10.2  UPLOAD (FROM THE INSTRUMENT TO THE “HOT KEY”)

1. 

Turn OFF the instrument by means of the ON/OFF key and remove the TTL serial cable if present; then
turn it ON again.

2. 

When the Wing unit  is ON, insert the “Hot key” and push 

X

 

key; the  "uPL" message appears.

3. Push 

SET” key to start the UPLOAD; the “uPL” message is blinking.

4. 

Turn OFF the instrument remove the “Hot Key”, plug in  the TTL serial cable, then turn it ON again.

At the end of the data transfer phase the instrument displays the following messages:
end “ for right programming.
err” for failed programming. In this case push “SET” key if you want to restart the programming again or
remove the not programmed “Hot key”.

11. ALARM 

SIGNALS

Message Cause

Outputs

“P1”

Thermostat probe failure

Alarm output ON; Compressor output according to

parameters “COn” and “COF”

“P2”

Evaporator probe failure

Alarm output ON; Other outputs unchanged

“P3”

Auxiliary probe failure

Alarm output ON; Other outputs unchanged

“HA”

Maximum temperature alarm

Alarm output ON; Other outputs unchanged

“LA”

Minimum temperature alarm

Alarm output ON; Other outputs unchanged

“EE”

Data or memory failure

Alarm output ON; Other outputs unchanged

“dA”

Defrost timeout alarm

Alarm output ON; Other outputs unchanged

“dAL”

Door switch alarm

Alarm output ON; Other outputs unchanged

“EAL”

External alarm

Alarm output ON; Other outputs unchanged

“BAL”

Serious external alarm

Alarm output ON; Other outputs OFF

“PAL”

Pressure switch alarm

Alarm output ON; Other outputs OFF

The alarm message is displayed until the alarm condition is recovery.
All the alarm messages are showed alternating with the room temperature except for the “P1” which is flashing.
To reset the “EE” alarm and restart the normal functioning press any key, the “rSt” message is displayed for
about 3s.

11.1 SILENCING 

BUZZER

Once the alarm signal is detected the buzzer can be silenced by pressing any key.

11.2   “EE” ALARM

The 

 instruments are provided with an internal check for the data integrity. Alarm “EE” flashes when a

failure in the memory data occurs. In such cases the alarm output is enabled.

11.3 ALARM 

RECOVERY

Probe alarms : “P1” (probe1 faulty), “P2” and “P3”; they automatically stop 10s after the probe restarts normal
operation. Check connections before replacing the probe.
Temperature alarms “HA” and “LA” automatically stop as soon as the thermostat temperature returns to normal
values or when the defrost starts.
Door switch alarm “dA”  stop as soon as the door is closed.
External alarms “EAL”, “BAL”  stop as soon as the external digital input is disabled “PAL” alarm is recovered by
switching OFF the instrument.

12. TECHNICAL 

DATA

Housing: 

self extinguishing ABS.

Case: facia 38x185 mm; depth 76mm
Mounting : panel mounting in a 150x31 mm panel cut-out with two screws. 

 3 x 2mm.

Distance between the holes 165mm

Protection: IP20.
Frontal protection: IP65 with frontal gasket mod RG-L. (optional)
Connections: Screw terminal block 

 2,5 mm

2

 heat-resistant wiring and 6,3mm Faston

Power supply: 230Vac or. 110Vac 

±

 10%

Power absorption: 7VA max.
Display: 3 digits, red LED, 14,2 mm high.
Inputs: 3 NTC probes
Digital inputs: 2 free voltage
Relay outputs: Total current on loads MAX. 20A
compressor: relay SPST 20(8) A, 250Vac
light: relay SPST 16(3) A, 250Vac
fans: relay SPST 8(3) A, 250Vac
defrost: relay SPST 8(3) A, 250Vac
Other output : alarm buzzer
Serial output : TTL standard
Communication protocol: Modbus - RTU
Data storing: on the non-volatile memory (EEPROM).
Kind of action: 1B.
Pollution grade: normal
Software class: A.
Operating temperature: 0÷60 °C.
Storage temperature: -25÷60 °C.
Relative humidity: 20

÷

85% (no condensing)

Measuring and regulation range: NTC probe: -40÷110°C (-58÷230°F)
Resolution: 0,1 °C or 1°C or 1 °F (selectable).
Accuracy (ambient temp. 25°C):  ±0,5 °C ±1 digit

13. CONNECTIONS

13.1 XW260L

C

ommo

n

D

o

o

r sw

it

ch

D

ig

it

a

l in

p

De

f.

Di

sp

la

y

R

oom

 

  

;:/

Def.

