dIXEL

 

Operating instructions 

1592001620 

 

1592001620 XC450D GB R1.0 10.07.2009 

XC450D 

2/3 

KEYBOARD 
SET

 

to see or modify the pressure set point (ON only during regulation mode) and for 
parameters. 

n

 (GIÙ) by holding it pressed for 3s, the regulation is enabled or disabled; it decreases 

the displayed values. 

 

o

 (SU)  to enter the alarm menu; it increases the displayed values. 

e

 CLOCK to enter the maintenance menu. 

 

KEY COMBINATIONS 

o

 

+  

n



To lock and unlock the keyboard. 

SET + 

n

  To enter the programming mode. 

SET + 

o

 

To exit the programming mode or the alarm menu. 

 

FUNCTIONING DURING OFF STATUS 

W hen  the  display  is  OFF,  the  controller  checks  only  the  LL  liquid  level  alarm,  the  P1 
pressure transducer status if absent, broken or when the pressure is out of scale.  

REGULATION  

HOW TO SET THE PRESSURE SET 

 

 

 

Instrument  in  regulation  mode  (Regulation  ON: push for 3sec 
the DOW N key) 

 

1) 

Push and release the 

SET 

key

2) 

The  Lower  display  will  show  the 

“SEtC” 

label,  the 

Upper display will show the pressure value

.  

3) 

To change the Set value push the 

or 

n

 

4) 

To  memorise  the  new  value  push  and release the 

SET 

key

 

within 30s. 

 

(

Regulation stop

: push for 3sec the DOW N key) 

 

HOW TO LOCK AND UNLOCK THE KEYBOARD 

 

1. 

 

Keep  pressed  for  more  than  3  s  the  [

o

 

and 

n

]  keys.  The 

“POF”  message  will  be  displayed  and  the  keyboard  will  be 
locked. 

2. 

 

At  this  point  it  will be possible only to see the set point, enter 
the alarm menu, see the alarm and hours menu. 

3.   Keep pressed together for more than 3s the [

o

 

and 

n

 ] keys 

to  unlock  the  keyboard,  till  the 

“Pon” 

message  will  be 

displayed.  

 

MESSAGES AND ALARMS 

 

Code 

Description 

Cause 

Action 

Reset 

OFF 

Controller in 

stand by  

“By  pass”  digital  input 
de-activated 

 

 

P1 

P1 probe 

failure alarm 

Probe  failure  or  out of 
range 

The  compressor  outputs 

are  activated  according 
to  CPP,  SPr  o  PoPr 
parameters 

Automatically  as  soon  as  the 
probe restarts working. 

EA1 
EA2 
EA3 

Input safeties 

alarm  

The 

corresponding 

digital  input  is  turned 
on. 

The  corresponding  output 
is turned off. 

Automatically  as  soon  as  the 
digital input is turned off.  
 

LA 

Minimum 

suction alarm 

Pressure  lower  than 
[SetC  –  LAL]  value 
after the tAo delay 

Signalling only 

Automatically:    as  soon  as  the 
pressure  or  temperature  reaches 
the    SetC-LAL+  differential  value 
(0.3bar o 1°C) 

HA 

Maximum 

suction alarm 

Pressure  higher  than 
[SETC+HAL] 

value 

after the tAo delay 

Signalling only 

Automatically:    as  soon  as  the 
pressure  or  temperature  reaches 
the (SetC+HAL - differential) value 
(0.3bar o 1°C) 

Pon 

Keyboard 

unlocked 

Press  together  for  3” 
the UP+DOWN keys 

Press  together  for  3”  the 
UP+DOWN keys  

The  POF  message  will  be 
displayed and the keyboard will be 
locked  

PoF 

Keyboard 

locked 

Press  together  for  3” 
the UP+DOWN keys 

Press  together  for  3”  the 
UP+DOWN keys 

The  “POn”  message  will  be 
displayed and the keyboard will be 
unlocked  

A12 

Wrong 

configuration 

Wrong  programmation 
of some resources  

Parameters check 

Automatic 

PARAMETERS PROGRAMMING 

 

 

 
 

 

 

TO  ENTER  THE  Pr1  PARAMETER  LIST

:  Hold  pressed  the 

[SET + 

n

]

 key for 3 s. 

 
TO ENTER THE Pr2 PARAMETER LIST

Select with the [

n

] key the 

Pr2 

parameter and press the 

SET 

key. 
1) 

The flashing value “0 --” is displayed on the upper display.  

2) 

Insert  the  password 

321

  using the 

o

 

and 

n

 

key and 

press SET. 
 

