

÷

SET; -58°F÷SET) Sets the minimum 

acceptable value for the set point. 

US  Maximum temperature set point limit: (SET

÷

110°C; SET÷230°F) Set the maximum acceptable 

value for set point. 

OdS Outputs activation delay at start up: (0÷255 min) This function is enabled at the initial start up 

of the instrument and inhibits any output activation for the period of time set in the parameter. 
(Light can work) 

AC  Anti-short cycle delay: (0÷30 min) interval between the compressor stop and the following 

restart. 

tHu  Kind of de-humidifying: db: only with de-humidifier relay (oA1= dEH) 

cHu with de-humidifier and compressor relay (oA1= dEH) 
c-H: without de-humidifier relay, by means of compressor and heating relays (oA1

 dEH)

LSH Minimum humidity set point limit: (

Lci ÷ Set H

) Sets the minimum acceptable value for the 

humidity set point. 

USH Maximum humidity set point limit: (

Set H ÷ uci

) Set the maximum acceptable value for 

humidity set point. 

 
DISPLAY 
CF  Measurement unit: °C
= Celsius; °F= Fahrenheit 
rES  Resolution (for °C): allows decimal point display. dE = 0,1°C; in = 1 °C  
rEH  Resolution for RH%: in = integer; Hd= half digit. 
DEFROST 
tdF   Defrost type: rE
 = electrical heater (Compressor OFF) 

in = hot gas (Compressor and defrost relays ON) 

EdF Defrost mode:  in = interval mode. The defrost starts when the time “Idf” is expired. 

Sd = Smartfrost mode. The time IdF (interval between defrosts) is increased only when the 
compressor is running (even non consecutively).  

SdF  Set point for SMARTFROST: (-30

÷

30 °C/ -22

÷

86 °F) evaporator temperature which allows the 

IdF counting (interval between defrosts) in SMARTFROST mode. 

dtE  Defrost termination temperature: (-50,0÷110,0°C; -58÷230°F) (Enabled only when the 

evaporator probe is present) sets the temperature measured by the evaporator probe which 
causes the end of defrost. 

IdF Interval between defrosts: (1÷120h) Determines the time interval between the beginning of two 

defrost cycles. 

MdF Duration of defrost: (0÷255 min) When P2P = n, no evaporator probe, it sets the defrost 

duration, when P2P = y, defrost end based on temperature, it sets the maximum length for 
defrost. 

dFd  Display during defrost:   rt = real temperature; it = temperature reading at the defrost start; 

Set = set point; dEF = “dEF” label;  dEG = “dEG” label; 

dAd  Defrost display time out: (0

÷

255 min) Sets the maximum time between the end of defrost and 

the restarting of the real room temperature display. 

Fdt   Drain down time: (0÷60 min.) time interval between reaching defrost termination temperature 

and the restoring of the control’s normal operation. This time allows the evaporator to eliminate 
water drops that might have formed due to defrost. 

dPO First defrost after start-up:  y = Immediately; n = after the IdF time 
Hud  Humidity control during defrost: no: the humidity control is stopped during the defrost; yES the 

humidity control works also during the defrost. 

FANS 
FnC  Fan operating mode: C-n
 = running when a load is on, OFF during the defrost;  

C-y = running when a load is on, ON during the defrost; 
O-n = continuous mode, OFF during the defrost; O-y = continuous mode, ON during the defrost; 

TEMPERATURE ALARMS 
ALC Temperature alarm configuration: rE
 = High and Low alarms related to Set Point  

Ab = High and low alarms related to the absolute temperature. 

ALL  Low temperature alarm setting: 

ALC = rE , 0 

÷

 50 °C or 90°F 