Comp

Fan

Light

Li

ne

Ne

u

tr

a

l

     

   

20A

250Vac

MA X

20A

8A

250Vac

16A

250Vac

8A

250Vac

14.  DEFAULT SETTING VALUES

Label Name

  Range

Default

Level

REGULATION

°C/°F

XW260L

Set

Set point

LS÷US

-5

Pr1

Hy

Differential

0,1÷25,5 °C / 1÷45°F

2

Pr1

LS

Minimum set point

 -50,0°C÷SET / -58°F÷SET

-30

Pr2

US

Maximum set point

SET ÷ 110°C / SET ÷ 230°F

20

Pr2

OdS

Outputs activation delay at start up

0÷255 min.

1

Pr2

AC

Anti-short cycle delay

0÷30 min.

1

Pr1

CCt

Compressor ON time during fast freezing

0 ÷ 23h 50 min.

0

Pr2

COn

Compressor ON time with faulty probe

0÷255 min.

15

Pr2

COF

Compressor OFF time with faulty probe

0÷255 min.

30

Pr2

DISPLAY

CF

Temperature measurement unit

°C ÷ °F

°C

Pr2

rES

Resolution (integer/decimal point)

in ÷ de

de

Pr1

Lod

Local display

P1 ÷ 1r2

P1

Pr2

Red

Remote display

P1 ÷ 1r2

P1

Pr2

DEFROST

tdF

Defrost type

rE,  rT,  in

rE

Pr1

EdF

Defrost mode

In, Sd

In

Pr2

SdF

Set point for SMART DEFROST

-30 ÷ +30°C / -22÷+86°F

0

Pr2

dtE

Defrost termination temperature (1°Evaporator)

-50,0÷110°C/ -58÷230°F

8

Pr1

IdF

Interval between defrost cycles

1÷120h

6

Pr1

MdF

(Maximum) length for 1° defrost

0÷255 min.

30

Pr1

dFd

Displaying during defrost

rt, it, SEt, dEF, dEG

it

Pr2

dAd

MAX display delay after defrost

0÷255 min.

30

Pr2

Fdt

Draining time

0÷60 min.

0

Pr2

dPO

First defrost after start up

n ÷ y

n

Pr2

dAF

Defrost delay after fast freezing

0 ÷ 23h 50 min.

2

Pr2

FANS

FnC

Fans operating mode

C-n, C-y, O-n, O-y

O-n

Pr2

Fnd

Fans delay after defrost

0÷255 min.

10

Pr2

FSt

Fans stop temperature

-50,0÷110°C/ -58÷230°F

2

Pr2

ALARMS

ALC

Temperature alarms configuration

rE÷Ab

rE

Pr2

ALU

MAXIMUM temperature alarm

-50,0÷110°C/ -58÷230°F

10

Pr1

ALL

minimum temperature alarm

-50,0÷110°C/ -58÷230°F

10

Pr1

AFH

Temperature alarm and fan differential

0,1÷25,5 °C / 1÷45°F

2

ALd

Temperature alarm delay

0÷255 min.

15

Pr2

dAO

Delay of temperature alarm at start up

0 ÷ 23h 50 min.

1,3

Pr2

EdA

Alarm delay at the end of defrost

0÷255 min.

30

Pr2

dot

Delay of temperature alarm after closing the door

0÷255 min.

15

Pr2

dOA

Open door alarm delay

0÷255 min.

15

Pr2

nPS

Pressure switch activation number

0÷15

0

Pr2

ANALOGUE INPUTS

Ot

Thermostat probe calibration

-12,0÷12,0°C / -21÷21°F

0

Pr1

OE

Evaporator probe calibration

-12,0÷12,0°C / -21÷21°F

0

Pr2

O3

Auxiliary probe calibration

-12,0÷12,0°C / -21÷21°F

0

Pr2

P2P

Evaporator probe presence

n ÷ y

y

Pr2

P3P

Auxiliary probe presence

n ÷ y

n

Pr2

HES

Temperature increase during the Energy Saving
cycle

-30÷30°C / -22÷86°F

0

Pr2

DIGITAL INPUTS

Odc

Open door control

no, Fan, CPr, F_C

Fan

Pr2

I1P

Door switch polarity

CL÷OP

CL

Pr2

I2P

Configurable digital input polarity

CL÷OP

CL

Pr2

i2F

Digital input configuration

EAL, bAL, PAL, dFr,

AUS, ES, OnF

EAL

Pr2

dId

Digital input alarm delay

0÷255 min.

5

Pr2

SAA

Set point for anti-condensing heater

-50,0÷110°C/ -58÷230°F

- - -

OTHER

1

Adr

Serial address

0÷247

1.0

Pr1

rEL

Software release

- - -

- - -

Pr2

Ptb

Map code

- - -

- - -

Pr2

Prd

Probes display

Pb1÷Pb3

- - -

Pr2

Pr2

Access parameter list

- - -

Pr2

Dixell s.r.l. Via dell’Industria, 27
32010 Z.I Pieve d’Alpago (BL) ITALY
tel. +39 - 0437 - 98 33 - fax +39 - 0437 - 98 93 13

(PDLOGL[HOO#GL[HOOFRP  KWWSZZZGL[HOOFRP

Reviews: