dIXEL
Installing and Operating Instructions
rel.1.0 - cod. 1598002153
1598002153 XW40LS GB VCS r1.0 06.12.2006.doc
XW40LS
3/3
2.
Automatically the parameter list of the
“Hot Key”
is downloaded into the Wing memory, the
“
doL
” message is blinking. After 10 seconds the instrument will restart working with the new
parameters.
3.
Turn OFF the instrument remove the
“Hot Key”,
plug in the TTL serial cable, then turn it ON
again.
At the end of the data transfer phase the instrument displays the following messages:
“
End
“ for right programming. The instrument starts regularly with the new programming.
“
Err
” for failed programming. In this case turn the unit off and then on if you want to restart the
download again or remove the “
Hot key
” to abort the operation.
8.2
UPLOAD (FROM THE INSTRUMENT TO THE “HOT KEY”)
1.
Turn OFF the instrument by means of the ON/OFF key and remove the TTL serial cable if
present; then turn it ON again.
2.
When the Wing unit is ON, insert the “
Hot key
” and push
o
key; the
"uPL"
message
appears.
3.
Push “
SET”
key to start the UPLOAD; the “
uPL
” message is blinking.
4.
Turn OFF the instrument remove the
“Hot Key”,
plug in the TTL serial cable, then turn it ON
again.
At the end of the data transfer phase the instrument displays the following messages:
“
end
“ for right programming.
“
err
” for failed programming. In this case push “SET” key if you want to restart the programming again
or remove the not programmed “
Hot key
”.
9.
ALARM SIGNALS
Message Cause
Outputs
“P1”
Thermostat probe failure
Alarm output ON; Compressor output according to
parameters “COn” and “COF”
“HA”
Maximum temperature alarm
Alarm output ON; Other outputs unchanged
“LA”
Minimum temperature alarm
Alarm output ON; Other outputs unchanged
“EE” Data or memory failure
Alarm output ON; Other outputs unchanged
The alarm message is displayed until the alarm condition is recovery.
All the alarm messages are showed alternating with the room temperature except for the “P1” which is
flashing. To reset the “EE” alarm and restart the normal functioning press any key, the “
rSt
” message is
displayed for about 3s.
9.1
SILENCING BUZZER
Once the alarm signal is detected the buzzer can be silenced by pressing any key.
9.2
“EE” ALARM
The
dIXEL
instruments are provided with an internal check for the data integrity. Alarm “EE” flashes
when a failure in the memory data occurs. In such cases the alarm output is enabled.
9.3
ALARM RECOVERY
Probe alarm
: “
P1
” (probe1 faulty), automatically stops 10s after the probe restarts normal operation.
Check connections before replacing the probe.
Temperature alarms
“
HA
” and “
LA
” automatically stop as soon as the thermostat temperature returns
to normal values or when the defrost starts.
10.
TECHNICAL DATA
Housing:
self extinguishing ABS.
Case:
facia 38x185 mm; depth 40mm
Mounting :
panel mounting in a 150x31 mm panel cut-out with two screws.
∅
3 x 2mm.
Distance between the holes 165mm
Frontal protection:
IP65 with frontal gasket mod RG-L. (optional)
Connections:
Faston 2.8mm for probe heat-resistant wiring and 6,3mm Faston for loads and supply
Power supply:
230Vac or. 110Vac
±
10%
Power absorption: 4
VA max.
Display
: 3 digits, red LED, 14,2 mm high.
Inputs
: 1 NTC or PTC probe
Relay outputs:
Total current on loads MAX. 20A
compressor:
relay SPST 20(8) A, 250Vac
light:
relay SPST 8(3) A, 250Vac
fan:
relay SPST 8(3) A, 250Vac
Other output :
alarm buzzer (optional)
Data storing
: on the non-volatile memory (EEPROM).
Kind of action:
1B.
Pollution grade:
normal
Software class:
A.
Operating temperature:
0÷60 °C.
Storage temperature:
-25÷60 °C.
Relative humidity:
20
÷
85% (no condensing)
Measuring and regulation range: PTC probe:
-50÷150°C (-58÷302°F)
NTC probe:
-40÷110°C (-58÷230°F)
Resolution:
0,1 °C or 1°C or 1 °F (selectable).
Accuracy (ambient temp. 25°C)
: ±0,5 °C ±1 digit
11.
CONNECTIONS
11.1
XW40LS
8(3)A
Hot - Key
Fan
Comp
20(8)A
8(3)A
N
L
N
N
Light
N
L
L
L
Max 20A
WARNING: Because of direct load connections, main voltage 230V is present in the faston of
loads, when the instrument is powered.
12.
DEFAULT SETTING VALUES
Label Name
Range
Default Level
REGULATION
°C/°F
Set Set
point
LS÷US
2 Pr1
Hy
Differential
0,1÷25,5 °C / 1÷45°F
1
Pr1
LS
Minimum set point
-50,0°C÷SET / -58°F÷SET
-10
Pr2
US
Maximum set point
SET ÷ 110°C / SET ÷
230°F
10 Pr2
OdS
Outputs activation delay at start up
0÷255 min.
1
Pr2
AC
Anti-short cycle delay
0÷30 min.
1
Pr1
CCt
Compressor ON time during fast freezing
0 ÷ 23h 50 min.
0
Pr2
COn
Compressor ON time with faulty probe
0÷255 min.
15
Pr2
COF
Compressor OFF time with faulty probe
0÷255 min.
5
Pr2
CH
Type of regulation
CL, Ht
CL
Pr2
DISPLAY
CF
Temperature measurement unit
°C ÷ °F
°C
Pr2
rES
Resolution (integer/decimal point)
in ÷ de
dE
Pr1
DEFROST
EdF
Defrost mode
In, Sd
in
Pr2
IdF
Interval between defrost cycles
1÷120h
7
Pr1
MdF
(Maximum) length for 1° defrost
0÷255 min.
60
Pr1
dFd
Displaying during defrost
rt, it, SEt, dEF, dEG
it
Pr2
dAd
MAX display delay after defrost
0÷255 min.
30
Pr2
dPO
First defrost after start up
n ÷ y
n
Pr2
dAF
Defrost delay after fast freezing
0 ÷ 23h 50 min.
0
Pr2
ALARMS
ALC
Temperature alarms configuration rE÷Ab
rE
Pr2
ALU
MAXIMUM temperature alarm -50,0÷110°C/
-58÷230°F
8
Pr1
ALL
minimum temperature alarm -50,0÷110°C/
-58÷230°F
2
Pr1
AFH
Temperature alarm differential
0,1÷25,5 °C / 1÷45°F
1
Pr2
ALd
Temperature alarm delay
0÷255 min.
15
Pr2
dAO
Delay of temperature alarm at start up
0 ÷ 23h 50 min.
1.3
Pr2
EdA
Alarm delay at the end of defrost
0÷255 min.
20
Pr2
ANALOGUE
INPUTS
Ot
Thermostat probe calibration
-12,0÷12,0°C / -21÷21°F
0
Pr1
OTHER
Pbc
Kind of probe
PbC, ntc
ntc
Pr2
rEL
Software release
- - -
2.0
Pr2
Ptb
Map code
- - -
-
Pr2
Prd Probes
display
Pb1
Pr2
Pr2
Access parameter list
- - -
Pr1