background image

dIXEL

 

Operating instruction manual 

1592019010 

 

1592019010 XEV11D GB r1.2 2008.07.08.doc 

                           

XEV11D 

2/4 

LED 

MODE 

Function 

VALVE

 

OFF 

Valve is closed 

ALARM

 

ON Alarm 

present 

ALARM

 

OFF 

There is no alarm 

5.

 

USER INTERFACE 

5.1

 

TO SEE THE READ-ONLY PARAMETERS 

1)

 

Press and release 

o

 key; 

2)

 

First read-only label is showed; 

3)

 

Slide labels with 

or 

n

arrows; 

4)

 

Press 

SET

 to see read-only value, to change value to see press 

SET

 

5)

 

To leave, press and release 

o

SET 

or wait time-out of about 3 minutes. 

5.2

 

TO SEE THE SET POINT 

 

1)

 

Press the 

SET

 key until the set point will be showed; 

2)

 

To come back to see temperature, wait about 5s or press newly 

SET 

key. 

5.3

 

TO MODIFY THE SET POINT 

To change the set point value operate as follows: 

1)

 

Press the 

SET

 key until the set point will be showed; 

2)

 

Use 

or 

n

 to change its value. 

3)

 

Press “

SET

” to store the new value. 

5.4

 

TO GO TO “PR1” PARAMETERS 

 

To enter in “Pr1” level menu: 
1)

 

Pressing 

SET

n

keys for about 3 seconds. 

2)

 

Instruments shows first parameter in Pr1 menu 

 

5.5

 

TO GO TO “PR2” PARAMETERS 

 

 

To enter  to “Pr2” parameters  list: 

1.

 

Enter to  “Pr1” 

2.

 

Select “Pr2” parameter and press SET 

3.

 

The “PAS” label will be shown, then “0 - - “ with 0 blinking. 

4.

 

Insert “321” password through 

and 

keys

then press SET to 

confirm. 

5.6

 

TO

 

MODIFY THE PARAMETERS VALUE  

 

 

To change the parameter’s value operate as 
follows: 
1.

 

Enter the Programming mode by 
pressing the Set and DOWN key for 
about 3s. 

2.

 

Select the required parameter. 

 

3.

 

Press the “

SET

” key to display its value 

4.

 

Use 

or 

n

 to change its value. 

5.

 

Press “

SET

” to store the new value and move to the following parameter. 

 

To exit

: Press 

SET + 

or wait 30s without pressing a key. 

NOTE

: the set value is stored even when the procedure is exited by waiting the time-out to expire. 

 

6.

 

PARAMETERS LIST 

NOTE:   All pressure parameters are relatives or absolutes depending on PrM parameter.

 

 

REGULATION 
FtY 

Kind of gas (

R22, 134, 404, 407, 410, 507, CO2): Type of gas used by plant. 

Fundamental parameter for correct functioning

 

of all system

PEO 

Probe Error opening percentage: 

(0÷100%) if a temporary probe error occurs, valve 

opening percentage is 

PEo

 until 

PEd

 time is elapsed. 

 

PEd 

Probe Error delay before stopping regulation: 

(0÷239 sec. – 240=unlimited) if probe 

error duration is bigger than 

PEd

 then valve totally closes. If 

PEd=240

 valve opening is 

PEo

 until probe error finishes. 

ESF 

Enable Start Function:

 (n÷Y) n= when digital input configured as CCL is activated, normal 

regulation starts immediately; Y= when digital input configured as CCL is activated valve 
opens with 

OPE

 percentage for time 

SFd.

 

OPE 

Start opening Percentage: 

(0÷100%) Opening valve percentage when start function is 

active and during post defrost phase. This phase duration is 

SFd time

SFd 

Start Function duration: (0.0÷42.0

 

min: tens of seconds)

  It sets start function duration 

and post-defrost duration. 

During this phase the alarms are neglected

 

ind 

injection delay: (0.0÷42.0

 

min: tens of seconds)

 view paragraph 3.1 

dSH delta 

SuperHeat: 

(0.1÷10°C / 1÷50°F) view paragraph 3.1 

dOP 

delta Opening Percentage: 

(0÷100%) view paragraph 3.1 

inb injection 

behaviour:

 (rEG ÷ cL) when an injection problem is signalled if 

inb=cL

 valve will 

close completely, if 

inb=rEG

 valve will regulate normaly by PI (see paragraph 3.1). 

