dixell Wing XW35L Installing And Operating Instructions Download Page 2

,QVWDOOLQJ DQG 2SHUDWLQJ ,QVWUXFWLRQV

6789: 9;<= >?9:@AB;;ABC@

6789: 9;<= >?9: @!AB;;"ABC@

1592009275  XW35L 8-40vdc GB r1.0 19.10.2004.doc

                           

D%EFG)H

2/4

4.

 

Use 

I

I

 or 

J

J

 to input the security code in the flashing digit; confirm the figure by pressing “

SET”.

The security code is “321“.

5.

 

If the security code is correct the access to “Pr2” is enabled by pressing “

SET” on the last digit.

Another possibility is the following: after switching ON the instrument the user can push Set and DOWN

keys within 30 seconds.

NOTE: each parameter in “Pr2” can be removed or put into “Pr1” (user level) by pressing “SET”  + 

J

J

.

When a parameter is present in “Pr1” LED 

 is on.

4.9

 

HOW TO CHANGE THE PARAMETER VALUE

1.

 

Enter the Programming mode.

2.

 

Select the required parameter with 

I

I

 or 

J

J

.

3.

 

Press the “

SET” key to display its value (

 and 

 LED starts blinking).

4.

 

Use 

I

I

 or 

J

J

 to change its value.

5.

 

Press “

SET” to store the new value and move to the following parameter.

To exit: Press SET + UP or wait 15s without pressing a key.

NOTE: the new programming is stored even when the procedure is exited by waiting the time-out.

4.10

 

HOW TO LOCK THE KEYBOARD

1. 

Keep the 

I

I

 and 

J

J

 keys pressed together for more than 3 s the 

I

I

 and 

J

J

 keys.

2. 

The “POF” message will be displayed and the keyboard is locked. At this point it is

only possible the viewing of the set point or the MAX o Min temperature stored and

to switch ON and OFF the light, the auxiliary output and the instrument.

TO UNLOCK THE KEYBOARD

Keep the 

I

I

 and 

J

J

 keys pressed together for more than 3s.

4.11

 

ON/OFF FUNCTION

By pushing the 

ON/OFF key, the instrument shows “OFF” for 5 sec. and the ON/OFF LED

is switched ON.

During the OFF status, all the relays are switched OFF and the regulations are stopped;

N.B. During the OFF status the Light button is active.

5.

 

PARAMETER LIST

REGULATION
Hy Differential: 
(0,1÷25,5°C; 1÷45°F): Intervention differential for set point, always positive.

Compressor Cut IN is Set Point Plus Differential (Hy). Compressor Cut OUT is when the

temperature reaches the set point.

LS Minimum set point limit: (-50,0°C

÷÷

SET; -58°F÷SET) Sets the minimum acceptable value for the

set point.

US Maximum set point limit: (SET

÷÷

110°C; SET÷230°F) Set the maximum acceptable value for set

point.

OdS Outputs activation delay at start up: (0÷255 min) This function is enabled at the initial start up of

the instrument and inhibits any output activation for the period of time set in the parameter. (Light

can work)

AC Anti-short cycle delay: (0÷30 min) interval between the compressor stop and the following restart.

CCt Thermostat override: (0min ÷23h 50min) allows to set the length of the continuous cycle. Can be

used, for instance, when the room is filled with new products.

Con Compressor ON time with faulty probe: (0÷255 min) time during which the compressor is active

in case of faulty thermostat probe. With COn=0 compressor is always OFF.

COF Compressor OFF time with faulty probe: (0÷255 min) time during which the compressor is off in

case of faulty thermostat probe. With COF=0 compressor is always active.

CH Type of action: CL = cooling; Ht = heating.

DISPLAY
CF Temperature measurement unit:
 °C = Celsius; °F = Fahrenheit. When the measurement unit is

changed the SET point and the values  of some parameters have to be modified.

rES Resolution (for °C): (in = 1°C; de = 0,1°C) allows decimal point display.

dE = 0,1°C; in = 1 °C

DEFROST
EdF Defrost mode:
 

in = interval mode. The defrost starts when the time “Idf” is expired.

Sd = Smartfrost mode. The time IdF (interval between defrosts) is increased only when the

compressor is running (even non consecutively) and only if the evaporator temperature is less than

the value in "

SdF” (set point for SMARTFROST).

IdF Interval between defrosts: (1÷120h) Determines the time interval between the beginning of two

defrost cycles.

MdF (Maximum) duration of defrost: (0÷255 min) When P2P = n, no evaporator probe, it sets the

defrost duration, when 

P2P = y, defrost end based on temperature, it sets the maximum length for

defrost.

dFd  Display during defrost:

rt = real temperature; it = temperature reading at the defrost start;

Set = set point; dEF = “dEF” label; 

dEG = “dEG” label;

dAd  Defrost display time out: (0

÷

255 min) Sets the maximum time between the end of defrost and the

restarting of the real room temperature display.

dPO First defrost after start-up:

= Immediately; n = after the IdF time

dAF  Defrost delay after fast freezing: (0min÷23h 50min)  after a Fast Freezing cycle, the first defrost

will be delayed for this time.

