background image

dIXEL

 

Installing and Operating Instructions 

rel.1.0 - cod. 1598002153 

 

1598002153 XW40LS GB VCS r1.0 06.12.2006.doc 

                           

XW40LS 

2/3

 

4.9

 

HOW TO CHANGE THE PARAMETER VALUE 

1.

 

Enter the Programming mode. 

2.

 

Select the required parameter with 

o

 or 

n

3.

 

Press the “

SET

” key to display its value (

 and 

 LED starts blinking). 

4.

 

Use 

o

 or 

n

 to change its value. 

5.

 

Press “

SET

” to store the new value and move to the following parameter. 

To exit

: Press 

SET + UP 

or wait 15s without pressing a key. 

NOTE

: the new programming is stored even when the procedure is exited by waiting the time-out. 

4.10

 

HOW TO LOCK THE KEYBOARD 

 

 

 

1.  

Keep the 

o

 and 

n

 keys pressed together for more than 3 s the 

o

 and 

n

 keys. 

2.  

The “POF” message will be displayed and the keyboard is locked. At this point it is 
only possible the viewing of the set point or the MAX o Min temperature stored and 
to switch ON and OFF the light, the auxiliary output and the instrument. 

 

TO UNLOCK THE KEYBOARD 

Keep the 

o

 and 

n

 keys pressed together for more than 3s. 

 

4.11

 

ON/OFF FUNCTION 

 

 

By pushing the 

ON/OFF

 key, the instrument shows “OFF” for 5 sec. and the ON/OFF 

LED is switched ON. 
During the OFF status, all the relays are switched OFF and the regulations are stopped;  

N.B. During the OFF status the Light button is active. 

 

 

5.

 

PARAMETER LIST 

REGULATION 
Hy Differential: 

(0,1÷25,5°C; 1÷45°F): Intervention differential for set point, always positive. 

Compressor Cut IN is Set Point Plus Differential (Hy). Compressor Cut OUT is when the 
temperature reaches the set point. 

LS  Minimum set point limit: 

(-50,0°C

÷

SET; -58°F÷SET) Sets the minimum acceptable value for 

the set point. 

US  Maximum set point limit: 

(SET

÷

110°C; SET÷230°F) Set the maximum acceptable value for set 

point. 

OdS Outputs activation delay at start up:

 (0÷255 min) This function is enabled at the initial start up 

of the instrument and inhibits any output activation for the period of time set in the parameter. 
(Light can work) 

AC  Anti-short cycle delay: 

(0÷30 min) interval between the compressor stop and the following 

restart. 

CCt Thermostat override:

 (0min ÷23h 50min) allows to set the length of the continuous cycle. Can 

be used, for instance, when the room is filled with new products.

 

Con Compressor ON time with faulty probe: 

(0÷255 min) time during which the compressor is active 

in case of faulty thermostat probe. With COn=0 compressor is always OFF. 

COF Compressor OFF time with faulty probe: 

(0÷255 min) time during which the compressor is off 

in case of faulty thermostat probe. With COF=0 compressor is always active. 

CH  Type of action: 

CL = cooling; Ht = heating.

 

 
DISPLAY 
CF  Temperature measurement unit:

 °C = Celsius; °F = Fahrenheit. When the measurement unit is 

changed the SET point and the values  of some parameters have to be modified. 

rES  Resolution (for °C)

: (in = 1°C; de = 0,1°C) allows decimal point display. 

dE

 = 0,1°C; 

in

 = 1 °C  

 

DEFROST 
EdF Defrost mode:

   

in

 = 

interval mode

. The defrost starts when the time “

Idf

” is expired. 

Sd

 = 

Smartfrost mode

. The time IdF (interval between defrosts) is increased only when the 

compressor is running (even non consecutively).  

IdF Interval between defrosts: 

(1÷120h) Determines the time interval between the beginning of two 

defrost cycles. 

MdF  (Maximum) duration of defrost: 

(0÷255 min) When 

P2P = n

, no evaporator probe, it sets the 

defrost duration, when 

P2P = y

, defrost end based on temperature, it sets the maximum length for 

defrost. 

dFd  Display during defrost:  
 rt

 = real temperature; 

it

 = temperature reading at the defrost start; 

Set

 = set point; 

dEF

 = “dEF” label; 

 dEG

 = “dEG” label;

 

dAd  Defrost display time out:

 (0

÷

255 min) Sets the maximum time between the end of defrost and 

the restarting of the real room temperature display. 

dPO First defrost after start-up:   
 y 

= Immediately; 

n

 = after the IdF time 

dAF  Defrost delay after fast freezing: 

(0min÷23h 50min)  after a Fast Freezing cycle, the first defrost 

will be delayed for this time. 