Sti 

Stop regulation interval: (0.0÷24.0

 

hours: tens of minutes)

  after regulating 

continuously for 

Sti

 time, the valve closes for 

Std

 time in order to prevent  ice creation. 

Std Stop 

duration: 

(0÷60 min.) it defines stop regulation time after 

Sti. 

During this stop display 

shows 

StP

 message 

MnF 

Maximum opening percentage at normal Functioning: 

(0÷100%) during regulation it 

sets the maximum valve opening percentage. 

FOt Forced 

Opening 

time-out

(0.0÷24.0

 

hours: tens of minutes)

  If Plant starting function is 

enabled for all 

FOt

 time the function is disabled automatically, see 

Plant starting function

 

paragraph. 

 

PI PARAMETERS (trained staff) 

 

CyP Cycle 

Period: 

(1 ÷ 15s) it permits to set cycle time. 

 

Pb Proportional 

band:

 (0.1 ÷ 50.0 / 1÷90°F)

 

PI proportional band 

rS Band 

Offset:

 (-12.0 ÷ 12.0°C / -21÷21°F) PI band offset 

inC Integration 

time:

 (0 ÷ 255s) PI integration time 

 

PROBE PARAMETERS 

 

tPP 

type of Pressure transducer: (PP – LAn) 

it sets

 

type of pressure transducer to use: 

PP= 

4÷20mA pressure transducer or ratiometric transducer 0÷5V, 

LAn=

 the pressure signal 

arrives from another XEV module.

 

PA4 

Probe value At 4mA or At 0V: 

(-1.0 ÷ P20 bar / -14 ÷ PSI / -10 ÷ P20 kPA*10) pressure 

value measured by probe at 4mA or at 0V (related to PrM parameter)

 

P20 

Probe value 20mA or At 5V: 

(PA4 ÷ 50.0 bar / 725 psi / 500 kPA*10) pressure value 

measured by probe at 20mA or at 5V (related to PrM parameter)

 

oPr 

Pressure probe calibration: 

(-12.0 ÷ 12.0 bar / -174÷174 psi / -120 ÷ 120 kPA*10)  

ttE 

type of tEmperature probe: 

(PtM ÷ Ntc) it allows to set the kind of probe used by the 

instrument: 

PtM 

= Pt1000, 

ntC = 

NTC probe. 

otE 

Temperature probe calibration: 

(-12.0 ÷ 12.0 °C / -21÷21 °F)

 

 

DIGITAL INPUTS 

 

i1P  

Digital Input 1 (Free of voltage) digital input polarity: 

(cL,OP)

 CL

= activated when 

closed; 

OP

= activated when opened 

i1F 

Digital Input 1 (Free of voltage) digital input function: 

(CCL, rL, dEF) 

CCL= 

cooling 

call; 

rL=

 digital input activates relay; 

dEF=

 digital input signals that defrost is active

 

d1d 

Digital Input 1 (Free of voltage) activation delay: 

(0÷255 min.)

 

this activation delay is 

used only if digital input is configured as rL 

i2P 

Digital Input 2 (High voltage) digital input polarity: 

(CL,OP) 

CL

= activated when closed; 

OP

=activated when opened 

i2F 

Digital Input 2 (High voltage) digital input function: 

(CCL, rL, dEF)

 CCL= 

cooling call; 

rL=

 digital input activates relay; 

dEF=

 digital input signals that defrost is active 

d2d 

Digital Input 2 (High voltage) activation delay: 

(0÷255 min.) this activation delay is used 

only if digital input is configured as rL 

 

ALARM

 

 

dAO 

Alarm delay after restarting regulation: (0.0÷42.0

 

min: tens of seconds)

  time between 

digital input activation (configured as CCL) and alarm signalling  

tdA 

Type of alarm signalled by relay: 

(ALL, SH, PrE, di, LOC, inJ) 

ALL=

 all alarm; 

SH=

 

superheat alarm; 

PrE=

 pressure alarm; 

di=

 activation only when digital input  configured as 

rL

 is actived; 

LOC=

 lock alarm in case of 

nPA

 events reached; 

inJ=

 activation in cases of 

injection alarm. 

