35
Carel Easy Series
Parameter
Min.
Max.
Def.
UOM
PS
PASSWORD
0
99
22
-
/
PROBE PARAMETERS
/5
Select °C / °F ( 0 = °C; 1 = °F)
0
1
0
-
/6
Disable decimal point (1 = disabled)
0
1
1
-
/C1
Probe calibration (OFFSET)
-50.0
50.0
1.8
°C/°F
r
CONTROL PARAMETERS
St
Setpoint (control temperature)
-50.0
90.0
-45.0
°C/°F
rd
Control differential (hysteresis)
0.0
19.0
3.0
°C/°F
r1
Minimum set point value
-50.0 90.0
-20.0 °C/°F
r2
Maximum set point value
-50.0 90.0
-20.0 °C/°F
c
COMPRESSOR PARAMETERS
c0
Comp. and fan start delay after start-up
0
100
0
min
c1
Min. time between successive comp. starts
0
100
3
min
c4
Compressor safety (duty setting)
0
100
15
min
d
DEFROST PARAMETERS
d0
Type of defrost (0 and 1= defrost by temperature; 2, 3 and
4= defrost by time)
0
4
2
-
dI
Interval between defrosts
0
199
6
h/min
dP
Max. or effective defrost duration
1
199
0
min/s
d4
Defrost when the instrument is switched on (1= activated)
0
1
0
-
d6
Disable temperature display during defrost (1= display disabled)
0
1
1
-
A
ALARM PARAMETERS
A0
Alarm differential
-20.0
20.0
10.0
°C/°F
AL
Low temperature alarm threshold/deviation
-50.0
250.0
-50.0
°C/°F
AH
High temperature alarm threshold/deviation
-50.0
250.0
250.0
°C/°F
Ad
Low and high temperature alarm delay
0
199
199
min
H
OTHER SETTINGS
H2
Enable keypad
0= keypad disabled
1= keypad enabled
2= keypad enabled except for ON/OFF function
0
2
1
-
EY
Restore the Default settings
0
1
0
-