Installing and Operating Instructions 

rel.1.0 - cod. 1598002153 

 

1598002153 XW40LS GB VCS r1.0 06.12.2006.doc 

                           

XW40LS 

3/3

 

2.

 

Automatically the parameter list of the 

“Hot Key”

 is downloaded into the Wing memory, the 

doL

” message is blinking. After 10 seconds the instrument will restart working with the new 

parameters. 

3.

 

Turn OFF the instrument remove the 

“Hot Key”, 

plug in  the TTL serial cable, then turn it ON 

again. 

At the end of the data transfer phase the instrument displays the following messages: 

End

 “ for right programming. The instrument starts regularly with the new programming. 

Err

” for failed programming. In this case turn the unit off and then on if you want to restart the 

download again or remove the “

Hot key

” to abort the operation. 

 

 

8.2

 

UPLOAD (FROM THE INSTRUMENT TO THE “HOT KEY”) 

1.

 

Turn OFF the instrument by means of the ON/OFF key and remove the TTL serial cable if 
present; then turn it ON again. 

2.

 

When the Wing unit  is ON, insert the “

Hot key

” and push 

o

 

key; the  

"uPL" 

message 

appears. 

3.

 

Push “

SET”

 key to start the UPLOAD; the “

uPL

” message is blinking. 

4.

 

Turn OFF the instrument remove the 

“Hot Key”, 

plug in  the TTL serial cable, then turn it ON 

again. 

At the end of the data transfer phase the instrument displays the following messages: 

end

 “ for right programming. 

err

” for failed programming. In this case push “SET” key if you want to restart the programming again 

or remove the not programmed “

Hot key

”. 

9.

 

ALARM SIGNALS 

Message  Cause 

Outputs 

“P1” 

Thermostat probe failure 

Alarm output ON; Compressor output according to 
parameters “COn” and “COF” 

“HA” 

Maximum temperature alarm 

Alarm output ON; Other outputs unchanged 

“LA” 

Minimum temperature alarm 

Alarm output ON; Other outputs unchanged 

“EE”   Data or memory failure 

Alarm output ON; Other outputs unchanged 

 
The alarm message is displayed until the alarm condition is recovery. 
All the alarm messages are showed alternating with the room temperature except for the “P1” which is 
flashing. To reset the “EE” alarm and restart the normal functioning press any key, the “

rSt

” message is 

displayed for about 3s. 

9.1

 

SILENCING BUZZER 

Once the alarm signal is detected the buzzer can be silenced by pressing any key.  

9.2

 

 “EE” ALARM 

The 

dIXEL

 instruments are provided with an internal check for the data integrity. Alarm “EE” flashes 

when a failure in the memory data occurs. In such cases the alarm output is enabled. 

9.3

 

ALARM RECOVERY 

Probe alarm

: “

P1

” (probe1 faulty), automatically stops 10s after the probe restarts normal operation. 

Check connections before replacing the probe. 

Temperature alarms

 “

HA

” and “

LA

” automatically stop as soon as the thermostat temperature returns 

to normal values or when the defrost starts. 

10.

 

TECHNICAL DATA 

Housing: 

self extinguishing ABS.

 

Case: 

facia 38x185 mm; depth 40mm 

Mounting :

 panel mounting in a 150x31 mm panel cut-out with two screws. 

 3 x 2mm. 

 

Distance between the holes 165mm 

Frontal protection:

 IP65 with frontal gasket mod RG-L. (optional) 

Connections: 

Faston 2.8mm for probe heat-resistant wiring and 6,3mm Faston for loads and supply 

Power supply: 

230Vac or. 110Vac 

±

 10% 

 

Power absorption: 4

VA max.

 

Display

: 3 digits, red LED, 14,2 mm high.  

Inputs

: 1 NTC or PTC probe 

Relay outputs:

 Total current on loads MAX. 20A

 

compressor:

 relay SPST 20(8) A, 250Vac  

light: 

relay SPST 8(3) A, 250Vac  

fan: 

relay SPST 8(3) A, 250Vac  

Other output :

 alarm buzzer (optional) 

Data storing

: on the non-volatile memory (EEPROM). 

Kind of action: 

1B. 

Pollution grade: 

normal 

Software class: 

A.

 

Operating temperature: 

0÷60 °C. 