 

ALARMS 
ALC Temperature alarm configuration 

rE

 = High and Low alarms related to Set Point  

Ab

 = High and low alarms related to the absolute temperature. 

ALU High temperature alarm setting:

  

 

ALC= rE, 0 

÷

 

50°C or 90°F 

 

ALC= Ab, ALL 

÷

 110°C or 230°F 

 

when this temperature is reached and after the ALd delay time the HA alarm is enabled. 

 

ALL  Low temperature alarm setting:

 

 

ALC = rE , 0 

÷

 50 °C or 90°F 

 

ALC = Ab , - 50°C or -58°F 

÷

 ALU 

 

when this temperature is reached and after the ALd delay time, the LA alarm is enabled,. 

AFH Temperature alarm differential: 

(0,1÷25,5°C; 1÷45°F) Intervention differential for temperature 

alarm set point, always positive.

 

ALd  Temperature alarm delay:

 (0÷255 min) time interval between the detection of an alarm condition 

and the corresponding alarm signalling. 

dAO Delay of temperature alarm at start-up:

 (0min÷23h 50min) time interval between the detection 

of the temperature alarm condition after the instrument power on and the alarm signalling.

 

EdA  Alarm delay at the end of defrost: 

(0

÷

255 min) Time interval between the detection of the 

temperature alarm condition at the end of defrost and the alarm signalling. 

 

 

PROBE INPUTS 
Ot  Thermostat probe calibration: 

(-12.0

÷

12.0°C/ -21

÷

21°F) allows to adjust possible offset of the 

thermostat probe. 

OTHER 
PbC  Type of probe:

 it allows to set the kind of probe used by the instrument: 

PbC

 = PBC probe, 

ntC = 

NTC probe. 

rEL   Release software:

 (read only) Software version of the microprocessor. 

Ptb   Parameter table:

 (read only) it shows the original code of the 

dIXEL

 parameter map. 

Prd   Probes display: 

(read only) display the temperature. 

Pr2   Access to the protected parameter list 

(read only). 

 

 

6.

 

INSTALLATION AND MOUNTING 

Instruments 

XW40LS 

shall be mounted on vertical panel, in a 150x31 mm hole, and fixed using two 

screws 

 3 x 2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-

LX). The temperature range allowed for correct operation is 0 - 60 °C. Avoid places subject to strong 
vibrations, corrosive gases, excessive dirt or humidity. The same recommendations apply to probes. 
Let the air circulate by the cooling holes. 

 

6.1

 

CUT OUT 

 

165

150

31

+0.5

-0

+0

.5

-0

+1

-1

Ø3 x2

 

 

6.2

 

MOUNTING 

 

1

1

2

2

3

3

4

4

RG-LX gascke

(optional)

 

7.

 

ELECTRICAL CONNECTIONS 

The instruments are provided with Faston (2,8mm) to connect the analogue inputs. Relays and power 
supply have a Faston connection (6,3mm). Heat-resistant cables have to be used. Before connecting 
cables make sure the power supply complies with the instrument’s requirements. Separate the probe 
cables from the power supply cables, from the outputs and the power connections. Do not exceed the 
maximum current allowed on each relay, in case of heavier loads use a suitable external relay. 

N.B.

 Maximum current allowed for all the loads is 20A. 

 

7.1

 

PROBE CONNECTIONS 

The probe shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration. 
It is recommended to place the thermostat probe away from air streams to correctly measure the 
average room temperature.  

 

8.

 

USE OF THE PROGRAMMING “HOT KEY “ 

The Wing units can UPLOAD or DOWNLOAD the parameter list from its own E2 internal memory to the 

“Hot Key” 

and vice-versa. 

 

8.1

 

DOWNLOAD (FROM THE “HOT KEY” TO THE INSTRUMENT) 

1.

 

Turn OFF the instrument by means of the ON/OFF key, remove the TTL serial cable if present, 
insert the 

“Hot Key” 

and then turn the Wing ON. 

Reviews: