dIXEL

 

Operating instructions 

1592001620 

 

1592001620 XC450D GB R1.0 10.07.2009 

XC450D 

1/3 

SAFETY STEP CONTROLLER 

 

XC450D 

GENERAL WARNING 

PLEASE READ BEFORE USING THIS MANUAL 

 

This manual is part of the product and should be kept near the instrument for easy and 
quick reference. 

 

The  instrument  shall  not  be  used  for  purposes  different  from  those  described 
hereunder. It cannot be used as a safety device. 

 

Check the application limits before proceeding. 

 SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do  not expose to water or moisture: use the controller only within the operating limits 
avoiding  sudden  temperature  changes  with  high  atmospheric  humidity  to  prevent 
formation of condensation. 

 

W arning: disconnect all electrical connections before any kind of maintenance. 

 

The instrument must not be opened. 

 

In  case  of  failure  or  faulty  operation  send  the  instrument  back  to  the  distributor or to 
“DIXELL S.r.l.” (see address) with a detailed description of the fault. 

 

Consider  the  maximum  current  which  can  be  applied  to  each  relay  (see  Technical 
Data). 

 

Ensure  that  the  wires  for  probes,  loads  and  the  power  supply  are  separated  and  far 
enough from each other, without crossing or intertwining. 

 

Fit the probe where it is not accessible by the end user. 

 

In  case  of  applications  in  industrial  environments,  the  use  of  mains  filters  (our  mod. 
FT1) in parallel with inductive loads could be useful. 

GENERAL DESCRIPTION 

 

XC450D

 is a safety step controller with 3 setps 

that  excludes  the  main regulator when it has a 
fault. It detects the compressor status by a free 
voltage  digital  input  that  is  activated  after  a 
settable  delay.  It  manages  a  relay  that 
excludes  the  main  regulator  of the compressor 
rack  and  starts  the  safety  regulation.  It  is 
provided  with  pressure  transducer  input,  4÷20 
mA,  while  the  regulation  is  performed  by three 
relays. 
It  has  a  HP  digital  input,  and  a  liquid  level 
digital  input  both  of  them  free  voltage, 
Furthermore  the  safeties  of  each  compressor 
can  be  connected  to  a  dedicated  free  voltage 
digital inputs. 
By  means  of  the  HOT  KEY  the  controller  can 
be easy programmed at power on. 
The  controller  can  be connected to the XJ500, 
controlling  and  monitoring  system,  thanks  to 
the  serial  TTL  output,  using  the  standard 
ModBus RTU protocol.

 

 

TECHNICAL FEATURES 

Housing: 

Self extinguishing ABS. 

Case: 

4 DIN modules 70x85 mm; depth 61mm

 

Mounting

: DIN RAIL 

 

Protection:

 IP20 

Display

: upper display 3 digits with d.p. lower display 4 digits with d.p. 

Connections:

 Screw terminal block 

 2,5 mm

2

 heat-resistant wiring. 

Power supply

: 120Vac 

 10%,50-60Hz or  230Vac 

 10%,50-60Hz or 24Vac 

Power absorption

: 5VA max; 

Probe input

: for 4÷20mA signals. 

Digital inputs

: 6 free voltage.  

Data storing:

 on the non-volatile memory (EEPROM). 

Relay outputs

: 6 relays SPDT 8(3) A, 250Vac. 

Operating temperature: 

0÷60 °C.; 

Storage temperature

: -30÷85 °C. 

Relative humidity:

 20

85% (no condensing). 

Measuring range

: -40÷110 °C (- 40÷230 °F) or 4÷20mA; 

Resolution

: 0.1 °C or 1°F (selectable);  

Accuracy (ambient temp. 25°C)

:  ±0,7 °C ±1 digit. 

 

WIRING CONNECTIONS 

 

 

Probes 
4-20mA: 

use terminals 9(+) 11(in)

  

MOUNTING & INSTALLATION 

MOUNTING 

The

  XC450D 

shall be mounted on an omega DIN rail. The temperature range allowed for 

correct  operation  is  0÷60  °C.  Avoid  places  subject  to  strong  vibrations,  corrosive  gases, 
excessive dirt or humidity. The same recommendations apply to probes. Let air circulate by 
the cooling holes. 

ELECTRICAL CONNECTIONS 

The  controller  is  provided  with  screw  terminal  blocks  for  wires  having  section  not  bigger 
than 2.5 mm

2

 

Check power supply data before connection wires.  
Keep the probe and the digital input wires separate from the power cable.

  

Do not exceed the maximum rating current for each relay, check technical data  and if the 
load is bigger, use filtered contactors. 
Before  connecting  cables  make  sure  the  power  supply  complies  with  the  instrument’s 
requirements.  Separate  the  input  connection  cables  from  the  power  supply  cables,  from 
the outputs and the power connections. 

Do not exceed the maximum current allowed 

on each relay

, in case of heavier loads use a suitable external relay. 

PRESSURE TRANSDUCERS 

Pressure probe (4 - 20 mA)

: respect the polarity. If using terminal ends be sure there are 

no  bear  parts  which  could  cause  short  circuiting  or  introduce  noise  disturbance  at  high 
frequencies.  To  minimise  the  induced  disturbances  use  shielded  cables  with  the  shield 
connected to earth.  

RS485 SERIAL LINE 

All models can be integrated into the  W EB monitoring and supervising systems using the 
TTL  serial  port.  They  use  the  standard  ModBus  RTU  protocol,  so  they  can  be fitted in a 
system  integrator  using this protocol. Check the product library presence if the version is 
previous to this model. 

XJ485CX INTERFACE 

 

Interface:

 XJ485CX 

 
Colour:

 orange 

 
Code

: XJ485CX-00000  + CAB/RS 0.2MT 

(with 20cm cable). 

 

USER INTERFACE  

 

Upper display

: OFF when the regulation 

is disabled. Pressure probe value during 
regulation mode. 

Lower display

: delay time when the digital 

input is ON. 

1-2-3 Icons

: loads output if set as 

compressor. Flashing with call delay.  

°C /°F

: temperature value 

Bar/Kpa/PSI

: pressure value 

Spanner

: maintenance menu for 

loads time 

 

Open book

: alarm storing 

 Alarm is happening 