Storage temperature: 

-25÷60 °C.  

Relative humidity:

 20

÷

85% (no condensing) 

Measuring and regulation range: PTC probe: 

-50÷150°C (-58÷302°F) 

NTC probe: 

-40÷110°C (-58÷230°F) 

Resolution: 

0,1 °C or 1°C or 1 °F (selectable). 

Accuracy (ambient temp. 25°C)

:  ±0,5 °C ±1 digit 

  

11.

 

CONNECTIONS 

11.1

 

XW40LS 

8(3)A

Hot - Key

Fan

Comp

20(8)A

8(3)A

N

L

N

N

Light

N

L

L

L

Max 20A

 

WARNING: Because of direct load connections, main voltage 230V is present in the faston of 

loads, when the instrument is powered. 

 

 

12.

 

DEFAULT SETTING VALUES 

 

Label  Name 

  Range 

Default  Level

 

REGULATION  

°C/°F 

 

Set Set 

point 

LS÷US 

2  Pr1 

Hy 

Differential 

0,1÷25,5 °C / 1÷45°F 

Pr1 

LS 

Minimum set point 

 -50,0°C÷SET / -58°F÷SET

-10 

Pr2 

US 

Maximum set point 

SET ÷ 110°C / SET ÷ 

230°F 

10 Pr2 

OdS 

Outputs activation delay at start up 

0÷255 min. 

Pr2 

AC 

Anti-short cycle delay 

0÷30 min. 

Pr1 

CCt 

Compressor ON time during fast freezing 

0 ÷ 23h 50 min. 

Pr2 

COn 

Compressor ON time with faulty probe 

0÷255 min. 

15 

Pr2 

COF 

Compressor OFF time with faulty probe 

0÷255 min. 

Pr2 

CH 

Type of regulation 

CL, Ht 

CL 

Pr2 

 DISPLAY 

 

 

CF 

Temperature measurement unit 

°C ÷ °F 

°C 

Pr2 

rES 

Resolution (integer/decimal point) 

in ÷ de 

dE 

Pr1 

 DEFROST 

 

 

EdF 

Defrost mode 

In, Sd 

in 

Pr2 

IdF 

Interval between defrost cycles 

1÷120h 

Pr1 

MdF 

(Maximum) length for 1° defrost 

0÷255 min. 

60 

Pr1 

dFd 

Displaying during defrost 

rt, it, SEt, dEF, dEG 

it 

Pr2 

dAd 

MAX display delay after defrost 

0÷255 min. 

30 

Pr2 

dPO 

First defrost after start up 

n ÷ y 

Pr2 

dAF 

Defrost delay after fast freezing 

0 ÷ 23h 50 min. 

Pr2 

 ALARMS 

 

 

ALC 

Temperature alarms configuration rE÷Ab 

rE 

Pr2 

ALU 

MAXIMUM temperature alarm -50,0÷110°C/ 

-58÷230°F 

Pr1 

ALL 

minimum temperature alarm -50,0÷110°C/ 

-58÷230°F 

Pr1 

AFH 

Temperature alarm differential 

0,1÷25,5 °C / 1÷45°F 

Pr2 

ALd 

Temperature alarm delay 

0÷255 min. 

15 

Pr2 

dAO 

Delay of temperature alarm at start up 

0 ÷ 23h 50 min. 

1.3 

Pr2 

EdA 

Alarm delay at the end of defrost  

0÷255 min. 

20 

Pr2 

 ANALOGUE 

INPUTS 

 

 

Ot 

Thermostat probe calibration 

-12,0÷12,0°C / -21÷21°F 

Pr1 

OTHER  

 

Pbc 

Kind of probe 

PbC, ntc 

ntc 

Pr2 

rEL 

Software release 

- - - 

2.0 

Pr2 

Ptb 

Map code 

- - - 

Pr2 

Prd Probes 

display 

Pb1 

  Pr2 

Pr2  

Access parameter list 

- - - 

 

Pr1 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Dixell S.p.A. Via dell’Industria, 27  
32010 Z.I Pieve d’Alpago (BL) ITALY  
tel. +39 - 0437 - 98 33 - fax +39 - 0437 - 98 93 13 

E-mail:[email protected]  -  http://www.dixell.com

 