Operating instruction manual 

1592019010 

 

1592019010 XEV11D GB r1.2 2008.07.08.doc 

                           

XEV11D 

4/4 

PI PARAMETERS (trained staff) 

CyP 

Cycle Period 

1 ÷ 15 s 

Pr1 

Pb 

Proportional band 

0.1 ÷ 50.0 °C / 1÷90 °F 

4.0 

Pr2 

rS 

Band Offset 

-12.0 ÷ 12.0 °C / -21 ÷ 

21°F 

0.0 Pr2 

inC 

Integration time 

0 ÷ 255 s 

120 

Pr2 

PROBE PARAMETERS 

tPP 

Type of pressure transducer 

PP - LAn 

PP 

Pr2 

PA4 

Probe value at 4mA or at 0V (related to 
PrM parameter) 

 -1.0 bar / -14 PSI / -10 

kPA*10

 ÷ P20 

-0.5 Pr2 

P20 

Probe value at 20mA or at 5V (related 
to PrM parameter) 

 PA4 ÷ 50.0 bar / 725 

PSI / 500 

kPA*10

 

11.0 Pr2 

oPr 

Pressure probe calibration 

-12.0 ÷ 12.0 bar / -174 ÷ 

174 psi / -120 ÷ 120 

kPA*10

 

0 Pr2 

ttE 

type of tEmperature probe 

PtM ÷ ntc 

PtM 

Pr2 

otE 

Temperature probe calibration 

-12.0 ÷ 12.0 °C / -21 ÷ 

21 °F 

0 Pr2 

DIGITAL INPUTS 

i1P 

Free of voltage digital input polarity 

cL – OP 

CL 

Pr2 

i1F 

Free of voltage digital input function 

CCL , rL, dEF 

CCL 

Pr2 

d1d 

Digital input 1 (free of voltage) 
activation delay 

0 ÷ 255 min. 

Pr2 

i2P 

Main voltage digital input polarity 

cL – OP 

CL 

Pr2 

i2F 

Main voltage digital input function 

CCL , rL, dEF 

CCL 

Pr2 

d2d 

Digital input 2 (Main voltage) activation 
delay 

0 ÷ 255min. 

Pr2 

ALARMS 

dAO 

Alarm delay after restarting regulation 

0.0÷42.0

 

hours: tens of 

seconds

 

3.3 

Pr2 

tdA 

Type of alarm signalled by relay 

ALL, SH, PrE, DI, LOC, 

inJ 

ALL Pr2 

LPL 

Lower pressure limit for superheat 
regulation (related to PrM parameter) 

PA4 ÷ P20 bar / PSI / 

kPA*10

 

-0.5 Pr2 

MOP 

Maximum operating pressure threshold 
(related to PrM parameter) 

PA4 ÷ P20 bar / PSI / 

kPA*10

 

11.0 Pr2 

LOP 

Minimum suction pressure limit (related 
to PrM parameter) 

PA4 ÷ P20 bar / PSI / 

kPA*10

 

-0.5 Pr2 

PHy 

Pressure alarm Hysteresis 

0.1 ÷ 5.0 bar / 1÷ 72 psi 

/ 1÷50 

kPA*10

 

0.1 Pr2 

dML 

delta MOP-LOP 

0 ÷ 100% 

30 

Pr2 

tPA 

Maximum time between two MOP 
and/or LOP events 

0.0÷42.0

 

hours: tens of 

seconds

 

0.1 

Pr2 

nPA 

Number of events before locking 

0(Off) ÷ 100 

Pr2 

MSH 

Maximum superheat alarm 

LSH ÷ 32.0 °C / LSH ÷ 

176 °F 

50.0 Pr1 

LSH 

Lowest superheat alarm 

0.0 ÷ MSH °C / 32 ÷ 
MSH °F 

2.5 Pr1 

SHy 

Superheat hysteresis 

0.1 ÷ 25.5 °C / 1 ÷ 77°F 

0.5 

Pr2 

SHd 

Superheat alarm activation delay  

0 ÷ 255 s 

10 

Pr1 

FrC 

Fast-Recovery Constant 

0÷100 s 

50 

Pr2 

DISPLAY 

Lod 

Local display 

SH - PEr – P1 - P2 

SH 

Pr1 

CF 

Temperature measurement units 

°C - °F 

°C 

Pr2 

PMu 

Pressure measurement unit 

bAr – PSI – PA 

bAr 

Pr2 

PrM 

Type of pressure (Absolute / relative) 

rEL – AbS 

rEL 

Pr2 

CLt 

Time to evaluate Cooling statistic  

0 ÷ 48 hours 

48 

Pr1 

CLP 

Cooling call percentage 

Read only 

- - - 

Pr2 

tP1 

Temperature probe value 

Read only 

- --  

Pr1 

PPr 

Pressure probe value 

Read only 

- - - 

Pr1 

tP2 

Temperature converted from pressure 
probe 

Read only 

- - - 

Pr1 

d1S 

Free of voltage digital input state 

Read only 

- - - 

Pr1 

d2S 

Main voltage digital input state 

Read only 

- - - 

Pr1 

Adr 

Serial address 

1÷247 

Pr2 

Mod 

Modbus type 

Std – AdU 

StD 

Pr2 

Ptb 

Parameters map 

- - - 

- - - 

Pr2 

rEL 

Release software 

- - - 

- - - 

Pr2

 

Pr2 

Second level menu  

- - - 

- - - 

Pr1

 

 

16.

 

EXAMPLE OF APPLICATION 

 
 

 