LPL 

Lower Pressure Limit for superheat regulation: 

(PA4 ÷ P20 bar / psi / 

kPA*10

) when 

suction pressure comes down to LPL the regulation is performed with a LPL fixed value for 
pressure, when pressure comes back to LPL the normal pressure value is used. (related to 
PrM parameter) 

MOP 

Maximum Operating Pressure threshold: 

(PA4 ÷ P20 bar / psi / 

kPA*10

)

 

if suction 

pressure exceeds maximum operating pressure value, instrument signals situation with  
alarm LED 

. (related to PrM parameter) 

LOP 

Lowest Operating Pressure:

 (PA4 ÷ P20 bar / psi / 

kPA*10

) if the suction pressure 

comes down to this value a low pressure alarm is signalled with alarm LED 

. (related to 

PrM parameter) 

PHy  

Pressure alarm Hysteresis: 

(0.1 ÷ 5.0 bar / 1÷ 72 PSI / 1÷50 

kPA*10

) alarm hysteresis 

to disable alarm signalling. 

dML delta 

MOP-LOP: 

(0 ÷ 100%) when a MOP alarm occurs valve will close of the dML 

percentage every cycle period until MOP alarm is active. When LOP occurs valve will open 
of the dML percentage every cycle period until LOP alarm is active. 

tPA 

Maximum time between two MOP and/or LOP events: (0.0÷42.0

 

min: tens of 

seconds)

  time interval to calculate the number of the pressure switch activation. 

nPA 

Number of events before locking: 

(0=Off ÷ 100) number of MOP or LOP events, during 

the “

tPA

” interval, before locking instrument.  

MSH 

Maximum SuperHeat alarm:

 (LSH÷32,0°C / LSH÷176°F) when superheat exceeds this 

value an high superheat alarm is signalled after interval 

SHd

 

LSH 

Lowest SuperHeat alarm:

 (0.0÷MSH °C / 32÷MSH °F) when superheat goes down to this 

value a low superheat alarm is signalled after interval 

SHd 

SHy 

SuperHeat alarm Hysteresis: 

(0.0÷25.5°C / 1÷77°F) hysteresis for superheat alarm 

deactivation

 

 

SHd 

SuperHeat alarm activation delay:

 (0÷255s) when a superheat alarm occurs, the time 

SHd have to pass before signalling alarm  

FrC Fast-recovery 

Constant: 

(0÷100s) permits to increase integral time when SH is below the 

set-point. If 

FrC=0

 fast recovery function is disabled. 

 

DISPLAY 

 

Lod  

Local  display:

(SH, PEr, P1, P2) 

SH= 

superheat; 

PEr = 

valve

 

opening percentage; 

P1= 

value of temperature measured; 

P2= 

pressure measured by P2 probe; 

CF 

Temperature measurement units: 

(°C÷°F)

 

°

C=

 Celsius degree; 

°F= 

Fahrenheit degree; 

ATTENTION:

 by changing measurement unit, the regulation parameters have to be 

correctly changed 

PMu 

Pressure Measurement units: 

(bAr, PSI, kPA*10) 

bAr=

 bar; 

PSI= 

psi; 

PA= KPa*10

ATTENTION:

 by changing measurement unit, the regulation parameters have to be 

correctly changed 

PrM 

Pressure visualization Mode: 

(rEL÷AbS)

 rEL= 

relative pressure; 

AbS=

 absolute 

pressure; 

CLt 

CooLing time statistic: 

(0÷48h) time interval used to evaluate a cooling call statistic.  

During this time comes calculated how much time the cooling call is remained active 

CLP 

CooLing Percentage (read only): 

Display the percentage of time during which the cooling 

call was active in the time interval defined by 

parameter

 

CLt

 

tP1 

temperature Probe value (read only):

 it shows temperature probe value from P1

 

Reviews: