dIXEL

 

Operating instructions 

1592001620 

 

1592001620 XC450D GB R1.0 10.07.2009 

XC450D 

3/3 

did 

LL  liquid  alarm  delay: 

0  ÷  255  min.  Delay  between  the  detection  of  the  LL 

liquid alarm condition and its signalling.

 

iP4 

Alarm stop polarity from pressure switch: oP

: the digital input is activated by 

opening the contact; 

CL

: the digital input is activated by closing the contact. 

iP5 

By-pass input polarity:

 

oP

: the digital input is activated by opening the contact; 

CL

: the digital input is activated by closing the contact. 

ALIP 

Alarm input for compressors and fans polarity  

 

oP

: the digital input is activated by opening the contact;  

 

CL

: the digital input is activated by closing the contact. 

COMPRESSORS REGULATION 

 
Pbd

 

Proportional band or neutral zone width

 (0.10÷10.0 bar). The band (or zone) 

is  symmetrical  compared  to  the  target  set  point,  with extremes: SET-Pbd/2 and 
SET+Pbd/2. 

Onon 

Minimum time between 2 following switching ON of the same compressor

 

(0÷255min). 

oFon 

Minimum  time  between  the  switching  off  of  a  compressor  and  the 
following switching on

 (0÷255min)  

don 

Time  delay  between  the  insertion  of  two  different  compressors 

(0÷99.5 

min; ris. 10s). 

doF 

Time  delay  between  switching  off  of  two  different  compressors

  (0÷99.5 

min; ris. 10s). 

odo 

Count time with by-pass input ON 

(0÷255min) 

LSE 

Minimum set point for compressors. 

 

HSE 

Maximum set point for compressors

ALARMS – COMPRESSOR SECTION 

PAo:  

Alarm  probe  exclusion  at  power  on.

  it  is  the  period  starting  from  instrument 

switch on, before an alarm probe is signalled. (0÷255 min). During this time if the 
pressure is out of range all the compressor are switched on. 

LAL

:  

Low  pressure  (temperature)  alarm

:  The  measurement  unit  depends  on  dEU 

parameter.  It’s  always  subtracted  to  the  set point. W hen the value 

SET-LAL

 is 

reached the A03C alarm is enabled, (possibly after the 

tAo

 delay time). 

HAL

High  pressure  (temperature)  alarm

:  The  measurement  unit  depends  on  dEU 

parameter.  It’s  always  added    to  the  set  point.  W hen  the  value  SET+HAL  is 
reached the A04C alarm is enabled, (possibly after the 

tAo

 delay time). 

tAo

:  

Low  and  High  pressure  (temperature)  alarms  delay

:  (0÷255  min)  time 

interval  between  the  detection  of  a  pressure  (temperature)  alarm  condition  and 
alarm signalling.

 

SPr

:   

Number of steps engaged with faulty probe

. (0÷#compr). 

OTHER 

tbA  

Alarm relay silencing: 

by pushing one of the keypad buttons. 

no

= alarm relay 

stays on; 

yES

=

 

alarm relay is switched off by pushing any keys. 

OAP 

Alarm  relay  output  polarity:    cL=

closed  when  activated; 

oP= 

opened

 

when 

activated 

oFF  

Switching ON/OFF enabling  from keyboard: 

(

no

 = disabled; 

yES

= enabled) 

It  permits  the  switching  ON/OFF  of  the  instrument  by  pressing the SET key for 
more than 4s.

 

Ad1

:  

Compressors address

  (1 –247)  It is used in monitoring system. 

Ad2

:  

Fans address

  (1 –247)  It is used in monitoring system. 

Ptb 

Parameter table code

: readable only. 

rEL 

Software release

 for internal use. 

Pr2  

Access to the protected parameter list 

(read only).

 

TYPE OF REGULATION 

-  OFF: 

the  instrument  doesn’t  make  the regulation; it detects the LL liquid alarm and the 

P1 broken transducer.

 

-  REGULATION  ON:   

when  the  digital  input  is  activated  or  set  manually  by  pushing the 

DOW N key for 3s. Compressors  depends on th SetC and Pbd parameters. 

 

-  RESET  REGULATION ON: 

turning off and on the controller, or with DOW N key during 

3”.

 

 

Functioning mode:  

 

rtY=db neutral zone

: If the pressure (temperature) is inside this zone the controller 

maintains the same number of loads switched on and off, without changing anything. 
W hen the pressure (temperature) go out from the zone, regulation starts. 

 

rtY=Pb proportional band

: The regulation band (Pbd) is divided into as many parts 

as there are stages. The numbers of stages switched ON is proportional to the value 
of the input signal: when this distances itself from the target set point and enters the 
various bands, the compressors are switched ON, to be then turned OFF when the 
signal brings near the set point. In this way if the pressure is greater than regulation 
band,  all  the  compressors  are  on,  if  the  pressure  (temperature)  is  lower  than  the 
regulation band all the compressors are off. 

SAFETY TIMES 

 

A load is turned ON only if the safety times onon, oFon, donF are over. 

