Operating instructions
cod. 1592001300
1592001300 XC440C gb r1.0 07.06.2004.doc
rel. 1.0
Page
24 / 28
Action
The alarm is signalled with standard action. The outputs are unchanged.
18.2 Alarm muting
Press any buttons to silence the buzzer during an alarm condition.
Hold pressed for more than 3 seconds switch off the alarm relay during an alarm condition
18.3 Alarm conditions – summary table
Code
Description
Cause
Action
Reset
P1
P1 probe failure
alarm
Probe failure or out of
range
The compressors
are activated
according to the
SPr or PoPr
parameters.
Automatically as soon as the probe restarts
working.
EA1
EA2
EA3
EA4
Load safeties
alarm
Safeties
compressor/fan input
activation.
NOTE: with step
compressors 1 input
for each compressor
has to be used.
the corresponding
load is turned off.
(with step
compressors all
relays referred to
the input are
disabled).
Recovery depends on ALMr parameter:
With ALMr = no The instrument restart the
standard operating mode when the input is
disabled.
With ALMr = yES manual recover for the
alarms of compressors and fans. Push the
DOWN key for 3s.
LA
Minimum
pressure
(temperature)
alarm for
compressors
Suction pressure or
temperature lower
than
SET_C-LAL value
signalling only
Automatically: as soon as the pressure or
temperature reaches the (Set_C-LAL+
differential) value.
(differential = 0.3bar or 1°C)
LA2
Minimum
pressure
(temperature)
alarm for fans
Condensing pressure
or temperature lower
than
SET_F-LAL value
signalling only
Automatically: as soon as the pressure or
temperature reaches the (Set_F-LAL+
differential) value.
(differential = 0.3bar or 1°C)
HA
Maximum
pressure
(temperature)
alarm for
compressors
Suction pressure or
temperature higher
than
SET_C+HAL value
signalling only
Automatically: as soon as the pressure or
temperature reaches the (Set_C + HAL -
differential) value.
(differential = 0.3bar or 1°C)
HA2
Maximum
pressure
(temperature)
alarm for fans
Condensing pressure
or temperature higher
than
SET_F+HAL value
signalling only
Automatically: as soon as the pressure or
temperature reaches the (Set_F + HAL -
differential) value.
(differential = 0.3bar or 1°C)
A5
Liquid level
alarm
Input enabled
signalling only
Automatically as soon as the input is disabled
A14
Load
maintenance
alarm
A load has worked for
the hour set in the
SEr parameter
signalling only
Manually: reset the running hour of the
compressor
(see par. 8
Running hours of loads
)