1592009211 XW10L-V GB r1.0 30.05.2011
XW10L – XW10V
4/4
10.3
ALARM RECOVERY
Probe alarm: “P1” (probe1 faulty), automatically stops 10s after the probe restarts normal operation.
Check connections before replacing the probe.
Temperature alarms “HA” and “LA” automatically stop as soon as the thermostat temperature returns
to normal values.
Door switch alarm “dA” stop as soon as the door is closed.
External alarms “EAL”, “BAL” stop as soon as the external digital input is disabled
Pressure switch alarm “PAL” alarm is recovered by switching OFF the instrument.
11.
TECHNICAL DATA
Housing: self extinguishing ABS.
Case
XW10L:
facia 38x185 mm; depth 76mm
XW10V:
facia 100x64 mm; depth 76mm
Mounting
XW10L: panel mounting in a 150x31 mm panel cut-out with two screws.
∅
3 x 2mm. Distance
between the holes 165mm
XW10L: panel mounting in a 56x72 mm panel cut-out with two screws.
∅
3x2mm. Distance
between the holes 40mm
Protection: IP20.
Frontal protection: IP65 with optional frontal gasket mod RG-L (XW40L); RGW-V (XW40V).
Connections: Screw terminal block
≤
2,5 mm
2
heat-resistant wiring and 6,3mm Faston
Power supply: 230Vac or. 110Vac
±
10%
Power absorption: 7VA max.
Display: 3 digits, red LED, 14,2 mm high.
Inputs: 1 NTC or PTC probe
Digital input: 1 free voltage
Relay outputs: Total current on loads MAX. 20A
compressor: relay SPST 20(8) A, 250Vac or. SPST 8(3) A, 250Vac
light: XW10L: relè SPDT 8(3) A, 250Vac; XW10V: relè SPST 16(6) A, 250Vac
Other output : alarm buzzer (optional)
Data storing: on the non-volatile memory (EEPROM).
Kind of action: 1B.
Pollution grade: normal
Software class: A.
Operating temperature: 0÷60 °C.
Storage temperature: -25÷60 °C.
Relative humidity: 20
÷
85% (no condensing)
Measuring and regulation range:
PTC probe: -50÷150°C (-58÷302°F)
NTC probe: -40÷110°C (-58÷230°F)
Resolution: 0,1 °C or 1°C or 1 °F (selectable).
Accuracy (ambient temp. 25°C): ±0,5 °C ±1 digit
12.
CONNECTIONS
Room
Probe
XW10V
Comp
Line
Ne
ut
ra
l
Light
19
12
5 6 7 8 9 10 11
2 3 4
17 18
20 21
Digital
Input
20A
250Vac
MAX
20A
16A
250Vac
Di
gi
ta
l i
np
.
Room
Probe
XW10L
20A
250Vac
MAX
20A
Comp
Li
ne
Ne
ut
ra
l
8A
250Vac
13 14 15 16
12
5 6 7 8 9 10 11
1 2 3 4
17
Luce
13.
DEFAULT SETTING VALUES
Label Name
Range
Default Level
REGULATION
°C/°F
Set Set
point
LS÷US
5/41 Pr1
Hy
Differential
0,1÷25,5 °C / 1÷45°F
2/4
Pr1
LS
Minimum set point
-50,0°C÷SET / -58°F÷SET -50/-58 Pr2
US
Maximum set point
SET ÷ 110°C / SET ÷
230°F
110/230
Pr2
OdS
Outputs activation delay at start up
0÷255 min.
0
Pr2
AC
Anti-short cycle delay
0÷30 min.
1
Pr1
CCt
Compressor ON time during fast freezing
0 ÷ 23h 50 min.
0.0
Pr2
COn
Compressor ON time with faulty probe
0÷255 min.
15
Pr2
COF
Compressor OFF time with faulty probe
0÷255 min.
30
Pr2
CH
Type of regulation
CL, Ht
CL
Pr2
DISPLAY
CF
Temperature measurement unit
°C ÷ °F
°C/F
Pr2
rES
Resolution (integer/decimal point)
in ÷ de
dE/-
Pr1
ALARMS
ALC
Temperature alarms configuration rE÷Ab
Ab
Pr2
ALU
MAXIMUM temperature alarm -50,0÷110°C/
-58÷230°F
110/230
Pr1
ALL
minimum temperature alarm
-50,0÷110°C/ -58÷230°F -40/-40
Pr1
AFH
Temperature alarm differential
0,1÷25,5 °C / 1÷45°F
2/4
Pr2
ALd
Temperature alarm delay
0÷255 min.
15
Pr2
dAO
Delay of temperature alarm at start up
0 ÷ 23h 50 min.
1,3
Pr2
dot
Delay of temperature alarm after closing the
door
0÷255 min.
15
Pr2
dOA
Open door alarm delay
0÷255 min.
15
Pr2
nPS
Pressure switch number
0÷15
0
Pr2
ANALOGUE
INPUTS
Ot
Thermostat probe calibration
-12,0÷12,0°C / -21÷21°F
0/0
Pr1
HES Temperature
increasing during the Energy
Saving cycle
-30÷30°F/-54÷54°F 0/0 Pr2
DIGITAL INPUTS
Odc
Open door control
no, Fan, CPr, F_C
no
Pr2
I2P
Configurable digital input polarity
CL÷OP
CL
Pr2
i2F
Digital input configuration
dor, EAL, bAL, PAL, dFr,
AUS, ES, OnF
dor Pr2
dId
Digital input alarm delay
0÷255 min.
5
Pr2
OTHER
Pbc
Kind of probe
PbC, ntc
ntc/Ptc
Pr2
rEL
Software release
- - -
2.0
Pr2
Ptb
Map code
- - -
- - -
Pr2
Prd
Probes display
Pb1
- - -
Pr2
Pr2
Access parameter list
- - -
- - -
Pr1