Regulation stops when the pressure (temperature) come back into the neutral zone. 

CONFIGURATION AND ALARM DIAGNOSTICS  

 
DIGITAL INPUTS FOR COMPRESSOR SAFETY 
ALIP:

 It establishes if the input is activated by closing (ALIP=cL) or by opening (ALIP=oP) 

the id1, id2, id3 contacts. 

 

Actions  

Every time one input is activated the corresponding output is turned off.  

P1 probe failure alarm 

It is generated by failure in the transducer. 

SPr

: number of steps engaged with faulty probe. 

 

It is an alarm signal with the activation of: relay, buzzer and P1 and P2 code display.  

 

Recovery 

Automatic as soon as probe restarts working. 

HA, LA: LA2 High and low pressure (temperature) alarms 

This  alarm  signals  that  the  pressure  (temperature)  is  out  of  limits  established  by 
parameters LAL – SetC+ HAL. 
The 

tAo 

and 

AFd 

parameters set the delay between alarm condition and alarm signalling. 

 

Action

 

The alarm is signalled with standard action. The outputs are unchanged. 

ALARM MUTING 

 

Press any buttons to silence the buzzer during an alarm condition. 
Hold pressed for more than 3 seconds switch off the alarm relay during an alarm condition 

PARAMETERS – DEFAULT VALUES 

Name 

bar  Level  Description 

Range 

SEtc 

3.0  -- 

Set Point for pressure 

LSE ÷ HSE 

oA4 

Cpr  Pr2 

Output 4 configuration 

cPr / FAn / StP / ALr / Lin / 
nu/Liq/MAn 

oA5 

Cpr  Pr2 

Output 5 configuration 

cPr / FAn / StP / ALr / Lin / 
nu/Liq/MAn 

oA6 

Cpr  Pr2 

Output 6 configuration 

cPr / FAn / StP / ALr / Lin / 
nu/Liq/MAn 

rtY 

db  Pr2 

Type of regulation 

db, pb 

StY 

yES  Pr2 

Compressor rotation 

no / YES 

PA04 

0,5  Pr2 

Adjustment of  read out for the Probe at 4mA 

0.0 bar  ÷ PA20 

PA20 

8,0  Pr2 

Adjustment of  read out for the Probe at 20mA  PA04 ÷ 51.0 bar  

cAL 

0  Pr2 

Probe 1 calibration 

-12.0 ÷ 12.0 

 

   

DIGITAL INPUTS 

 

i1C 

CL  Pr2 

Liquid alarm polarity 

oP / cL 

did 

60  Pr2 

Liquid alarm signalling delay 

0 ÷ 255 min. 

iP4 

CL  Pr2 

Alarm stop polarity from pressure switch 

oP / cL 

iP5 

CL  Pr2 

By-pass input polarity 

oP / cL 

ALiP 

CL  Pr2 

Alarm input for compressors and fans polarity 

oP / cL 

 

   

REGULATION 

 

Pbd 

0.6  Pr2 

Proportional band of compressors 

> 0 ÷ 10.0 bar  

onon 

5  Pr2 

Minimum time between 2 following switching 
ON 

0 ÷ 255 min. 

oFon 

2  Pr2 

Minimum time between the switching off and 
on 

0 ÷ 255 min. 

don 

0,3  Pr2 

Time delay between the insertion of two 
different compressors 

0 ÷ 99.5 min.( res. 10 “) 

doF 

0,1  Pr2 

Time delay between switching off of two 
different compressors 

0 ÷ 99.5 min. (res.10”. ) 

odo 

10  Pr2 

Regulation delay on start-up 

0 ÷ 255 minuti 

LSE 

0,5  Pr2 

Minimum set point for compressors 

PA04 ÷ HSE 

HSE 

4,0  Pr2 

Maximum set point for compressors 

LSE ÷ PA20 

 

   

PRESSURE ALARMS 

 

PAo 

30  Pr2 

Alarm probe exclusion at power on 

0 ÷ 255 min. 

LAL 

10  Pr1 

Low pressure (temperature) alarm – 
compressor section 

> 0 ÷ 30.0 bar  

HAL 

10  Pr1 

High pressure (temperature) alarm– 
compressor section 

> 0 ÷ 30.0  

tAo 

10  Pr1 

Low and High pressure (temperature) alarms 
delay– compressor section 

0 ÷ 255 min. 

SPr 

2  Pr2 

Number of steps engaged with faulty probe 

0 ÷ oA6 

tbA 

no  Pr2 

Alarm relay silencing 

no / YES 

OAP 

cL  Pr2 

Alarm relay output polarity 

oP ÷ cL 

 

   

OTHER 

 

oFF 

Yes  Pr2 

Switching ON/OFF enabling  from keyboard 

no / YES 

Ad1 

1  Pr2 

Serial address 

1 ÷ 247 

rEL 

-  Pr2 

Release micro 

readable only 

Ptb 

-  Pr2 

Parameter table code 

readable only

 

Pr2 

   Pr1 

Password protected menu 

readable only

 

 

 