To exit

: Press 

SET + UP 

or wait 30s without pressing a key. 

NOTE

:  the  set  value  is  stored  even  when  the  procedure  is 

exited by waiting the time-out to expire.

 

HOW TO CHANGE PARAMETER VALUES 

1.  Enter the Programming mode. 
2.  Select the required parameter with 

o

 or 

n

3.  Press the “

SET

” key the value start blinking. 

4.  Use 

o

 or 

n

 to change its value. 

5.  Press “

SET

” to store the new value and move to the following parameter. 

 

HOW TO USE THE HOT KEY 

HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD) 

1. 

Program one controller with the front keypad. 

2. 

W hen  the  controller  is  ON,  insert  the  “

Hot  key

”  and  push 

o

  key;  the   

"uPL" 

message appears followed a by flashing 

“End”

 

3. 

Push “

SET”

 key and the 

End

 will stop flashing. 

4. 

Turn OFF the instrument remove the 

“Hot Key”, 

then turn it ON again. 

 

NOTE

: the “

Err

” message is displayed for failed programming. In this case push again 

o

 

key if you want to restart the upload again or remove the “

Hot key

” to abort the operation. 

HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY (DOWNLOAD) 

 

1. 

Turn OFF the instrument. 

2. 

Insert  a 

programmed  “Hot  Key”  into  the  5  PIN  receptacle 

and  then  turn  the 

Controller ON. 

3. 

Automatically the parameter list of the 

“Hot Key”

 is downloaded into the Controller 

memory, the “

doL

” message is blinking followed a by flashing 

“End”.

 

4. 

After 10 seconds the instrument will restart working with the new parameters.  

5. 

Remove the 

“Hot Key”

 

NOTE 

the message “

Err

” is displayed for failed programming. In this case turn the unit off 

and then on if you want to restart the download again or remove the “

Hot key

” to abort the 

operation. 
The unit can UPLOAD or DOW NLOAD the parameter list from its own E2 internal memory 
to the 

“Hot Key” 

and vice-versa. 

 

LIST OF PARAMETERS 

PLANT DIMENSIONING AND TYPE OF REGULATION 

oA4, oA5, oA6 Configuration of 3 relays:

  

Each  relay  according  to  the  configuration  of  the  oA4,  oA5  and  oA6   parameter can work 
as: 

cPr

 

Compressor 

 

StP 

Compressor valve 

 

FAn 

Fan 

Not used 

ALr 

Alarm 

 

nu 

Not used 

Not used 

Lin 

Not used 

Not used 

Ali 

Only liquid alarm 

Not used 

Man 

Manual regulation 

Not used 

 

PLANT CONFIGURATION EXAMPLE: 

Plant with 3 compressors: 

 

[oA1 = Liq,]    fixed 

 

[oA2 = Man]   fixed 

 

[oA3 = nu]      fixed 

 

oA4 = Cpr, 

 

oA5 = Cpr, 

 

oA6 = Cpr. 

 

 

rty

Type of regulation: db

 = neutral zone, 

Pb

 = proportional band. 

Sty

Activation  type  of  sequence  for  compressors:  YES

  =  rotation:  this  algorithm 

distributes the working time between the various loads to ensure even run times. 

no

 = 

fixed  sequence:  the  compressors  are  enabled  and  disabled  in  fixed  sequence:  first, 
second etc. 

PRESSURE TRANSDUCER 

PA04 

Pressure value corresponding to  4 mA   

(0 ÷ PA20 bar). Minimum transducer 

pressure value (absolute value). 

PA20

 

Pressure  value  corresponding  to  20  mA  for  probe  1

  (PA04÷51.0  bar). 

Maximum pressure value (absolute value). 

CAL

 

Suction pressure calibration

 (-12.0÷12.0 bar). 

 
!PAY ATTENTION TO THE TRANSDUCER SETTING! 
The instrument automatically converts the pressure into relative pressure

.  

For  PP07  pressure  transducers  (-0,5÷7.0bar  or  0.5..8.0bar)  is  set  [PA04=0.50  and 
PA20=8.00]  and  for  PP11  pressure  transducers  (-0,5÷11.0bar  or  0.5..12.0bar)  is 
[PA04=0.50 e PA20=12.00], with 0÷30bar pressure transducer is [ PA04=1 e PA20=31].  

DIGITAL INPUT CONFIGURATION 

i1C 

Liquid alarm polarity

oP

: the digital input is activated by opening the contact; 

CL

: the digital input is activated by closing the contact.

 