FANS
FnC Fan operating mode:

C-n = running with the compressor, OFF during the defrost;

C-y = running with the compressor, ON during the defrost;

O-n = continuous mode, OFF during the defrost;

O-y = continuous mode, ON during the defrost;

Fnd  Fan delay after defrost: (0÷255 min) The time interval between the defrost end and evaporator

fans start.

FSt Fan stop temperature: (-50÷110°C; -58÷230°F) setting of temperature, detected by evaporator

probe, above which the fan is always OFF.

ALARMS
ALC Temperature alarm configuration

rE = High and Low alarms related to Set Point

Ab = High and low alarms related to the absolute temperature.

ALU High temperature alarm setting:

ALC= rE, 0 

÷÷

 50°C or 90°F

ALC= Ab, ALL 

÷

 110°C or 230°F

when this temperature is reached and after the ALd delay time the HA alarm is enabled.

ALL Low temperature alarm setting:

ALC = rE , 0 

÷÷

 50 °C or 90°F

ALC = Ab , - 50°C or -58°F 

÷÷

 ALU

when this temperature is reached and after the ALd delay time, the LA alarm is enabled,.

AFH Temperature alarm differential: (0,1÷25,5°C; 1÷45°F) Intervention differential for temperature

alarm set point, always positive.

ALd Temperature alarm delay: (0÷255 min) time interval between the detection of an alarm condition

and the corresponding alarm signalling.

dAO Delay of temperature alarm at start-up: (0min÷23h 50min) time interval between the detection of

the temperature alarm condition after the instrument power on and the alarm signalling.

EdA  Alarm delay at the end of defrost: (0

÷

255 min) Time interval between the detection of the

temperature alarm condition at the end of defrost and the alarm signalling.

dot  Delay of temperature alarm after closing the door : (0

÷

255 min) Time delay to signal the

temperature alarm condition after closing the door.

doA  Open door alarm delay:(0÷255 min) delay between the detection of the open door condition and

its alarm signalling: the flashing message “

dA” is displayed.

tbA  Buzzer and alarm relay silencing: by pushing one of the keypad buttons.

n= Only the Buzzer is silenced;

y= Buzzer and relay are silenced.

nPS  Pressure switch number: (0 

÷

15) Number of activation of the pressure switch, during the “

did

interval, before signalling the alarm event (I2F= PAL).

If the nPS activations in the did time are reached, switch off and on the instrument to restart

normal regulation.

PROBE INPUTS
Ot Thermostat probe calibration: 
(-12.0

÷÷

12.0°C/ -21

÷÷

21°F) allows to adjust possible offset of the

thermostat probe.

HES Temperature increase during the Energy Saving cycle : (-30,0°C 

÷

 30,0°C / -22÷86°F) sets the

increasing value of the set point during the Energy Saving cycle.

DIGITAL INPUTS
odc Compressor status when open door:

no, Fan = normal;  CPr, F_C = Compressor OFF.

I2P Configurable digital input polarity:

CL : the digital input is activated by closing the contact;

OP : the digital input is activated by opening the contact

I2F Digital input operating mode: configure the digital input function:

EAL = generic alarm;  bAL = serious alarm mode; PAL = Pressure switch; dFr = Start defrost;

AUS = Not used; Es = Energy Saving; onF = remote On/OFF; dor = door switch

did  Time interval/delay for digital input alarm:(0

÷

255 min.) Time interval to calculate the number of

the pressure switch activation when I2F=PAL. If I2F=EAL or bAL (external alarms), “did” parameter

defines the time delay between the detection and the successive signalling of the alarm.

OTHER
PbC  Type of probe:
 it allows to set the kind of probe used by the instrument:

PbC = PBC probe, ntC = NTC probe.

rEL  Release software: (read only) Software version of the microprocessor.

Ptb  Parameter table: (read only) it shows the original code of the 

KML

NPORQ

 parameter map.

Prd   Probes display: (read only) display the temperature.

Pr2  Access to the protected parameter list (read only).

6.

 

DIGITAL INPUTS

The controllers have 1  free contact digital input. It is programmable in seven different configurations by

the “

I2F” parameter.

6.1

 

DOOR SWITCH INPUT  (I2F = dor)

It signals the door status and the corresponding relay output status through the “

odc” parameter:

no = normal (any change);

Fan = Fan OFF;

CPr = Compressor OFF;

F_C = Compressor and fan OFF.

Since the door is opened, after the delay time set through parameter “

dOA”, the alarm output is enabled

and the display shows the message “

dA”. The alarm stops as soon as the external digital input is

disabled again. During this time and then for the delay “

dot” after closing the door, the high and low

temperature alarms are disabled.

6.2

 

GENERIC ALARM (I2F = EAL)

As soon as the digital input is activated the unit will wait for “

did” time delay before signalling the “EAL

alarm message. The outputs status don’t change. The alarm stops just after the digital input is de-

activated.

6.3

 

SERIOUS ALARM MODE (I2F = BAL)

When the digital input is activated, the unit will wait for “

did” delay before signalling the “BAL” alarm

message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-

activated.